Profibus (CME-PD01) User Manual Profibus is a registered trademark of Profibus International. The information supplied by this document is subject to change without notice. No responsibility or liability for the correctness of the information supplied within this document is assumed.
Table of Contents Chapter 1 Preface ........................................................................................1-1 1.1 Receiving and Inspection....................................................................1-1 1.2 Using this Manual ...............................................................................1-1 Chapter 2 Overview .....................................................................................2-1 2.1 Layout ...........................................................
5.3.5 Accessing Parameters via PKW Area......................................... 5-5 5.3.5.1 PKE ..................................................................................... 5-5 5.3.5.2 IND ...................................................................................... 5-6 5.3.5.3 Parameter Value (PWE) 3rd and 4th Word ......................... 5-7 5.3.5.4 Examples for PKW Mechanism........................................... 5-7 5.4 CME-PD01 Response Time ....................................
Chapter 1 Preface 1.1 Receiving and Inspection All Delta CME-PD01 have gone through rigorous quality control tests at the factory prior to the shipment. Upon the receive of CME-PD01, please check that the package includes: 1pcs CME-PD01, 1pcs communication cable (for RJ-45, 8 pins), 1 instruction sheet 1.
Chapter 1 Preface| CME-PD01 This page intentionally left blank 1-2 Revision October 2006, 2006PDD23000013
Chapter 2 Overview CME-PD01, defined as a communication module for PROFIBUS-DP, is used to link VFD-E series and PROFIBUS-DP system. 2.
Chapter 2 Overview| CME-PD01 The address in PROFIBUS-DP can be set via two rotary address switches, ADDH and ADDL, on CME-PD01: ADDH used as a high 4 bits of address, ADDL used as a low 4 bits of address. NOTE For more information of address switches, refer to Chapter 5 Communication. A specific 6-PIN communication cable for RJ-45, is used to connect the CME-PD01 to VFD-E series via RS-485 interface. VFD-E series supply the 15V DC power to CMEPD01 through this cable.
Chapter 3 Profibus Introduction 3.1 PROFIBUS PROFIBUS is an international, vendor- independent, opening filed bus standard for a wide range of applications in the fields of manufacturing, production, process and building automation, and other automation control field.
Chapter 3 Profibus Introduction| CME-PD01 3.2 PROFIBUS-DP PROFIBUS-DP is a PROFIBUS communication profile optimized for high-speed, time-critical data transmission at field level using low-cost connections. PROFIBUS-DP is a suitable substitute for conventional, costly parallel wiring of 24 V measurement signals in production and manufacturing automation, as well as for analog 4(0) to 20mA measurement signals in process automation.
Chapter 4 Installation Information Please make sure that the power of VFD-E series is OFF before installation or remove the CMEPD01 from network. 4.1 Installation Improper installation of the CME-PD01 will cost its life usage. Please follow the instructions to install your CME-PD01 carefully.
Chapter 4 Installation Information| CME-PD01 Power Supply The power of CME-PD01 is supplied from VFD-E series Drive. The VFD-E firmware version should be V2.02 and above. No external power needed. The +15VDC power is applied to CME-PD01 directly via a specific 6-PIN communication cable (This 6-PIN cable is packed together with CME-PD01). CME-PD01 is energized while the power is applied to the VFD-E series, then the SP LED will be steady green. 4.
Chapter 5 Communication Please make sure that you have read chapter 4 and fully understood the CME-PD01 installation. 5.1 PROFIBUS Address CME-PD01 has two rotary switches to set the PROFIBUS address, the only way for user to set the address. The address switches, ADDH and ADDL, allow user to set the address in a HEX format. ADDH is used to set high 4 bits of address, and ADDL is used to set low 4 bits of address.
Chapter 5 Communication| CME-PD01 VFD-E type Baud Rate 9600 P09-01=1 RTU 8, N, 2 P09-03=3 Freq. Source P02-00=3 Command Source P02-01=3 After these settings completed, connecting CME-PD01 and VFD-E series via communication cable mentioned earlier, CME-PD01 is then energized. Two LEDs will be firstly in orange because CME-PD01 is initialized and test itself. SP LED will be then in steady green since that the connection is established between CME-PD01 and VFD-E series. 5.
Chapter 5 Communication| CME-PD01 NOTE CME-PD01 supports PPO1 and PPO3 structure only. 5.3.2 Extended Configuration In addition to the PPO types, cyclical data can also be configured to EXT CONF 1 or EXT CONF 2 (see table below). These two extended configuration both have four process data words. The areas of consistency can be set flexibly.
