Operating Instructions VLT® 8000 AQUA
VLT® 8000 AQUA ■ Contents Introduction ......................................................................................................... 4 Software version ....................................................................................................... 4 Definitions ................................................................................................................ 5 Safety regulations ..............................................................................................
VLT® 8000 AQUA Control keys for parameter setup ........................................................................... Indicator lamps ....................................................................................................... Local control .......................................................................................................... Display mode .........................................................................................................
VLT® 8000 AQUA Derating for ambient temperature ......................................................................... Switching on the input .......................................................................................... Efficiency .............................................................................................................. Mains supply interference/harmonics .................................................................... CE labelling ....................................
VLT 8000 AQUA 176FA145.16 VLT® 8000 AQUA Operating Instructions Software version: 1.7x These Operating Instructions can be used for all VLT 8000 AQUA frequency converters with software version 1.7x. The software version number can be seen from parameter 624 Software version no. 4 MG.83.A2.
VLT® 8000 AQUA AEO: Automatic Energy Optimization - function that dynamically adjusts the current supplied to a variable torque load to optimize motor power factor and motor efficiency. analog inputs: The analog inputs can be used for controlling various functions of the frequency converter. There are two types of analog inputs: Current input, 0-20 mA Voltage input, 0-10 V DC. analog ref. A signal transmitted to input 53, 54 or 60. Can be voltage or current.
VLT® 8000 AQUA from the frequency converter, i.e. in a front panel, by means of the installation kit option. LSB: Least significant bit. Used in serial communication. MCM: Stands for Mille Circular Mil, an American measuring unit for cable cross-section. Setup: There are four Setups, in which it is possible to save parameter settings. It is possible to change between the four parameter Setups and to edit one Setup, while another Setup is active.
The voltage of the frequency converter is dangerous whenever the equipment is connected to mains. Incorrect installation of the motor or the frequency converter may cause damage to the equipment, serious personal injury or death. Consequently, the instructions in this manual, as well as national and local rules and safety regulations, must be complied with. 117, Motor thermal protection). In UL/cUL applications ETR provides Class 20, over-load protection in accordance with the NEC ®. 6.
VLT® 8000 AQUA ■ Use on isolated mains See section RFI Switch regarding use on isolated mains. It is important to follow the recommendations regarding installation on IT-mains, since sufficient protection of the complete installation must be observed. Not taking care using relevant monitoring devices for IT-mains may result in damage.
VLT® 8000 AQUA Introduction to AQUA: This section tells you the advantages you can obtain by using a VLT 8000 AQUA - such as Automatic Energy Optimization, Constant Torque or Variable Torque and other AQUA relevant functions. This section also contains examples of applications as well as information about Danfoss. Installation: This section tells you how to carry out a mechanically correct installation of the VLT 8000 AQUA.
VLT® 8000 AQUA ■ Control principle A frequency converter rectifies AC voltage from mains into DC voltage, after which this DC voltage is converted into a AC current with a variable amplitude and frequency. 1. Mains 3 x 200 3 x 380 3 x 525 3 x 525 - voltage 240 V AC, 480 V AC, 600 V AC, 690 V AC, 50 50 50 50 / / / / 60 60 60 60 Hz. Hz. Hz. Hz. 2. Rectifier A three-phase rectifier bridge that rectifies AC current into DC current. 3. Intermediate circuit DC voltage = 1.35 x mains voltage [V]. 4.
VLT® 8000 AQUA • • Introduction • Energy savings in a constant air volume system Compensation in the oversynchronous working range Reduces acoustic motor noise MG.83.A2.
VLT® 8000 AQUA ■ Example of application - Constant pressure regulation in water supply system The demand for water from waterworks varies considerably during the course of a day. In the night, practically no water is used, while in the morning and in the evening the consumption is high. In order to maintain a suitable pressure in the water supply lines in relation to the current demand, the water supply pumps are equipped with speed control.
■ PC software and serial communication Danfoss offers various options for serial communication. Using serial communication, it is possible to monitor, program and control one or several frequency converters from a centrally located computer. All VLT 8000 AQUA units have an RS 485 port as standard with a choice of two protocols. The protocols selectable in parameter 500 protocols are: • FC Protocol • Modbus RTU A bus option card allows higher transmission speed than RS 485.
VLT® 8000 AQUA ■ LON - Local Operating Network LonWorks is an intelligent fieldbus system which improves the possibility of decentralising control, as communication is enabled between individual units in the same system (Peer-to-Peer). This means that there is no need for a big main station for handling all the signals of the system (Master-Slave). Signals are sent direct to the unit that needs them via a common network medium.
VLT® 8000 AQUA Introduction ■ Accessories IP 20 bottom cover Application option Type IP 4x top cover IP IP 4 x top cover 1) 1) Description Order no.
VLT® 8000 AQUA Rittal Installation Kit Type Description Order No.
VLT® 8000 AQUA In "Master/Slave Mode", the drive that has the Cascade Controller option card installed in it, along with its associated motor, is designated as the master. Up to four additional motors, each with its own drive, can be operated in slave mode. The Cascade Controller functions to stage the slave drives/motors - on & off (as required), as a function of "best system operating efficiency".
VLT® 8000 AQUA ■ Ordering numbers, LC filter modules Mains supply 3 x 200 - 240 V LC filter LC filter for VLT type enclosure 8006-8008 IP 00 8011 IP 00 8016 IP 00 8022 IP 00 8027 IP 00 8032 IP 00 8042 IP 00 8052 IP 00 8062 IP 00 Rated current at 200 V 25.0 A 32 A 46 A 61 A 73 A 88 A 115 A 143 A 170 A Max.
VLT® 8000 AQUA Mains supply 3 x 690 V 8052 8062 8072 8102 8122 8152 8202 8252 8302 8352 8402 8502 8602 8652 Rated Current at 690 V 54 73 86 108 131 155 192 242 290 344 400 530 600 630 Max. output frequency (Hz) 60 60 60 60 60 60 60 60 60 60 60 60 60 60 Power dissipation (W) 290 390 480 600 550 680 920 750 1000 1050 1150 500 570 600 Ordering no. IP00 130B2223 130B2225 130B2225 130B2226 130B2228 130B2228 130B2229 130B2231 130B2231 130B2232 130B2234 130B2241 130B2242 - Ordering no.
VLT® 8000 AQUA ■ LC filters VLT 8006-8011 380 - 480 V The drawing on the left gives the measurements of IP 20 LC filters for the above-mentioned power range. Min. space above and under enclosure: 100 mm. IP 20 LC filters have been designed for side-by-side installation without any space between enclosures. Max. motor cable length: - 150 m screened/armoured cable - 300 m unscreened/unarmoured cable If EMC standards are to be complied with: EN 55011-1B: Max. 50 screened/armoured cable EN 55011-1A: Max.
VLT® 8000 AQUA LC filter IP 00 LC type A [mm] 175Z4600 220 175Z4601 220 175Z4602 250 175Z4603 295 175Z4604 355 175Z4605 360 175Z4606 280 175Z4607 280 175Z4608 280 175Z4609 295 175Z4610 355 175Z4611 355 175Z4612 405 B [mm] 135 145 165 200 205 215 170 175 180 200 205 235 230 C [mm] 92 102 117 151 152 165 121 125 131 151 152 177 163 MG.83.A2.02 - VLT is a registered Danfoss trademark Max.
VLT® 8000 AQUA ■ LC filter VLT 8042-8062 200-240 V / 8072-8602 380 - 480 V The table and the drawing give the measurements of IP 20 LC filters. IP 20 LC filters must be integrated and protected against dust, water and aggressive gases.
VLT® 8000 AQUA Higher total current to be handled by the installations - Increases load on transformer (sometimes it will require a larger transformer, particular at retrofit) - Increases heat losses in transformer and installation - In some cases demands larger cables, switches and fuses Higher voltage distortion due to higher current - Increase risk for disturbing electronic equipment connected to same grid A high percentage of rectifier load from eg frequency converters, will increase the harmonic curre
VLT® 8000 AQUA Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 400 V and assuming typical motor load (4 or 2 pole motor). VLT 8000 is based on a max. 110% torque application. The pre-calculated filter current may be different than the input current ratings of VLT 8000 as stated in the respective operating instructions, as these numbers are based on different operating conditions.
■ Unpacking and ordering a VLT frequency converter If you are in doubt as to which frequency converter you have received and which options it contains, use the following to find out. ■ Type code ordering number string On the basis of your order, the frequency converter is given an ordering number that can be seen from the nameplate on the unit.
VLT® 8000 AQUA 200-240 V Typecode Position in string 4.0 kW/5.0 HP 5.5 kW/7.5 HP 7.5 kW/10 HP 11 kW/15 HP 15 kW/20 HP 18.5 kW/25 HP 22 kW/30 HP 30 kW/40 HP 37 kW/50 HP 45 kW/60 HP T2 C00 C20 CN1 C54 ST SL R0 R1 R3 9-10 8006 8008 8011 8016 8022 8027 8032 8042 8052 8062 11-13 11-13 X X X X X X X 11-13 11-13 X X X X X X X X X X 14-15 X X X X X X X X X X 14-15 X X X X X X X 16-17 X X X X X X X X X X 16-17 16-17 X X X X X X X X X X X X X X X X 380-480 V Typecode T4 Position in string 4.
VLT® 8000 AQUA Typecode Position in string 1.1 kW/1.5 HP 1.5 kW/2.0 HP 2.2 kW/3.0 HP 3.0 kW/4.0 HP 4.0 kW/5.0 HP 5.5 kW/7.5 HP 7.5 kW/10 HP 11 kW/15 HP 15 kW/20 HP 18.
VLT® 8000 AQUA Optional selections, 200-600 V Display D01) Without LCP DL With LCP Position: 18-19 Fieldbus option F00 No options F10 Profibus DP V1 F30 DeviceNet F40 LonWorks free topology Position: 20-22 Application option A00 No options A312) Relay card 4 relays A32 Cascade Controller Position: 23-25 Coating C03) No coating C1 With coating Position: 26-27 1) Not available with enclosure compact IP 54 2) Not available with fieldbus options (Fxx) 3) Not available for power sizes from 8452 to 8652,
VLT® 8000 AQUA Introduction ■ TYPE CODE Table/Ordering form MG.83.A2.
VLT® 8000 AQUA ■ General technical data Mains supply (L1, L2, L3): Supply voltage 200-240 V units ........................................................................ 3 x 200/208/220/230/240 V ±10% Supply voltage 380-480 V units ................................................................ 3 x 380/400/415/440/460/480 V ±10% Supply voltage 525-600 V units ............................................................................... 3 x 525/550/575/600 V ±10% Supply voltage 525-690 V units ..........
