Specification Sheet
Delta reserves the right (1) to make changes in specifications and materials, and (2) to change or discontinue models, both without notice or obligation.
Dimensions are for reference only. See current full-line price book or www.specselect.com for finish options and product availability.
Note: Measurements may vary ± 6mm (0.25")
DSP–R2570-MIXLF Rev. A Page 4.C.1
Refer to www.specselect.com for individual models. Note: Use this page as a product submittal sheet.
Thermostatic Mixing Valve
o R2570-MIXLF
SPECIFICATION: (example)
•Thermostaticmixingvalve
•Brassbody
•Thermostaticelementsensestheoutlet
water temperature and reacts to maintain
a constant delivery temperature even under
changing flows or variations in supply
temperatures or pressures
•Regulatingpistonmadefrom
Engineered polymer
•Outletflowreducedtoatrickleintheevent
of a cold water supply failure
•Snap-oncoveroveraspindlemechanism
that requires a special tool to adjust
temperature.Thespecialtoolisprovided
with each valve.
•Suppliedwithintegralpoppetstylecheck
valves on both inlets to prevent crossflow
•Inlets/outlets:1/2"coppersweat
•Outlettemperaturerange:
95 - 120˚F (35 - 49˚C)
•Hottemperaturesupplyrange:
120 - 180˚F (49 - 82˚C)
•Minimumacceptabletemperature
differential of hot water inlet to tempered
water outlet is 5˚F (3˚C)
•Workingpressure:
145psi(1,000kPa)max.
•Pressuredifferencebetweenhotandcold
supplyshouldnotexceed± 20%
•Maximumflowrate@45psipressureloss
–11.0gpm(42L/min)
•Minimumflowrate@45psipressureloss
–0.34gpm(1.29L/min)
THERMOSTATIC MIXING VALVE
117.6 mm
(4.63")
119.4 mm
(4.7")
1/2"SWEATINLET
HOT
1/2"SWEAT
INLET
COLD
1/2"SWEATOUTLET
MIXED
38.9 mm
(1.53")
66 mm
(2.6")
FLOW RATE vs PRESSURE
Approvals:
• ListedtoASSE1069,ASSE1070and
CSAB125.3
• Verifiedcompliantwith0.25%weighted
average Pb content regulations
(ContactDeltaRepresentativeforStateand/or
Local Approvals.)
10
12
8
6
4
2
00
7.6
15.1
22.7
30.3
37.9
45.4
0
10 20 30 40 50
Pressure Differential (psi)
FLOW
(L/min.)
FLOW
(GPM)
DSP–R2570-MIXLF Rev. A