Manual Page 1 of 19 AL-602-03-902 EnoPuck BASIC Desk Sensor with vibration and PIR sensor EnOcean 902 MHz Part no. 12408 Version 1.1.02, valid since FW/HW 1.0 / 2.0 © DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61 06.07.2021 Hauptstraße 76, 32479 Hille Tel: +49 5734 51466 - 0 Technical data might change info@deuta-controls.de; www.deuta-controls.
AL-602-03-902 EnoPuck BASIC Product manual Page 2 of 19 © 2021 DEUTA Controls GmbH All rights reserved This Manual, including all figures and illustrations, is copyright-protected. Any further use of this Manual by third parties that violate pertinent copyright provisions is prohibited. Reproduction, translation, electronic and phototechnical filing/archiving (e.g., photocopying) as well as any amendments require the written consent of DEUTA Controls GmbH, Bergisch Gladbach, Germany.
AL-602-03-902 EnoPuck BASIC Product manual Page 3 of 19 Table of contents 1 Validity of this documentation ......................................................................................... 5 2 Intended use .................................................................................................................. 5 3 Disposal ......................................................................................................................... 6 4 Device description ................
AL-602-03-902 EnoPuck BASIC Product manual Page 4 of 19 8 Safety remarks ..............................................................................................................14 9 Device labels .................................................................................................................15 10 FCC (United States) Regulatory Statement ...............................................................16 11 ISED Regulatory Statement ..............................................
AL-602-03-902 EnoPuck BASIC Product manual Page 5 of 19 1 Validity of this documentation This documentation is only applicable to the product AL-602-03-902 EnoPuck BASIC and is only applicable starting from products with FW/HW Version 1.0/2.0. The device must only be installed and operated according to the instructions in these operating instructions.
AL-602-03-902 EnoPuck BASIC Product manual Page 6 of 19 3 Disposal Electrical and electronic equipment may not be disposed of with household waste. This also applies to products without this symbol. Electrical and electronic equipment contain materials and substances that can be harmful to the environment and health. Electrical and electronic equipment must be disposed of properly after use. Note only for EU: WEEE 2012/19/EU applies throughout Europe. Directives and laws may vary nationally.
AL-602-03-902 EnoPuck BASIC Product manual 4.3 Page 7 of 19 Observe intended use The AL-602-03-902 EnoPuck BASIC must not be used in any relation with equipment that supports, directly or indirectly, human health or life or with applications that can result in danger for people, animals or real value. 4.4 Observe statutory provisions for operating frequency range.
AL-602-03-902 EnoPuck BASIC Product manual Page 8 of 19 5 Technical data 5.1 Communication / EnOcean wireless interface Type EnOcean Number 1 Transmit / receive center frequency 902.875 MHz Maximum transmission power +99 dBµV/m Table 1: Technical data / communication 5.2 Sensor: Vibration sensor Measuring range ±8g Sensitivity 0,05 g Table 2: Technical data / vibration sensor 5.
AL-602-03-902 EnoPuck BASIC Product manual 5.6 Page 9 of 19 Power supply Power supply voltage 2x AA, 1,5V internal batteries Power consumption Typ. 1 mW, 50 µA standby Table 6: Technical data / power supply 5.7 Environmental conditions Operating temp. 0..50 °C Storage temp. -20 ..+70 °C Rel. humidity 0..99 % rel. humidity, non condensing Protection class IP20 Table 7: Technical data / environmental conditions 5.
AL-602-03-902 EnoPuck BASIC Product manual Page 10 of 19 6 Functional description in detail 6.1 Events and messages Vibration and motion are monitored in parallel by the AL-602-03-902 EnoPuck BASIC. The events are handled with the same priority, whatever will happen first. 6.1.1 Detect vibrations The EnoPuck BASIC continuously monitors the environment by the PIR sensor on top of the housing.
AL-602-03-902 EnoPuck BASIC Product manual 6.2 Page 11 of 19 Table of supported EEP’s (EnOcean Equipment Profiles) 6.2.1 Transmit / TX The EnOcean wireless standard defines so called EnOcean Equipment Profiles (EEP). Each EnOcean based product sends and receives data according to at least one standardized data format. The EnoPuck BASIC transmits data described as follows: Cons. nr.
AL-602-03-902 EnoPuck BASIC Product manual Page 12 of 19 Offset Size Bitrange Data Shortcut 24 4 DB0.7…DB0.4 Not used (= 0) 28 1 DB0.3 LRN bit 29 2 DB0.2…DB0.1 Not used (= 0) 31 1 DB0.
AL-602-03-902 EnoPuck BASIC Product manual Page 13 of 19 6.2.2 Receive/ RX The EnoPuck BASIC only sends EnOcean telegrams. No data is received / interpreted. Cons. Nr. EEP - - © DEUTA Controls GmbH Description - Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61 06.07.2021 Hauptstraße 76, 32479 Hille Tel: +49 5734 51466 - 0 Technical data might change info@deuta-controls.de; www.deuta-controls.
AL-602-03-902 EnoPuck BASIC Product manual Page 14 of 19 7 Service / changing batteries Caution: When opening the device, you have to take care of electrostatic discharge. Otherwise, electronics will be damaged. In case of discharged batteries, they can be replaced with two new AA batteries, 1,5 V. You have to remove carefully the four screws on the backside of the EnoPuck BASIC (Tool: Bit T6). Do not touch any electronic components, since you could damage the device.
AL-602-03-902 EnoPuck BASIC Product manual Page 15 of 19 Keep new and used batteries away from children. 9 Device labels The following labels are placed on the bottom side of the EnoPuck BASIC: IC FCC ID: 2AZTH-AL-602-03-902 IC: 27242-60203902 PMN: AL-602-03-902 FVIN: 1.0 HVIN: 2.0 RoHS AL-602-03-902/EnoPuck Basic PN: 12408 2 x Bat Typ AA Made in Germany DEUTA Controls GmbH FT Paffrather Straße 140 51465 Bergisch Gladbach Germany SN: xxxxx © DEUTA Controls GmbH HV QS PG Paffrather Str.
AL-602-03-902 EnoPuck BASIC Product manual Page 16 of 19 10 FCC (United States) Regulatory Statement This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation.
AL-602-03-902 EnoPuck BASIC Product manual Page 17 of 19 12 Dimensions / drawings Diameter: 100 mm; Height: approx. 28 mm+ 7 mm lens cover if mounted © DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61 06.07.2021 Hauptstraße 76, 32479 Hille Tel: +49 5734 51466 - 0 Technical data might change info@deuta-controls.de; www.deuta-controls.
AL-602-03-902 EnoPuck BASIC Product manual Page 18 of 19 13 Ordering information Part name Part nr. Description Table sensor, EnoPuck BASIC, EnOcean 902 MHz, sensors for vibration and PIR detector; AL-602-03-902 EnoPuck BASIC 12408 supply voltage 2x AA 1,5 V internal, dimensions 100 x 28 mm, PC, white opaque; incl. adhesive pad; © DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61 06.07.
AL-602-03-902 EnoPuck BASIC Product manual Page 19 of 19 List of tables Table 1: Technical data / communication .............................................................................. 8 Table 2: Technical data / vibration sensor ............................................................................. 8 Table 3: Technical data / PIR sensor ..................................................................................... 8 Table 4: Technical data / user interfaces ...........................