VLT® 8000 AQUA Control card, digital inputs: Number of programmable digital inputs ................................................................................................................ 8 Terminal nos. ............................................................................................................ 16, 17, 18, 19, 27, 29, 32, 33 Voltage level ...........................................................................................................
VLT® 8000 AQUA Frequency ranges (digital output used as pulse output) ............................................................................ 0-32 kHz Current range at analog output ............................................................................................................ 0/4 - 20 mA Maximum load to frame (terminal 39) at analog output ................................................................................ 500 Accuracy of analog output ........................................
VLT® 8000 AQUA Cable lengths and cross-sections: Max. motor cable length, screened cable ........................................................................................... 150m/500 ft Max. motor cable length, unscreened cable ..................................................................................... 300m/1000 ft Max. motor cable length, screened cable VLT 8011 380-480 V .......................................................... 100m/330 ft Max.
VLT® 8000 AQUA Externals: Enclosure .................................................................................. IP00/Chassis, IP20/IP21/NEMA 1, IP54/NEMA 12 Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36) Max. relative humidity ............................................................. 93 % +2 %, -3 % (IEC 68-2-3) for storage/transport Max. relative humidity ................................................
VLT® 8000 AQUA VLT 8000 AQUA protection: • Electronic motor thermal protection against overload. • Temperature monitoring of heat-sink ensures that the frequency converter cuts out if the temperature reaches 90°C (194 °F) for IP00, IP20 and NEMA 1. For IP54, the cut-out temperature is 80°C (176 °F). An overtemperature can only be reset when the temperature of the heat-sink has fallen below 60°C (140 °F).
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 200 - 240 V According to international requirements Output current4) VLT type 8006 8008 8011 IVLT,N [A] 16.7 24.2 30.8 33.9 18.4 26.6 Output power (240 V) IVLT, MAX (60 s) [A] SVLT,N [kVA] 6.9 10.1 12.8 Typical shaft output PVLT,N [kW] 4.0 5.5 7.5 PVLT,N [HP] 5 7.5 10 10/8 16/6 16/6 16.0 23.0 30.0 4/10 16/6 16/6 Typical shaft output Max. cable cross-section to [mm2 ]/[AWG] motor and DC-bus Max. input current Max.
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 200 - 240 V According to international requirements Output current4) VLT type 8016 8022 8027 8032 8042 8052 8062 46.2 59.4 74.8 88.0 115 143 170 50.6 65.3 82.3 96.8 127 158 187 46.0 59.4 74.8 88.0 104 130 154 50.6 65.3 82.3 96.8 115 143 170 19.1 24.7 31.1 36.6 41.0 52.0 61.0 PVLT,N [kW] 11 15 18.
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 380 - 480 V According to international requirements Output current VLT type 8006 8008 8011 IVLT,N [A] (380-440 V) 10.0 13.0 16.0 11.0 14.3 17.6 8.2 11.0 14.0 9.0 12.1 15.4 IVLT, MAX (60 s) [A] (380-440 V) IVLT, N [A] (441-480 V) IVLT, MAX (60 s) [A] (441-480 V) Output power SVLT,N [kVA] (400 V) 7.2 9.3 11.5 SVLT,N [kVA] (460 V) 6.5 8.8 11.2 Typical shaft output PVLT,N [kW] 4.0 5.5 7.
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 380 - 480 V Output current VLT type 8016 8022 8027 8032 8042 IVLT,N [A] (380-440 V) 24.0 32.0 37.5 44.0 61.0 26.4 35.2 41.3 48.4 67.1 21.0 27.0 34.0 40.0 52.0 23.1 29.7 37.4 44.0 57.2 SVLT,N [kVA] (400 V) 17.3 23.0 27.0 31.6 43.8 SVLT,N [kVA] (460 V) 16.7 21.5 27.1 31.9 41.
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 380 - 480 V According to international requirements Output current VLT type 8052 8062 8072 8102 8122 IVLT,N [A] (380-440 V) 73.0 90.0 106 147 177 80.3 99.0 117 162 195 65.0 77.0 106 130 160 71.5 84.7 117 143 176 SVLT,N [kVA] (400 V) 52.5 64.7 73.4 102 123 SVLT,N [kVA] (460 V) 51.8 61.3 84.
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 380 - 480 V According to international requirements VLT type 8152 8202 8252 8302 8352 IVLT,N [A] (380-440 V) 212 260 315 395 480 IVLT, MAX (60 s) [A] (380-440 V) 233 286 347 435 528 IVLT,N [A] (441-480 V) 190 240 302 361 443 IVLT, MAX (60 s) [A] (441-480 V) 209 264 332 397 487 SVLT,N [kVA] (400 V) 147 180 218 274 333 353 Output current Output power 151 191 241 288 Typical shaft output (380-440 V) PVLT,N [kW] SVLT,N
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 380 - 480 V According to international requirements Output current Output power 8502 8602 8652 IVLT,N [A] (380-440 V) 600 VLT type 8452 658 745 800 IVLT, MAX (60 s) [A] (380-440 V) 660 724 820 880 IVLT,N [A] (441-480 V) 540 590 678 730 IVLT, MAX (60 s) [A] (441-480 V) 594 649 746 803 SVLT,N [kVA] (400 V) 416 456 516 554 SVLT,N [kVA] (480 V) 430 470 540 582 450 Typical shaft output (380-440 V) PVLT,N [kW] 315 355 400 Typical
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 525 - 600 V According to international requirements VLT type Output current IVLT,N [A] (550 V) 8002 8003 8004 8005 8006 8008 8011 2.6 2.9 4.1 5.2 6.4 9.5 IVLT, MAX (60 s) [A] (550 V) 2.9 3.2 4.5 5.7 7.0 10.5 12.7 IVLT,N [A] (575 V) 2.4 2.7 3.9 4.9 6.1 9.0 11.0 IVLT, MAX (60 s) [A] (575 V) 2.6 3.0 4.3 5.4 6.7 9.9 12.1 2.5 2.8 3.9 5.0 6.1 9.0 11.0 2.4 2.7 3.9 4.9 6.1 9.0 11.
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 525 - 600 V According to international requirements 8016 8022 8027 8032 8042 8052 8062 8072 Output current IVLT,N [A] (550 V) 18 23 28 34 43 54 65 81 IVLT, MAX (60 s) [A] (550V) 20 25 31 37 47 59 72 89 IVLT,N [A] (575 V) 17 22 27 32 41 52 62 77 IVLT, MAX (60 s) [A] (575 V) 19 24 30 35 45 57 68 85 17 22 27 32 41 51 62 77 Output SVLT,N [kVA] (550 V) 17 22 27 32 41 52 62 77 Typical shaft output PVLT,N [kW
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 525 - 690 V Max. cable cross-section to V LT type IVLT,N [A] (525-550 V) IVLT, MAX (60 s) [A] (525-550 V) IVLT,N [A] (551-690 V) IVLT, MAX (60 s) [A] (551-690 V) SVLT,N [kVA] (550 V) SVLT,N [kVA] (575 V) SVLT,N [kVA] (690 V) [kW] (550 V) [HP] (575 V) [kW] (690 V) [mm2]4,5 motor Max. cable cross-section to [AWG]2,4,5 [mm2]4,5 Output Typical shaft output loadsharing and brake Rated input current Max.
VLT® 8000 AQUA ■ Technical data, mains supply 3 x 525 - 690 V According to international requirements Output current V LT type IVLT,N [A] (525-550 V) IVLT, MAX (60 s) [A] (525-550 V) IVLT,N [A] (551-690 V) IVLT, MAX (60 s) [A] Max. cable cross-section (551-690 V) [kVA] (550 V) [kVA] (575 V) [kVA] (690 V) [kW] (550 V) [HP] (575 V) [kW] (690 V) [mm2]4,6 to motor Max.
VLT® 8000 AQUA According to international requirements 8602 8652 IVLT,N [A] (525-550 V) 523 VLT type 8502 596 630 IVLT, MAX (60 s) [A] (525-550 V) 575 656 693 IVLT,N [A] (551-690 V) 500 570 630 IVLT, MAX (60 s) [A] (551-690 V) 550 627 693 Output current Output power SVLT,N [kVA] (550 V) 498 568 600 SVLT,N [kVA] (575 V) 498 568 627 SVLT,N [kVA] (690 V) 598 681 753 Typical shaft output (525-550 V) PVLT,N [kW] 500 560 630 Typical shaft output (551-690 V) PVLT,N [HP] 400 500 6
VLT® 8000 AQUA ■ Fuses UL compliance To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
VLT® 8000 AQUA Bussmann SIBA Littel fuse Ferraz-Shawmut 8002 KTS-R3 5017906-004 KLS-R003 A6K-3R 8003 KTS-R4 5017906-004 KLS-R004 A6K-4R 8004 KTS-R5 5017906-005 KLS-R005 A6K-5R 8005 KTS-R6 5017906-006 KLS-R006 A6K-6R 8006 KTS-R8 5017906-008 KLS-R008 A6K-8R 8008 KTS-R10 5017906-010 KLS-R010 A6K-10R 8011 KTS-R15 5017906-016 KLS-R015 A6K-15R 8016 KTS-R20 5017906-020 KLS-R020 A6K-20R 8022 KTS-R30 5017906-030 KLS-R030 A6K-30R 8027 KTS-R35 5014006-040 KLS-R035
VLT® 8000 AQUA Non UL compliance If UL/cUL is not to be complied with, we recommend the above mentioned fuses or: VLT 8006-8032 200-240 V type gG VLT 8042-8062 200-240 V type gR VLT 8006-8072 380-480 V type gG VLT 8102-8122 380-480 V type gR VLT 8152-8352 380-480 V type gG VLT 8452-8652 380-480 V type gR VLT 8002-8072 525-600 V type gG Not following the recommendation may result in damage of the drive in case of malfunction.
VLT® 8000 AQUA ■ Mechanical dimensions All the below listed measurements are in mm/in VLT type A B 800/31.5 370/14.6 C a b aa/bb Type 335/13.2 780/30.7 270/10.6 225/8.9 B IP 00/Chassis 200 - 240 V 8042 - 8062 IP 00 380 - 480 V 8152 - 8202 1046/41.2 408/16.1 373/14.71) 1001/39.4 304/12.0 225/8.9 J 8252 - 8352 1327/52.2 408/16.1 373/14.71) 1282/50.5 304/12.0 225/8.9 J 8452 - 8652 1547/60.9 585/23.0 494/19.41) 1502/59.1 304/12.0 225/8.9 (aa) I 8052 - 8202 1046/41.