Chapter 5 Communication| CME-PD01 11B:Change direction 00B:1st Accel / Decel time Bit 6~7 01B:2nd Accel / Decel time Bit 8~15 Reserved Frequency Command Bit 0 1:E.F. ON Bit 1 1:Reset command Bit 2~15 Reserved NOTE Table above is for reference only, please check VFD-E series user manual for details. The control word that is mapping to the address of VFD-E series can be carried out by CME-PD01, so the bit assignments in the user manual of VFD-E series is valid.
Chapter 5 Communication| CME-PD01 NOTE Table above is for reference only, please check VFD-E series user manual for details. CME-PD01 will get the status word from VFD-E series, so the bit assignments in the user manual of VFD-E series is valid. 5.3.5 Accessing Parameters via PKW Area In cyclical data, CME-PD01 can provide request and response (read / write) message to access the VFD-E parameters.
Chapter 5 Communication| CME-PD01 Fault numbers for "Cannot process request" response NO. Description 0 Illegal Parameter number Parameter does not exist 1 Parameter value cannot be modified Parameter is a read-only parameter or can not change in current state 2 Minimum/maximum not reached / exceeded 18 Other error 5.3.5.
Chapter 5 Communication| CME-PD01 NOTE In IND, Bit 15 uses a multiplier of 20, so the value of Bit 15 for the access P2000- P3999 must be set to 1. 5.3.5.3 Parameter Value (PWE) 3rd and 4th Word All parameters for the VFD-E series are 16-bit. A 16-bit parameter value is transferred by PWE2 (4th word). PWE1 (3rd word) must be set to 0 on the PROFIBUS-DP master in this case. 5.3.5.
Chapter 5 Communication| CME-PD01 Request Word 1 (PKE) Response 11C2 Word 1 (PKE) 11C2 Word 2 (IND) 2000 Word 2 (IND) 2000 Word 3 (PWE1) 0000 Word 3 (PWE1) 0000 Word 4 (PWE2) 0000 Word 4 (PWE2) 0868 Example 3: Write data 2 to parameter P0804 To write data to P0804, request ID is set to 2 (Modify parameter value - word), Para Page Select should be set because the parameter address is greater than 2000.
Chapter 5 Communication| CME-PD01 in decimal, if set Page Select to 14, then the Basic PNU is 29952-14*2000=1952(0x7A0), thus, the data sequence are as follows: Master - > CME-PD01 : 17A0700000000000 read data from 0x7500 CME-PD01 - > Master : 17A0700000000300 Request Response Word 1 (PKE) 17A0 Word 1 (PKE) 17A0 Word 2 (IND) 7000 Word 2 (IND) 7000 Word 3 (PWE1) 0000 Word 3 (PWE1) 0000 Word 4 (PWE2) 0000 Word 4 (PWE2) 0300 If the data that CME-PD01 returns is 0x0300, it indicates that Sc
Chapter 5 Communication| CME-PD01 T1: transmission time between Master and CME-PD01 T2: waiting time for CME-PD01 buffer T3: transmission time between CME-PD01 and VFD-E T1 Master CME-PD01 Timer Data Buffer T3 VFD series Drives T2 T1 depends on the actual transmission speed and the type of master in use. T2 depends on the internal timer of CME-PD01. Data is transmitted to VFD-E series per 70ms triggered by a timer. User cannot change the time-out interval.
Chapter 6 Parameters Setting in GSD file 6.1 GSD File A GSD file is a text file used to identify PROFIBUS-DP device (Master or Slave), which contains the necessary data for the configuration of DP slaves within a standard DP master. Typical information in a GSD file are Vendor information, supported Baud rates, Timing information, supported Options/features and Available I/O signals. The GSD file is the fundamental building block for the master parameter record.
Chapter 6 Parameters Setting in GSD file| CME-PD01 Auto_Baud_supp =1 9.6_supp =1 19.2_supp =1 93.75_supp =1 187.5_supp =1 500_supp =1 1.5M_supp =1 3M_supp =1 6M_supp =1 12M_supp =1 MaxTsdr_9.6 = 60 MaxTsdr_19.2 = 60 MaxTsdr_93.75 = 60 MaxTsdr_187.5 = 60 MaxTsdr_500 = 100 MaxTsdr_1.
