User's Manual

2007-10-12
5011642701-DNT1
DeviceNet Communication Module (CME-DN01) Instruction Sheet
DeviceNet is a trademark of the Open DeviceNet Vendor Association, Inc.
Please thoroughly read and understand the following contents to ensure correct use before operation.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/industrialautomation
A. Panel Appearance and Dimensions
72.2 [2.84]
57.3 [2.26]
14.3 [0.57]
59.7 [2.35]
3.5 [0.14]35.8 [1.41]
CME-DN01
ADD1 ADD2
SP
500K
250K
125K
BAUD
MODNET
UNIT: mm(inch)
1
543
2
1. For RS-485 connection to VFD-E
2. Communication port for connecting DeviceNet network
3. Address selector
4. Baud rate selector
5. Three LED status indicators for monitor
B. Wiring and Settings
Refer to following diagram for details.
CME-DN01
ADD1 ADD2
SP
500K
250K
125K
BAUD
MODNET
MAC address Date Rate
CAN-LV+
Empty
pin
CAN-H V-
1: Reserved
2: EV
5: SG+
6: Reserved
7: Reserved
8: Reserved
3: GND
4: SG-
Setting baud rate
BAUD
0
Switch
Value
Baud
Rate
0 125K
1 250K
2 500K
Other
NOT
used
Setting MAC addresses:
use decimal system.
ADD1
ADD2
C. Mounting Method
Step1 and step2 show how to mount this communication
module onto VFD-E. The dimension in the following is for
your reference.
Dimensions
UNIT: mm(inch)
STEP 1
STEP 2
D. Power Supply
No external power is needed. Power is supplied via
RS-485 port that is connected to VFD-E. An 8 pins RJ-45
cable, which is packed together with this communication
module, is used to connect the RS-485 port between
VFD-E and this communication module for power. This
communication module will perform the function once it is
connected. Refer to the following paragraph for LED
indications.
E. LEDs Display
1. SP: Green LED means in normal condition, Red LED
means abnormal condition.
2. Module: Green blinking LED means no I/O data
transmission, Green steady LED means I/O data
transmission OK. Red LED blinking or steady LED
means module communication is abnormal.
3. Network: Green LED means DeviceNet
communication is normal, Red LED means abnormal.
NOTE
Please download the auto EDS generator and user manual
at http://www.delta.com.tw/industrialautomation/

Summary of content (2 pages)