VLT® 8000 AQUA ■ Mechanical dimensions 52 MG.83.A2.
VLT® 8000 AQUA ■ Mechanical dimensions (cont.) Installation Type H, IP 20, IP 54 Type I, IP 00 Type J, IP 00, IP 21, IP 54 MG.83.A2.
VLT® 8000 AQUA ■ Mechanical installation ■ Installation of VLT 8006-8652 Please pay attention to the requirements All frequency converters must be installed in a that apply to integration and field mounting way that ensures proper cooling. kit, see the below list. The information given in the list must be observed to avoid serious damage Cooling or injury, especially when installing large units. The frequency converter must be installed vertically.
VLT® 8000 AQUA Compact IP 00/Chassis, IP 21/NEMA 1 and IP 54/NEMA 12 Side-by-side All units in the above-mentioned series require a minimum space of 225 mm (8.9 in) above the enclosure and must be installed on a plane floor. This applies to IP 21/NEMA 1 and IP 54/NEMA 12 units. Gaining access requires a minimum space of 579 mm (22.8 in) in front of the frequency converter.
VLT® 8000 AQUA ■ General information about electrical installation ■ High voltage warning conductor for the same conductor cross-section CVESS. If more than one device is installed in cabinets, the cabinet rear plate, which must be made of metal, should be used as a common earth reference plate. The metal cabinets of the different devices are mounted on the cabinet rear plate using the lowest possible HF impedance.
VLT® 8000 AQUA Installation ■ Extra protection with regard to indirect contact ELCB relays, multiple protective earthing or earthing can be used as extra protection, provided that local safety regulations are complied with. In the case of an earth fault, a DC content may develop in the faulty current. Never use ELCB relays, type A, since such relays are not suitable for DC fault currents.
VLT® 8000 AQUA ■ RFI switch Mains supply isolated from earth: If the frequency converter is supplied from an isolated mains source ( IT mains) or TT/TN-S mains with grounded leg, the RFI switch is recommended to be turned off (OFF)1). For further reference, see IEC 364-3. In case optimum EMC performance is needed, parallel motors are connected or the motor cable length is above 25 m, it is recommended to set the switch in ON position.
VLT® 8000 AQUA Compact IP 54/NEMA 12 VLT 8006 - 8011 380 - 480 V Installation Compact IP 20/NEMA 1 VLT 8052 - 8122 380 - 480 V VLT 8027 - 8032 200 - 240 V VLT 8052 - 8072 525 - 600 V Compact IP 54/NEMA 12 VLT 8016 - 8032 380 - 480 V VLT 8006 - 8011 200 - 240 V Compact IP 54/NEMA 12 VLT 8102 - 8122 380 - 480 V Compact IP 54/NEMA 12 VLT 8042 - 8072 380 - 480 V VLT 8016 - 8032 200 - 240 V MG.83.A2.
VLT® 8000 AQUA All enclosure types VLT 8152-8652 380 - 480 V 60 MG.83.A2.
VLT® 8000 AQUA ■ High voltage test A high voltage test can be carried out by short-circuiting terminals U, V, W, L1, L2 and L3 and energizing by max. 2.5 kV DC for one second between this short-circuit and the chassis. NB!: The RFI switch must be closed (position ON) when high voltage tests are carried out. The mains and motor connection must be interrupted in the case of high voltage tests of the total installation if the leakage currents are too high.
VLT® 8000 AQUA ■ EMC-correct electrical installation 525-600 V units do not comply with European EMC and Low Voltage Directives. The following is a guideline to good engineering practice, when installing drives. Following these guidelines is advised, where compliance with EN 50081, EN 55011 or EN 61800-3 First environment is required. If the installation is in EN 61800-3 Second environment, then it is acceptable to deviate from these guidelines. It is however not recommended.
Installation VLT® 8000 AQUA MG.83.A2.
VLT® 8000 AQUA ■ Earthing/Grounding of screened/armoured control cables Generally speaking, control cables must be screened/ armoured and the screen must be connected by means of a cable clamp at both ends to the metal cabinet of the unit. The drawing below indicates how correct earthing/grounding is carried out. Correct earthing/grounding Control cables and cables for serial communication must be fitted with cable clamps at both ends to ensure the best possible electrical contact.
VLT® 8000 AQUA Compact IP 54/NEMA 12 VLT 8006-8011, 380-480 V Compact IP 20/NEMA 1 VLT 8006-8032, 200-240 V VLT 8016-8072, 380-480 V VLT 8016-8072, 525-600 V Compact IP 20/NEMA 1 VLT 8006-8011, 380-480 V VLT 8002-8011, 525-600 V MG.83.A2.
VLT® 8000 AQUA Compact IP 00/Chassis VLT 8042-8062, 200-240 V Compact IP 54/NEMA 12 VLT 8006-8032, 200-240 V VLT 8016-8072, 380-480 V Compact IP 54/NEMA 12 VLT 8042-8062, 200-240 V Compact IP 20/NEMA 1 VLT 8042-8062, 200-240 V 66 MG.83.A2.
Compact IP 54/NEMA 12 VLT 8102-8122, 380-480 V MG.83.A2.02 - VLT is a registered Danfoss trademark Installation Compact IP 20/NEMA 1 VLT 8102-8122, 380-480 V IP 54/NEMA 12, IP 21/NEMA 1 VLT 8152-8202, 380-480 V VLT 8052-8202, 525-690 V IP 00/Chassis VLT 8152-8202, 380-480 V VLT 8052-8202, 525-690 V Note: The RFI switch has no function in the 525-690 V drives.
VLT® 8000 AQUA ■ Electrical installation, power cables IP 20/NEMA 1 VLT 8006-8032, 200-240 V VLT 8016-8122, 380-480 V VLT 8016-8072, 525-600 V IP 54/NEMA 12, IP 21/NEMA 1 with disconnect and main fuse VLT 8252-8352, 380-480 V VLT 8252-8402, 525-690 V IP 00/Chassis with disconnect and main fuse VLT 8252-8352, 380-480 V VLT 8252-8402, 525-690 V Note: The RFI switch has no function in the 525-690 V drives. 68 MG.83.A2.
Compact IP 20/NEMA 1, and IP 54/NEMA 12 VLT 8006-8011, 380-480 V VLT 8002-8011, 525-600 V IP 54/NEMA 12 VLT 8006-8032, 200-240 V VLT 8016-8072, 380-480 V MG.83.A2.
VLT® 8000 AQUA ■ Electrical installation, power cables IP 00/Chassis and IP 20/NEMA 1 VLT 8042-8062, 200-240 V IP 54/NEMA 12 VLT 8042-8062, 200-240 V Compact IP 54 /NEMA 12 VLT 8102-8122, 380-480 V 70 MG.83.A2.
VLT® 8000 AQUA ■ Electrical installation, power cables Compact IP 00 with disconnect and fuse VLT 8452-8652 380-480 V and VLT 8502-8652, 525-690 V Compact IP 00 without disconnect and fuse VLT 8452-8652 380-480 V and VLT 8502-8652, 525-690 V Note: The RFI switch has no function in the 525-690 V drives. MG.83.A2.
VLT® 8000 AQUA Compact IP 21 / IP 54 without disconnect and fuse VLT 8452-8652 380-480 V and VLT 8502-8652, 525-690 V Note: The RFI switch has no function in the 525-690 V drives. Position of earth terminals, IP 21 / IP 54 72 MG.83.A2.
VLT® 8000 AQUA ■ Use of emc-correct cables Braided screened/armoured cables are recommended to optimise EMC immunity of the control cables and the EMC emission from the motor cables. The ability of a cable to reduce the in- and outgoing radiation of electric noise depends on the transfer impedance (ZT).
VLT® 8000 AQUA ■ Tightening torque and screw sizes The table shows the torque required when fitting terminals to the frequency converter. For VLT 8006-8032, 200-240 V; VLT 8006-8122, 380-480 and VLT 8002-8072, 525-600 V the cables must be fastened with screws. For VLT 8042-8062, 200-240 V; VLT 8152-8652, 380-480 V and VLT 8052-8652, 525-690 V, the cables must be fastened with bolts. VLT type These figures apply to the following terminals: Mains terminals (Nos.) 91, 92, 93 L1, L2, L3 Motor terminals (Nos.
VLT® 8000 AQUA ■ Mains connection Mains must be connected to terminals 91, 92, 93. Nos. 91, 92, 93 Mains voltage 3 x 200-240 V L1, L2, L3 Mains voltage 3 x 380-480 V Mains voltage 3 x 525-600 V Mains voltage 3 x 525-690 V NB!: Check that the mains voltage corresponds to the mains voltage of the frequency converter, which can be seen from the nameplate.
VLT® 8000 AQUA Problems may arise at the start and at low rpm values if the motor sizes are widely different. This is because the relatively high ohmic resistance in small motors calls for a higher voltage at the start and at low rpm values. In systems with motors connected in parallel, the electronic thermal relay (ETR) of the frequency converter cannot be used as motor protection for the individual motor.
VLT® 8000 AQUA ■ DC bus connection The DC bus terminal is used for DC back-up, with the intermediate circuit being supplied from an external DC source. Terminal nos. Nos. 88, 89 Contact Danfoss if you require further information. ■ High-voltage relay The cable for the high-voltage relay must be connected to terminals 01, 02, 03. The high-voltage relay is programmed in parameter 323, Relay 1, output. Max. cross-section: Torque: Screw size: Relay output 1 1+3 break, 1+2 make. Max. 240 V AC, 2 Amp. Min.
VLT® 8000 AQUA ■ Electrical installation, control cables Torque: Screw size: Digital inputs. See parameters 300-307 Digital inputs. 20 Common for digital inputs. 39 Common for analog/digital outputs. See Examples of connection. 42, 45 Analog/digital outputs for indicating frequency, reference, current and torque. See parameters 319-322 Analoge/digital outputs. 50 Supply voltage to potentiometer and thermistor 10 V DC. 53, 54 Analog voltage input, 0 - 10 V DC. 55 Common for analog inputs.
VLT® 8000 AQUA ■ Switches 1-4 The dipswitch is located on the control card. It is used for serial communication and external DC supply. The switching position shown is the factory setting. Switch 1 has no function. Switches 2 and 3 are used for terminating an RS 485 interface, serial communication. In the first and the last frequency converter, switches 2 and 3 must be ON. In the other frequency converter, switches 2 and 3 must be OFF.