Chapter 6 Parameters Setting in GSD file| CME-PD01 0x00,0x00,\ 0x21,0x01,\ 0x21,0x02,\ 0x21,0x03,\ 0x21,0x04,\ 0x00,0x01,\ 0x00,0x02,\ 0x00,0x02,\ 0x00,0x01,\ 0x00,0x00 Module = "4 PKW, 2 PZD (PPO 1) " 0xF3, 0xF1 EndModule Module = "0 PKW, 2 PZD (PPO 3) " 0x00, 0xF1 EndModule Module = "4 PKW, 4 PZD " 0xF3, 0xF3 EndModule Module = "0 PKW, 4 PZD " 0x00, 0xF3 EndModule PrmText = 1 Text(0) = "Address discontinuous" Text(1) = "Address continue" EndPrmText PrmText = 2 Text(0) = "Ignore and Continue" Text
Chapter 6 Parameters Setting in GSD file| CME-PD01 Unsigned16 0x0000 0-65535 EndExtUserPrmData ExtUserPrmData = 4 "Data Input 4" Unsigned16 0x0000 0-65535 EndExtUserPrmData ExtUserPrmData = 5 "Data Output 1(VFD -> CME-PD01)" Unsigned16 0x2101 0-65535 EndExtUserPrmData ExtUserPrmData = 6 "Data Output 2" Unsigned16 0x2102 0-65535 EndExtUserPrmData ExtUserPrmData = 7 "Data Output 3" Unsigned16 0x2103 0-65535 EndExtUserPrmData ExtUserPrmData = 8 "Data Output 4" Unsigned16 0x2104 0-65535 EndExtUserPrmData ExtUs
Chapter 6 Parameters Setting in GSD file| CME-PD01 Ext_User_Prm_Data_Ref(10) = 6 Ext_User_Prm_Data_Ref(12) = 7 Ext_User_Prm_Data_Ref(14) = 8 Ext_User_Prm_Data_Ref(16) = 9 Ext_User_Prm_Data_Ref(18) = 10 Ext_User_Prm_Data_Ref(20) = 11 Ext_User_Prm_Data_Ref(22) = 12 Ext_User_Prm_Data_Ref(24) = 13 File END: ========================================================== NOTE The required GSD file is available and can be downloaded from the DELTA web site http://www.delta.com.
Chapter 6 Parameters Setting in GSD file| CME-PD01 Item Name Type Description Default 8 Data Output 4 UINT This is a MODBUS address. CME-PD01 will monitor this address, and copy the return data to the 4th word of cyclic input data PZD if selecting module "4 PKW, 4 PZD". 9 d_state UINT This is a flag. If address in Data Output 1 ~ Data Output 4 is continuous, set it to 1 or set it to 0. 0x0001 UINT This is a length, and unit is word. It specifies the length of CME-PD01 to process data in PZD.
Chapter 6 Parameters Setting in GSD file| CME-PD01 Data Output 4 = 0x2103; dout_len = 0x0003; The MODBUS address in Data Output 1~Data Output 4 is continuous, so you can set the d_state to 1, then CME-PD01 will monitor the address starting from Data Output 1, and monitor 3 words from VFDE series Drives one time. When the dout_len is 3, CME-PD01 will ignore the address in Data Output 4.
Chapter 6 Parameters Setting in GSD file| CME-PD01 This page intentionally left blank 6-8 Revision October 2006, 2006PDD23000013
Chapter 7 Troubleshooting 7.1 LED Displays Two LEDs, SP and NET LED, are used to monitor the CME-PD01 communication status. NET LED State LED is off Indication No power Corrective Actions 1. Verify that the power supply of CME-PD01. 2. Check whether the power supply is connected and that power is applied to the CME-PD01 through the connector. Check whether the switch value is valid, valid Rapid Flashing Invalid PROFIBUS address value of slave is within 1-125.
Chapter 7 Troubleshooting| CME-PD01 SP LED State Indication LED is off Flashing Red LED Corrective Actions 1. Verify that the power supply of CME-PD01 No power 2. Check whether the power supply is connected and that power is applied to the CME-PD01 through the connector CRC check error Check if the communication setting in VFD-E is (9600, <8,N,2>, RTU) Connection failure, or no connection Red LED Flashing Green LED AC Drive returns error code Green LED Operating normally 1.
Chapter 7 Troubleshooting| CME-PD01 00 – Normal 01 – CRC check error 02 – VFD-E returns error code 03 – Communication is time-out Byte 9 indicates the error code when byte 8 is 02 (VFD-E will return error code). Refer to the Section 7.3 for the meanings of invalid code. User can get the diagnostic data via PZD area any time. Following table is some special MODBUS Description Comm. address addresses that CME-PD01 provides to indicate the diagnostic status. 0x7500 High byte Low byte SP Comm.
Chapter 7 Troubleshooting| CME-PD01 Error Code Description Illegal command code 01 Corrective Actions 1. The command code received in the command message is not available for the drives. 2. 03 Check the Parameter number in PKW area, and refer the VFD-E user manual. 2. The command code received in the command message is not available for the drives. Check the settings of parameters “Data Input 1” to “Data Input 4”, “Data Output 1” to “Data Output 4”, and refer to the VFD-E user manual. 3.
Chapter 8 Dimensions ADDH ADDL NET SP CME-P B01 57.3 [2.26] 59.7 [2.35] 3.6 [0.14] 72.2 [2.84] 34.8 [1.37] Revision October 2006, 2006PDD23000013 3.5 [0.