Specifications

Installation Instructions D- Series
Issue
Date October 6, 2003
D-70, D-140, D-210, and D-280 Series
Electric Non-Spring Return Actuators
(8, 16, 24, and 32 N·m)
Installation
Mount D- Series actuators in any convenient
orientation.
Install the actuators on a 3/8 to 3/4 in.
(9.5
to 19 mm) round shaft or a 3/8 to 5/8 in.
(9.5
to 16 mm) square shaft, 2 in. (51 mm) or longer. If
the
shaft is less than 2 in. (51 mm) long, install an
extension
recommended by the damper or valve
manufacturer.
IMPO
RTANT: The D- Series actuators are
intended to control equipment under normal
operating conditions. Where failure or malfunction of
a D- Series actuator could lead to an abnormal
operating condition that could cause personal injury
or damage to the equipment or other property, other
devices (limit or safety controls) or systems (alarm
or supervisory) intended to warn of, or protect
against, failure or malfunction of the D- Series
actuator must be incorporated into and maintained
as part of the control system.
To
mount the actuator, proceed as follows:
1. Press
and hold the gear release lever, and rotate
the
coupler to the 0 or 90° position. Release the
gear
release lever. (See Figure 1.)
Parts Included
Note: is the distance from the center of the
holes in the anti-rotation bracket to the center
of the shaft. (See Table 1 for dimensions.)
A
U-bolt
wi
th
Cl
amp
Nuts (2)
Shaft Center
Coupler
Gear
Release
Anti-rotation
Bracket
A
3
0
9
0
0
6
0
0
3
0
6
0
9
0
All Models
Del
ta D- Series actuator
DD
A-160 anti-rotation bracket
two No. 12-24 x 1/2 in. self-tapping hex
washer-head
screws
D24-210
and D24-280
Include one DDA-105 pluggable 3-terminal block
D24-210-FB135
and D24-FB1K
Include two DDA-105 pluggable 3-terminal blocks
D24-210-A
and D24-280-A
Include three DDA-105 pluggable 3-terminal blocks
Figure
1: Mounting Positions
Special Tools Needed
Table
1: Shaft Sizes and Distances from the
Anti-Rotation
Bracket to Shaft Center
torque wrench with 10 mm socket
digital
voltmeter or DDA-200 commissioning tool
(for the models with zero and span
po
tentiometers)
Shaft
Diameter 5/8 in. 1/2 in. 3/8 in.
A Dimensions
(See
F igure 1.)
6-1/8
in. 6-3/16 in. 6-1/4 in.
155 mm 157 mm 159 mm
Mounting
IMPORTANT: The actuator is intended for
indoor mounting only, with no direct exposure to
water beyond NEMA 2 conditions. Use an
appropriate shield or enclosure where the
environment exceeds NEMA 2 specifications.
2. Bend or cut the anti-rotation bracket to fit the
damper
frame or duct as shown in Figure 2.
© 2003 Delta Control Products, Inc. 1
Part No. 34-636-836, Rev F www.deltacp.com

Summary of content (8 pages)