VLT® 8000 AQUA ■ Bus connection The serial bus connection in accordance with the RS 485 (2-conductor) norm is connected to terminals 68/69 of the frequency converter (signals P and N). Signal P is the positive potential (TX+,RX+), while signal N is the negative potential (TX-,RX-). If more than one frequency converter is to be connected to a given master, use parallel connections.
VLT® 8000 AQUA There are 8 digital inputs, which are controlled with 24 V DC. Terminals 16-19, 27, 29, 32, 33. These inputs can be programmed in accordance with the table in Inputs and outputs 300-328. There are two analog/digital outputs (terminals 42 and 45), which can be programmed to show the present status or a process value, such as 0-fMAX. Relay outputs 1 and 2 can be used for giving the present status or a warning.
VLT® 8000 AQUA ■ Connection examples ■ Run permissive ■ Single-pole start/stop - Start/stop using terminal 18. Parameter 302 = Start [1] Quick-stop using terminal 27. Parameter 304 = Coasting stop, inverse [0] - ■ Digital speed up/down - Start permitted with terminal 16. Parameter 300 = Run permissive [8]. Start/stop with terminal 18. Parameter 302 = Start [1]. Quickstop with terminal 27. Parameter 304 = Coasting stop, inverse [0].
VLT® 8000 AQUA ■ 3-wire start/stop MG.83.A2.02 - VLT is a registered Danfoss trademark 83 Installation Installation - Stop inverse by means of terminal 32. Parameter 306 = Stop inverse[14] - Latched start using terminal 18. Parameter 302 = Latched start [2] - Jog by means of terminal 29.
VLT® 8000 AQUA ■ Control unit LCP The front of the frequency converter features a control panel - LCP (Local Control Panel). This is a complete interface for operation and programming of the VLT 8000 AQUA. The control panel is detachable and can - as an alternative - be installed up to 3m/10 ft away from the frequency converter, e.g. on the front panel, by means of a mounting kit option. warning (WARNING) and alarm (ALARM), respectively.
[+/-] is used for selecting parameters and for changing a chosen parameter. These keys are also used to change the local reference. In addition, the keys are used in Display mode to switch between operation variable readouts. [<>] is used when selecting a parameter group and for moving the cursor when changing numerical values. ■ Indicator lamps At the bottom of the control panel is a red alarm lamp and a yellow warning lamp, as well as a green voltage LED.
VLT® 8000 AQUA 4th line VAR 2 STATUS FREQUENCY 40.0Hz SETUP 1 175ZA683.10 3rd line 195NA113.10 OFF means that the frequency converter ignores all ■ Display mode control commands and stops the motor. In normal operation, any 4 different operating variables The centre part of the status line indicates the can be indicated continuously: 1.1 and 1.2 and refe-rence element that is active. REMOTE means 1.3 and 2.
VLT® 8000 AQUA REF% CURR.A.POW.,KW 50.0Hz SETUP 1 175ZA695.10 operating data names and units of operating data are displayed. In the second line, operating data 2 remains unchanged. When the key is released, the different operating data values are shown. AUTO REMOTE RUNNING 0 40Hz 40.0Hz SETUP 1 176FA156.10 USE +/- Installation ■ Display mode IV: This display mode is only active in connection with local reference, see also Reference handling.
VLT® 8000 AQUA ■ Navigation between display modes FREQUENCY 40.0Hz AUTO REMOTE RUNNING ▲ Press briefly ▲ Display mode I With remote reference ▲ HAND LOCAL RUNNING USE +/40Hz 40.0Hz 80% ---- 60 ▲ 1 HAND LOCAL RUNNING 5,9 KW 40.0 Hz SETUP 0 7,8A With local reference AUTO REMOTE RUNNING Display mode IV Display mode II Keep the [DISPLAY MODE] key down ▲ REF% CURR.A POW.,KW 40.0 Hz AUTO REMOTE RUNNING Display mode III 175ZA697.10 88 MG.83.A2.
24.2 Hz SETUP 205 MAX. REFERENCE 1 000060,000 Hz 5 The selected digit is indicated by a flashing cursor. The bottom display line gives the data value that will be entered (saved) when signing off by pressing the [OK] button. Use [CANCEL] to cancel the change. MOTOR CURRENT 3.90 A SETUP 1 175ZA689.10 If the selected parameter is a functional value, the selected text value can be changed by means of the [+/-] keys. FREQUENCY 50.0 SETUP SETUP 1 209 JOG FREQUENCY 1 0.
VLT® 8000 AQUA ■ Quick Menu The QUICK MENU key gives access to 12 of the most important setup parameters of the drive. After programming, the drive will, in many cases, be ready for operation.
VLT® 8000 AQUA ■ Parameter Data Enter or change parameter dataor settings in accordance with the following procedure. 1. 2. Press Quick Menu key. Use ‘+’ and ‘-’ keys to find parameter you choose to edit. 3. Press Change Data key. 4. Use ‘+’ and ‘-’ keys to select correct parameter setting. To move to a different digit within parameter, use < and > arrows. Flashing cursor indicates digit selected to change. 5. Press Cancel key to disregard change, or press OK key to accept change and enter new setting. 1.
VLT® 8000 AQUA ■ Programming By means of parameter 004 LCP copy, all Setups can be transferred from one frequency converter to another by moving the control panel. First all parameter values are copied to the control panel. This can then be moved to another frequency converter, where all parameter values can be copied from the control unit to the frequency converter. Using the [EXTEND MENU] key, it is possible to have access to all the parameters for the frequency converter.
VLT® 8000 AQUA Connection examples Setup change (UPLOAD ALL PARAMET.) Download all parameters (DOWNLOAD ALL PARAM.) Download power-independent par. (DOWNLOAD SIZE INDEP.) [1] [2] [3] Function: Parameter 004 LCP copy is used if the integrated copying function of the control panel is to be used. This function is used if all parameter Setups are to be copied from one frequency converter to another by moving the control panel. Description of choice: - Selection of Setup using terminals 32 and 33.
VLT® 8000 AQUA 005 Max. value of user-defined readout (CUSTOM READOUT) Value: 0.01 - 999,999.99 Function: ✭ 100.00 Function: This parameter allows a choice of the max. value of the user-defined readout. The value is calculated on the basis of the present motor frequency and the unit selected in parameter 006 Unit for user-defined readout. The programmed value is reached when the output frequency in parameter 202 Output frequency high limit, fMAX is reached.
Feedback [unit] (FEEDBACK [UNITS]) Motor voltage [V] (MOTOR VOLTAGE [V]) DC link voltage [V] (DC VOLTAGE [V]) Thermal load, motor [%] (THERM.MOTOR LOAD [%]) Thermal load, VLT [%] (THERM.DRIVE LOAD [%]) Digital input [Binary code] (DIGITAL INPUT [BIN]) Analog input 53 [V] (ANALOG INPUT 53 [V]) Analog input 54 [V] (ANALOG INPUT 54 [V]) Analog input 60 [mA] (ANALOG INPUT 60 [MA]) Relay status [binary code] (RELAY STATUS) Pulse reference [Hz] (PULSE REFERENCE [HZ]) External reference [%] (EXT.
VLT® 8000 AQUA the relay is active, a "0" indicates inactive. Paramater 007 uses an 8-bit word with the last two positions not used. Relays 6-9 are provided with the cascade controller and four relay option cards Pulse reference [Hz] states a pulse frequency in Hz connected to terminal 17 or terminal 29. External reference [%] gives the sum of the external references as a percentage (the sum of analog/ pulse/serial communication) in the range from Minimum reference, RefMIN to Maximum reference, RefMAX.
VLT® 8000 AQUA Function: This parameter decides the local reference unit. Description of choice: If Disable [0] is selected in this parameter, the [AUTO START] key will be inactive. Description of choice: Choose the required unit for local reference. 015 Reset on LCP (RESET BUTTON) 012 Hand start on LCP (HAND START BTTN) [0] [1] Function: This parameter allows selection/deselection of the Hand start key on the control panel.
VLT® 8000 AQUA Function: Setting of the desired operating mode when the mains voltage is reconnected. Description of choice: Auto restart [0] is selected if the frequency converter is to start up in the same start/stop condition as immediately before power to the frequency converter is cut off. OFF/Stop [1] is selected if the frequency converter is to remain stopped when the mains voltage is connected, until a start command is active.
VLT® 8000 AQUA ■ Configuration The selection of configuration and torque characteristics influences the parameters that can be seen in the display. If Open loop [0] is selected, all parameters relating to PID regulation will be hidden. Consequently, the user is only able to see the parameters that are of significance for a given application. 100 Configuration (CONFIG.
VLT® 8000 AQUA Torque. CT operation is achieved by maintaining a constant U/f ratio over the operating range. At the works, a rated kW value P M,N has been selected that depends on the type of unit. Description of choice: NB!: It is important that the values set in parameters 102-106 Nameplate data correspond to the nameplate data of the motor with respect to either star coupling Y or delta coupling . Select a value that equals the nameplate data on the motor.
VLT® 8000 AQUA Function: Select the rated motor frequency fM,N. Description of choice: Select a value that equals the nameplate data on the motor. 105 Motor current, IM,N (MOTOR CURRENT) Value: 0.01 - IVLT,MAX A ✭ Depends on the choice of motor. Function: The rated motor current IM,N forms part of the frequency converter calculations of torque and motor thermal protection. Set the motor current IVLT,N, taking into connected motor.
VLT® 8000 AQUA - AMA can only be carried out if the rated motor current of the motor is min. 35% of the rated out-put current of the frequency converter. NB!: Some motors (such as motors with 6 or more poles) may be unable to run Automatic Adaptation. Limited AMA or use of parameters 123 and 124 is a procedure which can be effective in such cases since procedure measures motor’s stator and effects of cable length. Multiple motor applications cannot use any form of AMA.
VLT® 8000 AQUA Description of choice: Description of choice: Adjust the damping percentage until the motor resonance has disappeared. Select Disable [0] if this function is not required. Select Enable [1] to activate motor preheating. The DC current is set in parameter 113 Motor preheater DC current. 110 High break-away torque 113 Motor preheater DC current (HIGH START TORQ.) Value: 0.0 - 0.5 sec. (PREHEAT DC-CURR.) ✭ 0.0 sec.
VLT® 8000 AQUA 114 DC braking current 116 DC brake cut-in frequency (DC BRAKE CUT-IN) (DC BRAKE CURRENT) Value: ✭ 50 % The maximum value depends on the rated motor current. If the DC braking current is active, the frequency converter has a switching frequency of 4 kHz.
VLT® 8000 AQUA Select Thermistor trip [2] if cutting out (trip) is desired when the connected thermistor overheats. Select ETR Warning 1-4, if a warning is to come up on the display when the motor is overloaded according to the calculations. The frequency converter can also be programmed to give off a warning signal via one of the digital outputs. Select ETR Trip 1-4 if tripping is desired when the motor is overloaded according to the calculations.
VLT® 8000 AQUA Motor size 0.5 kW - 7.5 kW 11 kW - 45 kW 55 kW - 355 kW Change-over >10 Hz >5 Hz >3-4 Hz made automatically, including the stator resistance RS. A manually entered RS must apply to a cold motor. The shaft performance can be improved by fine-tuning RS and X S, see procedure below. Description of choice: 121 Slip compensation (SLIP COMPENSAT.) Value: -500 - 500 % ✭ 100 % Function: Slip compensation is calculated automatically, i.e. on the basis of the rated motor speed nM,N.
VLT® 8000 AQUA 124 Stator reactance (STATOR REACT.) Value: ✭depends on the choice of motor Function: After setting motor data in parameters 102-106, a number of adjustments of various parameters are made automatically, including the stator resistance XS. The shaft performance can be improved by fine-tuning R S and XS, see procedure below. Description of choice: XS can be set as follows: Programming 1.
VLT® 8000 AQUA ■ References and Limits 200-228 NB!: The output frequency of the frequency converter can never assume a value higher than 1/10 of the switching frequency (parameter 407 Switching frequency). Description of choice: A value from fMIN to the choice made in parameter 200 Output frequency range can be selected. In this parameter group, the frequency and reference range of the frequency converter are established.
VLT® 8000 AQUA Remote references are defined as: • External references, such as analog inputs 53, 54 and 60, pulse reference via terminal 17/29 and reference from serial communication. • Preset references. The resulting reference can be shown in the display by selecting Reference [%] in parameters 007-010 Display readout and in the form of a unit by selecting Resulting reference [unit]. See the section on Feedback handling in connection with a closed loop.
VLT® 8000 AQUA 203 Reference site (REFERENCE SITE) Minimum reference is ignored when the local reference is active (parameter 203 Reference site). The unit for the reference can be seen from the following table: Value: ✭Hand/Auto linked reference (LINKED TO HAND/AUTO) Remote reference (REMOTE) Local reference (LOCAL) [0] [1] [2] Par. 100 Configuration = Open loop Par. 100 Configuration = Closed loop Unit Hz Par.
VLT® 8000 AQUA 206 Ramp-up time of warnings and alarms), the frequency converter automatically extends the ramp-down time. (RAMP UP TIME) Value: 1 - 3600 sec. ✭ Depends on the unit Function: The ramp-up time is the acceleration time from 0 Hz to the rated motor frequency fM,N (parameter 104 Motor frequency, fM,N). It is assumed that the output current does not reach the current limit (set in parameter 215 Current limit ILIM).
VLT® 8000 AQUA ■ Reference type The example shows how the resulting reference is calculated when Preset references are used together with Sum and Relative in parameter 210 Reference type. See Calculation of resulting reference. See also the drawing in Reference handling. The following parameters have been set: Par. 204 Minimum reference: Par. 205 Maximum reference: Par. 211 Preset reference: Par. 308 Terminal 53, analog input: Par. 309 Terminal 53, min. scaling: Par. 310 Terminal 53, max.
VLT® 8000 AQUA NB!: If Sum or Relative is selected, one of the preset references will always be active. If the preset references are to be without influence, they should be set to 0% (as in the factory setting) via the serial communication port. 211 Preset reference 1 (PRESET REF. 1) Description of choice: 212 Preset reference 2 (PRESET REF. 2) Set the required maximum output current ILIM. 213 Preset reference 3 (PRESET REF. 3) 216 Frequency bypass, bandwidth 214 Preset reference 4 (PRESET REF.
VLT® 8000 AQUA See also parameter 216 Frequency bypass, bandwidth. 221 Warning: Low current, ILOW (WARN. LOW CURR.) Value: 0.0 - par. 222 Warning: High current IHIGH, ✭ 0.0A Function: When the motor current is below the limit, ILOW, programmed in this parameter, the display shows a flashing CURRENT LOW, provided Warning [1] has been selected in parameter 409 Function in case of no load. The frequency converter will trip if parameter 409 Function in case of no load has been selected as Trip [0].
VLT® 8000 AQUA Description of choice: The higher signal limit of the motor frequency, fHIGH, must be programmed within the normal working range of the frequency converter. See drawing at parameter 221 Warning: Low current, ILOW. 225 Warning: Low reference, REFLOW (WARN. LOW REF.) Value: -999,999.999 - REFHIGH (par.226) ✭ -999,999.999 Function: When the remote reference lies under the limit, RefLOW, programmed in this parameter, the display shows a flashing REFERENCE LOW.
VLT® 8000 AQUA to generate a warning signal via terminal 42 or 45 and via the relay outputs. In Closed loop, the unit for the feedback is programmed in parameter 415 Process units. Description of choice: Set the required value within the feedback range (parameter 413 Minimum feedback, FBMIN, and 414 Maximum feedback, FBMAX ). minimum speed (frequency) for too long a period of time.
VLT® 8000 AQUA param. 419 ) and continues operation in standard (normal) "closed loop" mode. NB!: The pipe fill closed loop operation is not started until the PID-start frequences, par. 422 has been reached. then the number set in this parameter (230) would be dimensioned as Bar/Second. Changes to this parameter can be made in steps of .001 units. 231 Filled Setpoint (FILLED SETPOINT) The value to use for the "Filled" Setpoint parameter 231, can be determined by: 1.
VLT® 8000 AQUA ■ Inputs and outputs 300-328 In this parameter group, the functions that relate to the input and output terminals of the frequency converter are defined. The digital inputs (terminals 16, 17, 18, 19, 27, 29, 32 and 33) are programmed in parameters 300-307. The table below gives the options for programming the inputs. The digital inputs require a signal of 0 or 24 V DC. A signal lower than 5 V DC is a logic ‘0’, while a signal higher than 10 V DC is a logic ‘1’.
VLT® 8000 AQUA Value: No function Reset Coasting stop, inverse Reset and coasting stop, inverse Start Reversing Reverse and start DC-braking, inverse Safety interlock Freeze reference Freeze output Selection of Setup, lsb Selection of Setup, msb Preset reference, on Preset reference, lsb Preset reference, msb Speed down Speed up Run permissive Jog Data change lock Pulse reference Pulse feedback Hand start Auto start Latched start Off stop Stop inverse Motor alternation ) Global default setting Function: I
VLT® 8000 AQUA brake current and 115 DC braking time is different from 0. Logic ‘0’ implements DC braking. See DC braking. Safety interlock has the same function as Coasting stop, inverse, but Safety interlock generates the alarm message EXTERNAL FAULT on the display when terminal 27 is logic ‘0’. The alarm message will also be active via digital outputs 42/45 and relay outputs 1/2, if programmed for Safety interlock. The alarm can be reset using a digital input or the [OFF/STOP] key.
VLT® 8000 AQUA active, the frequency converter will always be in Open loop [0], regardless of the selection made in parameter 100 Configuration. Jog is not active if a stop command has been given via terminal 27. Data change lock is selected if data changes to parameters are not to be made via the control unit; however, it will still be possible to carry out data changes via the bus. Pulse reference is selected if a pulse sequence (frequency) is selected as a reference signal.
VLT® 8000 AQUA ■ Analog inputs Two analog inputs for voltage signals (terminals 53 and 54) are provided for reference and feedback signals. Furthermore, an analog input is available for a current signal (terminal 60). A thermistor can be connected to voltage input 53 or 54. The two analog voltage inputs can be scaled in the range of 0-10 V DC; the current input in the range of 0-20 mA.
VLT® 8000 AQUA 309 Terminal 53, min. scaling For reasons of accuracy, voltage losses in long signal lines should be compensated for. (AI 53 SCALE LOW) Value: 0.0 - 10.0 V ✭ 0.0 V 312 Terminal 54, min. scaling Function: This parameter is used for setting the signal value that has to correspond to the minimum reference or the minimum feedback, parameter 204 Minimum reference, RefMIN/413 Minimum feedback, FBMIN. See Reference handling or Feedback handling.
VLT® 8000 AQUA 315 Terminal 60, min. scaling and in parameter 316 Terminal 60, max. scaling. parameter 315 Terminal 60, min. scaling, a value has been selected that exceeds 2 mA. Description of choice: Set the desired time. 315 Terminal 60, min. scaling (AI 60 SCALE LOW) Value: 0.0 - 20.0 mA ✭ 4.0 mA Function: This parameter determines the signal value that corresponds to the minimum reference or the minimum feedback, parameter 204 Minimum reference, RefMIN/413 Minimum feedback, FBMIN.
VLT® 8000 AQUA Outputs (depending on the value set in parameter 322 Terminal 45, output, pulse scaling. If the output is used as a voltage output (0-10 V), a pull-down resistor of 470 (max. 500 ) should be fitted to terminal 39 (common for analog/digital outputs). If the output is used as a current output, the resulting impedance of the connected equipment should not exceed 500 . terminal no.
VLT® 8000 AQUA Description of choice: No function Selected if the frequency converter is not to react to signals. Drive ready The frequency converter control card receives a supply voltage and the frequency converter is ready for operation. Stand by The frequency converter is ready for operation, but no start command has been given. No warning. Running Is active when there is a start command or the output frequency is above 0.1 Hz. Running at ref. value Speed according to reference.
VLT® 8000 AQUA External RefMIN - Ref MAX 0-20 mA and External RefMIN - RefMAX 4-20 mA and External RefMIN - RefMAX 0-32000 p which generates an output signal proportional to the resulting reference value in the interval Minimum reference, RefMIN - Maximum reference, RefMAX (parameters 204/205).
VLT® 8000 AQUA 322 Terminal 45, output, pulse scaling Description of choice: Set the desired value. (AO 45 PULS SCALE) Value: 1 - 32000 Hz ✭ 5000 Hz Function: This parameter allows scaling of the pulse output signal. ■ Relay outputs Relay outputs Relay outputs 1 and 2 can be used to give the present status or a warning. Relay 1 1 - 3 break, 1 - 2 make Max. 240 V AC, 2 Amp. The relay is placed with mains and motor terminals. Relay Outputs Relay 2 4 - 5 make Max. 50 V AC, 1 A, 60 VA. Max.
VLT® 8000 AQUA If the parameter 556 Bus time interval function becomes active, relay 1 and relay 2 will become cut off if they are activated via the serial communication. Programming Motor Alteration. The output is controlled by a timer to activate alternate available run time between multiple motors. ✭ = factory setting. () = display text [] = value for use in communication via serial communication port MG.83.A2.
VLT® 8000 AQUA 323 Relay 1, output function Description of choice: (RELAY1 FUNCTION) See data choice and connections in Relay outputs. Function: This output activates a relay switch. Relay switch 01 can be used for indicating status and warnings. The relay is activated when the conditions for the relevant data values have been fulfilled. Activation/deactivation can be programmed in parameter 324 Relay 1, ON delay and parameter 325 Relay 1, OFF delay. See General technical data.
VLT® 8000 AQUA ■ Application functions 400-434 401 Automatic restart time (AUTORESTART TIME) Value: 0 - 1800 sec. Includes this parameter group, the special functions of the frequency converter PID regulation, setting of the feedback range and the Setup of the Sleep mode function. Additionally, this parameter group includes: - Reset function. - Flying start. - Option of interference reduction method. - Setup of any function upon loss of load, e.g. because of a damaged V-belt.
VLT® 8000 AQUA ■ Sleep mode Sleep mode makes it possible to stop the motor when it is running at low speed, similar to a no load situation. If consumption in the system goes back up, the frequency converter will start the motor and supply the power required. NB!: Energy can be saved with this function, since the motor is only in operation when the system needs it. Sleep mode is not active if Local reference or Jog has been selected The function is active in both Open loop and Closed loop.
VLT® 8000 AQUA 403 Sleep mode timer 406 Boost setpoint (SLEEP MODE TIMER) Value: 0 - 300 sec.(OFF) (BOOST SETPOINT) ✭ OFF Function: This parameter enables the frequency converter to stop the motor if the load on the motor is minimal. The timer in parameter 403 Sleep mode timer starts when the output frequency drops below the frequency set in parameter 404 Sleep frequency. When the time set in the timer has expired, the frequency converter will turn off the motor.
VLT® 8000 AQUA NB!: Switching frequencies higher than 4.5 kHz implement automatic derating of the maximum output of the frequency converter. See Derating of high switching frequency. 408 Interference reduction method (NOISE REDUCTION) Value: ✭ASFM (ASFM) Fixed switching frequency (FIXED SWITCHING FREQ.) LC filter fitted (LC-FILTER CONNECTED) [0] [1] [2] Function: Used to select different methods for reducing the amount of acoustic interference from the motor.
VLT® 8000 AQUA Function: Select the function which is to be activated when the frequency converter is exposed to an overtemperature condition. Description of choice: At Trip [0] the frequency converter will stop the motor and export an alarm. At Autoderate & warning [1] the frequency converter will first reduce the switching frequency to minimize internal losses. If the overtemperature condition persists, the frequency converter will reduce the output current until the heat sink temperature stabilizes.
VLT® 8000 AQUA 415 Units relating to closed loop (REF. / FDBK.
VLT® 8000 AQUA Correction for voltage losses in long signal cables can be carried out when using a transmitter with a voltage output. This is done in parameter group 300 Min./Max.scaling. Feedback The feedback signal must be connected to a terminal on the frequency converter. Use the list below to decide which terminal to use and which parameters to program.
VLT® 8000 AQUA Start-up conditions In some applications, optimum setting of the process regulator will mean that it takes an exces-sive time for the required process state to be reached. In such applications it might be an advantage to fix an output frequency to which the frequency converter is to bring the motor before the process regulator is activated. This is done by programming a PID start-up frequency in parameter 422.
VLT® 8000 AQUA ■ PID overview The block diagram below shows reference and setpoint in relation to the feedback signal. ■ Feedback handling The feedback handling can be seen from the block diagram on the next page. The block diagram shows how and by which parameters the feedback handling can be affected. Options as feedback signals are: voltage, current, pulse and bus feedback signals. In zone regulation, feedback signals must be selected as voltage inputs (terminals 53 and 54).
VLT® 8000 AQUA 1 setpoint and 1 feedback If only 1 setpoint and 1 feedback signal are used, parameter 418 Setpoint 1 will be added to the remote reference. The sum of the remote reference and Setpoint 1 becomes the resulting reference, which will then be compared with the feedback signal. 1 setpoint and 2 feedbacks Just like in the above situation, the remote reference is added to Setpoint 1 in parameter 418. Depending 416 Feedback conversion (FEEDBACK CONV.
VLT® 8000 AQUA Value: Minimum (MINIMUM) ✭Maximum (MAXIMUM) Sum (SUM) Difference (DIFFERENCE) Average (AVERAGE) 2-zone minimum (2 ZONE MIN) 2-zone maximum (2 ZONE MAX) Feedback 1 only (FEEDBACK 1 ONLY) Feedback 2 only (FEEDBACK 2 ONLY) [0] [1] [2] [3] [4] [5] [6] [7] [8] Function: This parameter allows a choice between different calculation methods whenever two feedback signals are used.
VLT® 8000 AQUA The setpoint can be offset with digital, analog or bus signals, see reference handling. Used in Closed loop [1] parameter 100 Configuration and only if 2-zone minimum/maximum is selected in parameter 417 Feedbackfunction. Description of choice: Set the required value. The process unit is selected in parameter 415 Process units. 420 PID normal/inverse control (PID NOR/INV.
VLT® 8000 AQUA 426 PID differentiator gain limit Used in Closed loop [1] (parameter 100). (PID DIFF. GAIN) Quick regulation is obtained by a high gain, but if the gain is too high, the process may become unstable. 424 PID integration time (PID INTEGR.TIME) Value: 0.01 - 9999.00 sec. (OFF) ✭ OFF Function: The integrator provides a constant change of the output frequency during constant error between the reference/setpoint and the feedback signal.
VLT® 8000 AQUA 434 Motor Alteration Function (MOTOR ALT. FUNCTION) Value: ✭Ramp (RAMP) Coast (COAST) [0] [1] Function: When a motor is stopped after the duration set in parameter 433, Motor alternation time expires, the motor is commanded to either coast or ramp to a stop. If the motor is not running at the time of alteration, the relay simply changes state. If the motor is running at the time of alteration, a start command is sent following alteration.
VLT® 8000 AQUA Using the frequency for initiating sleep-mode is acceptable in many cases, but if the suction pressure is varying or the pump has a flat pump curve toward low speed, this method might not be accurate enough. The enhanced sleep mode has been developed to overcome problems under such conditions. If operating with constant pressure control in the system, for instance a drop in the suction pressure will lead to an increase in frequency to maintain pressure.
VLT® 8000 AQUA • • • • • Dry run protection. Shuts down at no or low flow and protects the motor and pump from overheating. Improved energy savings with Enhanced sleep mode. Minimized risk of bacterial growth in drinking water because of insufficient motor cooling. Easy commissioning. Works together with the Danfoss cascade controller. Only centrifugal pumps with radial impeller show a clear one to one relationship between flow and power.
VLT® 8000 AQUA 466 Maximum Pump Frequency Description of choice: (PUMP MAX. FREQ) Value: Value par. 201 fMIN - par. 202 fMAX (Hz) ✭ 50 Function: This parameter is linked to parameter 468 Maximum pump power and is used for the no/low flow power curve. Description The factor is multiplied to the power values. E.g. 1.2 will increase the power value with 1.2 over the whole frequency range. 470 Dry Run Time Out (DRY RUN TIME OUT) Value: 5-30 sec.
VLT® 8000 AQUA not be able to reset (automatically or manually) a dry run trip before the timer has expired. 472 Boost Time-Out (BOOST TIMEOUT) Value: 0 (DISABLE) - 999 s ✭ 30 min. Function: Use this parameter to specify the maximum time spent to reach the Boost setpoint specified in parameter 406. If the boost setpoint cannot be reached within the specified time, the frequency converter will continue in normal operation (Not entering sleep mode).
VLT® 8000 AQUA ■ Serial communication for FC protocol * Please note that these are option cards with separate input terminals. ■ Telegram communication Control and reply telegrams The telegram communication in a master/slave system is controlled by the master. A maximum of 31 slaves can be connected to one master, unless a repeater is used. If a repeater is used, a maximum of 126 slaves can be connected to one master.
VLT® 8000 AQUA Pause time, min.: Response time, min.: Response time, max.: 2 characters 2 characters 20 msec. The time between individual characters in a telegram is not to exceed 2 characters and the telegram must be completed within 1.5 times the rated telegram time. If the baudrate is 9600 kbaud and the telegram length is 16 baud, the telegram must be completed within 27.5 msec. Telegram length (LGE) Thetelegram length is the number of data bytes plus address byte ADR plus data control byte BCC.
VLT® 8000 AQUA ■ Data character (byte) The build-up of data blocks depends on the type of telegram. There are three types of telegram and the telegram type applies to both control telegram (master slave) and reply telegram (slave master). The three types of telegram are the following: 1. Parameter bytes 1. Parameter block, used for transferring parameters between master and slave. The data block has 12 bytes (6 words) and also contains the process block. 3.
VLT® 8000 AQUA If the command cannot be carried out, the slave will send this reply (0111) Command cannot be executed and give the following error message in the parameter value (PWE): Example - Index: The first error code (index [1]) in parameter 615 Error code must be read. (reply 0111) 0 PKE = 1267 Hex (read parameter 615 Error code). IND = 0001 Hex - Index no. 1.
VLT® 8000 AQUA VLT 8000 AQUA has two parameters for which a text can be written: parameters 533 and 534 Display text, see the description of these under the parameter description. In order to write a text via the PWE block, the parameter command (AK) must be set to ’F’ Hex.
VLT® 8000 AQUA Conversion: The different attributes for each parameter can be seen in the section on factory settings. Since a parameter value can only be transferred as a whole number, a conversion factor must be used to transfer decimals. Example: Parameter 201: minimum frequency, conversion factor 0.1. If parameter 201 is to be set to 10 Hz, a value of 100 must be transferred, since a conversion factor of 0.1 means that the transferred value will be multiplied by 0.1.
VLT® 8000 AQUA ■ Control word according to FC protocol The control word is used for transmitting commands from a master (e.g. a PC) to a slave. starting are fulfilled. Note: In parameter 503 Coasting stop the choice is made of how bit 03 is to be gated with the corresponding function of terminal 27. Bit 04, Quick stop: Bit 04 = "0" leads to a stop in which the motor speed is ramped down to stop via parameter 207 Ramp-down time. Bit = 0 Bit =1 Preset ref. lsb Preset ref.
VLT® 8000 AQUA to disconnect the control word if it is not to be used in connection with updating or reading of parameters. Bit 11, Relay 1: Bit 11 = "0": Relay 1 is not activated. Bit 11 = "1": Relay 1 is activated, provided Control word bits 11/12 has been selected in parameter 323 Relay outputs. Bit 12, Relay 2: Bit 12 = "0": Relay 2 is not activated. Bit 12 = "1": Relay 2 is activated, provided Control word bits 11/12has been selected in parameter 326 Relay outputs.
VLT® 8000 AQUA Bit 10, Out of frequency range: Bit 10 = "0" if the output frequency has reached the value in parameter 201 Output frequency low limit or parameter 202 Output frequency high limit. Bit 10 = "1" means that the output frequency is within the limits stated. Bit 11, Not running/running: Bit 11 = "0" means that the motor is not running. Bit 11 = "1" means that the VLT 8000 AQUA has a start signal, or that the output frequency is greater than 0 Hz. Bit 12, No function: Bit 12 has no function.
VLT® 8000 AQUA ■ Present output frequency The value of the present output frequency of the frequency converter at any given time is transmitted as a 16-bit word. The value is transmitted in the form of whole numbers 0 -± 32767 (±200 %). 16384 (4000 Hex) corresponds to 100 %. The output frequency has the following format: 0-16384 (4000 Hex) 0-100 % (Par. 201 Output frequency low limit - Par. 202 Output frequency high limit).
VLT® 8000 AQUA ■ Serial communication 500-556 In this parameter group, the serial communication of the frequency converter is set up. In order to use serial communication, address and baudrate must always be set. In addition, such present operational data as reference, feedback and motor temperature can be read via serial communication. Description of choice: The transmission speed of the frequency converter must be set at a value that corresponds to the transmission speed of the master.
VLT® 8000 AQUA 504 DC brake (DC BRAKE) [0], Serial communication [1], Logic and [2] or Logic or [3] has been selected. Value: Digital input (DIGITAL INPUT) Serial communication (SERIAL PORT) Logic and (LOGIC AND) ✭Logic or (LOGIC OR) [0] [1] [2] [3] Digital input [0] Serial Kl.18 com. Function 0 0 Stop 0 1 Stop 1 0 Start 1 1 Start Function: See functional description under parameter 503 Coasting.
VLT® 8000 AQUA 1 0 Counterclock. 1 1 Counterclock. Logic and [2] Serial Kl.19 com.Function 0 0 Clockwise 0 1 Clockwise 1 0 Clockwise 1 1 Counterclock. Serial communication [1] Serial Kl.19 com.Function 0 0 Clockwise 0 1 Counterclock 1 0 Clockwise 1 1 Counterclock. Logic or [3] Serial Kl.19 com.Function 0 0 Clockwise 0 1 Counterclock. 1 0 Counterclock. 1 1 Counterclock.
VLT® 8000 AQUA Logic or [3] Bus Bus Setup/Pre- Setup/Premsb lsb set set msb lsb 0 0 0 0 0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0 0 1 1 1 1 0 0 0 1 0 0 1 1 0 1 0 1 0 1 1 1 1 0 0 1 1 0 1 1 1 1 0 1 1 1 1 Setup no. Preset ref. no. 1 2 3 4 2 2 4 4 3 4 3 4 4 4 4 4 ✭ = factory setting. () = display text [] = value for use in communication via serial communication port 162 MG.83.A2.
VLT® 8000 AQUA 509 - 532 Data read-out Description 509 510 511 512 513 514 515 516 517 518 519 520 521 522 Resulting reference Resulting reference [unit] Feedback [unit] Frequency [Hz] User-defined read-out Motor current [A] Power [kW] Motor voltage [V] Motor voltage [V] DC link voltage [V] Thermal load, motor [%] Thermal load, VLT [%] Digital input Terminal 53, analog input [V] 523 Terminal 54, analog input [V] 524 Terminal 60, analog input [mA] 525 526 527 528 529 530 531 532 537 Pulse reference
VLT® 8000 AQUA Motor voltage, parameter 517: Gives the voltage fed to the motor. DC link voltage, parameter 518: Gives the intermediate circuit voltage of the frequency converter. Thermal load, motor [%], parameter 519: Gives the calculated/estimated thermal load on the motor. 100 % is the cut-out limit. See also parameter 117 Motor thermal protection. Thermal protection, VLT [%], parameter 520: Gives the calculated/estimated thermal load on the frequency converter. 100 % is the cut-out limit.
VLT® 8000 AQUA 533 Display text 1 536 Bus feedback 2 (BUS FEEDBACK2) (DISPLAY TEXT ARRAY 1) [XXXXXXXXXXXXXXXXXXXX] CLEANING SYSTEM NO.2 VLT NO.8 SETUP 1 175ZA792.10 Function: Here, a text of max. 20 characters can be written that will be shown in display line 1, provided LCP display text [27] has been selected in parameter 007 Large display read-out. Example of display text.
VLT® 8000 AQUA Description of choice: message. The resulting retransmissions of messages will slow communications on the network. If this value is set too long, the drive will wait longer than necessary to determine that the message is completed. This will delay the drive’s response to the message and possibly cause the master controller to time out. The resulting retransmissions of messages will slow communications on the network.
■ Warning words 1+2 and Alarm word Warning word, extended status word and alarm word are shown in Hex format on the display. If there is more than one warning or alarm, a sum of the total warnings or alarms will be shown.
VLT® 8000 AQUA ■ Service functions 600-631 This parameter group contains functions such as operating data, data log and fault log. It also has information on the nameplate data of the frequency converter. These service functions are very useful in connection with operating and fault analysis in an installation. 600-605 Operating data Value: Parameter no. 600 601 602 603 604 605 Description Operating data: Operating hours Hours run kWh counter No. of cut-ins No. of overtemps. No.
VLT® 8000 AQUA 606 - 614 Data log Value: Parameter no. 606 607 608 609 610 Description Data log: Digital input Control word Status word Reference Feedback Display text Unit (LOG: DIGITAL INP) (LOG: BUS COMMAND) (LOG: BUS STAT WD) (LOG: REFERENCE) (LOG: FEEDBACK) Decimal Decimal Decimal % Par. 414 611 612 613 614 Output frequency Output voltage Output current DC link voltage (LOG: MOTOR FREQ.) (LOG: MOTOR VOLT) (LOG: MOTOR CURR.) (LOG: DC LINK VOLT) Hz Volt Amp Volt 63.
VLT® 8000 AQUA 615 Fault log: Error code Description of choice: The fault log is only reset after manual initialization. (See Manual initialization). (F. LOG: ERROR CODE) Value: [Index 1-10] Error Code: 0 - 99 Function: This parameter makes it possible to see the reason why a trip (cut-out of the frequency converter) occurs. 10 [1-10] log values are stored. The lowest log number [1] contains the latest/most recently saved data value; the highest log number [10] contains the oldest data value.
VLT® 8000 AQUA Function: In addition to its normal function, this parameter can be used for two different tests. Furthermore, it is possible to reset to the default factory settings for all Setups, except parameters 501 Address, 502 Baud rate, 600-605 Operating data and 615-617 Fault log. Description of choice: Normal function [0] is used for normal operation of the motor.
VLT® 8000 AQUA 621 - 631 Nameplate Value: Parameter nr. 621 622 623 624 625 626 627 628 629 630 631 Description Nameplate: Unit type Power component VLT ordering no. Software version no. LCP identification no. Database identification no. Power component identification no. Application option type Application option ordering no. Communication option type Communication option ordering no.
VLT® 8000 AQUA NB!: Parameters 700-711 for the relay card are only activated if a relay option card is installed in the VLT 8000 AQUA. 702 Relay 6, OFF delay (RELAY6 OFF DELAY) 705 Relay 7, OFF delay (RELAY7 OFF DELAY) 708 Relay 8, OFF delay 700 Relay 6, function (RELAY8 OFF DELAY) (RELAY6 FUNCTION) 711 Relay 9, OFF delay 703 Relay 7, function (RELAY9 OFF DELAY) (RELAY7 FUNCTION) Value: 0 - 600 sec. 706 Relay 8, function (RELAY8 FUNCTION) 709 Relay 9, function ✭ 0 sec.
VLT® 8000 AQUA 80.0% 5.08A 2.15kW 40.0Hz SETUP 1 175ZA701.10 ■ Status messages Status messages appear in the 4th line of the display - see example below. The left part of the status line indicates the active type of control of the frequency converter. The centre part of the status line indicates the active reference. The last part of the status line gives the present status, e.g. "Running", "Stop" or "Stand by". AUTO REMOTE RUNNING HAND LOCAL STOP OFF LOCAL STOPRAMPING HAND JOGGING . . . .
VLT® 8000 AQUA Automatic Motor Adaptation completed (AMA STOP) Automatic motor adaptation has ben completed. The frequency converter is now ready for operation after the Reset signal has been enabled. Please note that the motor will start after the frequency converter has received the Reset signal. Stand by (STANDBY) The frequency converter is able to start the motor when a start command is received.
VLT® 8000 AQUA ■ List of warnings and alarms The table gives the different warnings and alarmsand indicates whether the fault locks the frequency converter. After Trip locked, mains supply must be cut and the fault must be corrected. Reconnect mains supply and reset the frequency converter before being ready. A Trip can be reset manually in three ways 1. Via the control key [RESET] 2. Via a digital input 3.
VLT® 8000 AQUA 1 TRIP (RESET) ALARM:12 CURRENT LIMIT ■ Warnings and alarms WARNING 1 Under 10 V (10 VOLT LOW) The 10 V voltage from terminal 50 on the control card is below 10 V. Remove some of the load from terminal 50, as the 10 Volts supply is overloaded. Max. 17 mA/min. 590 . WARNING/ALARM 2 Live zero fault (LIVE ZERO ERROR) The current or voltage signal on terminal 53, 54 or 60 is below 50% of the value preset in parameter 309, 312 and 315 Terminal, min. scaling.
VLT® 8000 AQUA giving an alarm. The frequency converter cannot be reset until the counter is below 90%. The fault is that the frequency converter is overloaded by more than 100% for too long. WARNING/ALARM 10 Motor overtemperature (MOTOR TIME) According to the electronic thermal protection (ETR), the motor is too hot. Parameter 117 Motor thermal protection allows a choice of whether the frequency converter is to give a warning or an alarm when the Motor thermal projection reaches 100%.
VLT® 8000 AQUA NB!: AMA can only be carried out if there are no alarms during tuning. CHECK 103, 105 [0] Parameter 103 or 105 has a wrong setting. Correct the setting and start AMA all over. LOW P.105 [1] The motor is too small for AMA to be carried out. If AMA is to be enabled, the rated motor current (parameter 105) must be higher than 35% of the rated output current of the frequency converter. ASYMMETRICAL IMPEDANCE [2] AMA has detected an asymmetrical impedance in the motor connected to the system.
VLT® 8000 AQUA A choice must thus be made by pressing [CHANGE DATA] and choosing "Continue" + [OK] or "Stop" + [OK]. If parameters need to be changed, select "Stop"; start up AMA all over. WARNING 39 CHECK PAR. 104, 106 Parameters 104 Motor frequency fM,N, or 106 Rated motor speed nM,N, have probably not been set correctly. Check the setting and select "Continue" or [STOP]. WARNING 40 CHECK PAR. 103, 105 Parameter 103 Motor voltage, UM,N or 105 Motor current, IM,N has not been set correctly.
VLT® 8000 AQUA ■ Special conditions ■ Aggressive environments In common with all electronic equipment, a frequency converter contains a large number of mechanical and electronic components, all of which are vulnerable to environmental effects to some extent. The frequency converter should not therefore be installed in environments with airborn liquids, particles or gasses capable of affecting and damaging the elec-tronic components.
VLT® 8000 AQUA ■ Calculation of resulting reference The calculation made below gives the resulting reference when parameter 210 Reference type is programmed for Sum [0] and Relative [1], respectively. External reference is the sum of references from terminals 53, 54, 60 and serial communication. The sum of these can never exceed parameter 205 Max. reference. External reference can be calculated as follows: (Par. 205 Max. ref. - Par. 204 Min. ref.) x Ana. signal Te r Ext. ref. = m. 53 [V] Par. 310 Term.
VLT® 8000 AQUA ■ Earth leakage current Earth leakage current is primarily caused by the capacitance between motor phases and the motor cable screen. See drawing on the following page. The size of the leakage current to the earth depends on the following factors, in order of priority: 1. Length of motor cable 2. Motor cable with or without screen 3. Switching frequency 4. RFI filter used or not 5.
VLT® 8000 AQUA ■ Extreme running conditions Short circuit VLT 8000 AQUA is protected against short circuits by means of current measurement in each of the three motor phases. A short circuit between two output phases will cause an overcurrent in the inverter. However, each transistor of the inverter will be turned off individually when the short circuit current exceeds the permitted value.
VLT® 8000 AQUA - the motor cable (type, cross-section, length screened or unscreened) inductance The natural induction causes an overshot UPEAK in the motor voltage before it stabilises itself at a level which depends on the voltage in the intermediate circuit. The rise time and the peak voltage UPEAK affect the service life of the motor. If the peak voltage is too high, motors without phase coil insulation are the ones that will primarily be affected.
VLT® 8000 AQUA ■ Acoustic noise The acoustic interference from the frequency converter comes from two sources: 1. DC intermediate circuit coils 2. Integral fan.
VLT® 8000 AQUA • The current of VLT 8152-8652, 380-480 V and VLT 8052-8402, 525-690 V, is to be derated 1%/Deg C above 40° C to 55° C maximum. ■ Derating for air pressure Below 1000m/3300 ft altitude no derating is necessary. Above 1000m/3300 ft the ambient temperature (TAMB) or max. output current (IVLT,MAX) must be derated in accordance with the diagram below: If VLT 8000 AQUA is operated at temperatures above 45ºC (113°F), a derating of the continuous output current is necessary.
VLT® 8000 AQUA ■ Derating for running at low speed When a centrifugal pump or a fan is controlled by a VLT 8000 AQUA frequency converter, it is not necessary to reduce the output current at low speed because the load characterstic of the centrifugal pumps/fans, automatically ensures the necessary reduction. For CT (Constant Torque) applications, consult motor manufacturer for motor derating guideline based upon operating load and duty cycle.
VLT® 8000 AQUA ■ Air humidity VLT 8000 AQUA has been designed to meet the IEC 68-2-3 standard, EN 50178 pkt. 9.4.2.2/DIN 40040, class E, at 40°C. See specifications under General technical data. Efficiency of VLT 8000 AQUA (η VLT) The load on the frequency converter has little effect on its efficiency. In general, the efficiency is the same at the rated motor frequency fM,N, regardless of whether the motor supplies 100% of the rated shaft torque or only 75%, i.e. in case of part loads.
VLT® 8000 AQUA ■ Mains supply interference/harmonics A frequency converter takes up a non-sinusoidal current from mains, which increases the input current IRMS. A non-sinusoidal current can be transformed by means of a Fourier analysis and split up into sine wave currents with different frequencies, i.e.
■ CE labelling ■ What is covered What is CE labelling? The EU "Guidelines on the Application of Council The purpose of CE labelling is to avoid technical Directive 89/336/EEC" outline three typical situations obstacles to trade within EFTA and the EU. The of using an frequency converter.
VLT® 8000 AQUA ■ Danfoss frequency converter and CE labeling CE labelling is a positive feature when used for its original ■ Compliance with EMC directive 89/336/EEC In the great majority of cases, the frequency converter purpose, i.e. to facilitate trade within the EU and EFTA. is used by professionals of the trade as a complex However, CE labelling may cover many different component forming part of a larger appliance, specifications. This means that is has to be checked system or installation.
Motor cable Yes Yes 300 m unscreened/ unarmoured 50 m br. screened/ armoured MG.83.A2.02 - VLT is a registered Danfoss trademark Yes7) Yes7) 150 m br. screened/ armoured No Yes7) 2) 7) Yes Yes No 1) 3) 7) No No No No No Radiated 30 MHz- 1 GHz screen ends should be made in accordance with the section on electrical installation.
VLT® 8000 AQUA ■ EMC Immunity In order to confirm immunity against interference from electrical phenomena, the following immunity test has been made on a system consisting of a frequency converter (with options, if relevant), a screened/armoured control cable and control box with potentiometer, motor cable and motor. The tests were made in accordance with the following basic standards: EN 61000-4-2 (IEC 1000-4-2): Electrostatic discharges (ESD) Simulation of electrostatic discharges from human beings.
VLT® 8000 AQUA ■ Immunity, continued Basic standard Burst Surge ESD Radiated electro- Mains RF common Radiated radio IEC 1000-4-4 IEC 1000-4-5 1000-4-2 magnetic field distortion mode voltage freq.elect.
VLT® 8000 AQUA ■ Factory settings PNU Parameter # Factory setting Range description 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 Language Active Setup Copying of Setup LCP copy Max value of user-defined readout Unit for user-defined readout Big display readout Small display readout 1.1 Small display readout 1.2 Small display readout 1.
VLT® 8000 AQUA PNU Parameter # Factory setting Range description 201 Output frequency low limit, fMIN 202 Output frequency, fMAX 203 Reference site 0.0 Hz 60 Hz/ 50 Hz Hand/Auto linked Changes 4-setup Con- Data during ver- type operation sion 0.0 - fMAX fMIN -120 Hz Yes Yes Yes Yes Yes Yes index -1 -1 0 6 6 5 0.000-par. 100 par. 100-999.
VLT® 8000 AQUA Conversion index 74 2 1 0 -1 -2 -3 -4 Data type Conversion factor 0.1 100 10 1 0.1 0.01 0.001 0.0001 Data type shows the type and length of the telegram. Data type 3 4 5 6 7 9 198 Description Integer 16 Integer 32 Unsigned 8 Unsigned 16 Unsigned 32 Text string MG.83.A2.
VLT® 8000 AQUA ■ Factory settings PNU Parameter # 300 301 302 303 304 Factory setting Range Changes Conver- Data during sion type operation Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes index 0 0 0 0 0 5 5 5 5 5 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 0 0 0 0 -1 -1 0 -1 -1 0 -4 -4 0 0 0 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 0 0 6 5 0 0 0 0 0 0 6 5 6
VLT® 8000 AQUA ■ Factory settings PNU Parameter # 400 401 402 403 404 405 406 407 Factory setting Range Changes description Reset function Automatic restart time Flying start Sleep mode timer Sleep frequency Wake up frequency Boost setpoint Switching frequency Infinate Automatic 10 sec. Enable Off 0 Hz 60 Hz/ 50 Hz 100% Depends on the 0 - 1800 sec. 0 - 300 sec. fMIN - Par. 405 Par. 404 - fMAX 1 - 200 % 1.5 - 14.
VLT® 8000 AQUA ■ Factory settings PNU Parameter # Factory setting Range description 500 501 Protocol Address FC 001 502 503 504 506 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 555 556 570 571 Baudrate Coasting DC-brake Start Reversing Selection of Setup Selection of Preset Reference Data Read-out: Reference % Data Read-out: Reference Unit Data Read-out: Feedback Data Read-out: Frequency User Defined Read-out Data Rea
VLT® 8000 AQUA ■ Factory settings PNU Parameter # Factory setting Range Changes description 600 601 602 603 604 606 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 Operating data: Operating hours Operating data: Hours run Operating data: kWh counter Operating data: No. of cut-ins Operating data: No. of overtemps Operating data: No.
VLT® 8000 AQUA ■ Option Card (for the four relay option card) PNU Parameter # description Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay 6, 6, 6, 7, 7, 7, 8, 8, 8, 9, 9, 9, Output Function On Delay Off Delay Output Function On Delay Off Delay Output Function On Delay Off Delay Output Function On Delay Off Delay Running 000 sec. 000 sec. NO FUNCTION 000 sec. 000 sec. NO FUNCTION 000 sec. 000 sec. NO FUNCTION 000 sec. 000 sec. Range 0 to 600 sec. 0 to 600 sec. 0 to 600 sec.
VLT® 8000 AQUA ■ Index Digital speed up/down .................................................. 135 Direction of IEC motor rotation ......................................... 75 Display mode ............................................................... 85 A Display mode I ............................................................. 86 analog inputs ............................................................... 31 Display readout ............................................................
VLT® 8000 AQUA High voltage test ........................................................... 61 Pulse feedback ........................................................... 121 Pulse input .................................................................. 31 Pulse reference ........................................................... 121 I Pulse scaling............................................................... 127 IT mains......................................................................
VLT® 8000 AQUA Technical data, mains supply 3 x 525 - 600 V ................. 43, 44 Telegram build-up ........................................................ 149 Telegram communication ............................................... 149 Telegram length ........................................................... 150 Tightening torque .......................................................... 74 Time out .................................................................... 124 Torque characteristics ........
www.danfoss.com/drives 175R0894 MG83A202 *MG83A202* Rev.