FDYMP-L7 Concealed Ceiling Unit Split Sky Air air conditioning systems technical data
Split - Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard.
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 TABLE OF CONTENTS FDYMP-L 1 Features 2 Specifications ................................................................................. ....................................................................... 2 3 Nominal capacity, capacity steps and nominal input Technical specifications 3 Dimensional drawings ..................................................... 6 4 Piping diagrams ........................................................
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 1 1 1 Features + Lightweight and compact: the depth of the unit is just 279mm for all capacity sizes. + Both discharge and suction ducts can be easily connected via flanges on the unit. + The air filter is easily accessible from underneath, even after the installation of the ducts.
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 2 Specifications 1 2 NOMINAL CAPACITY and NOMINAL INPUT For indoor units only: INDOOR UNITS NOMINAL INPUT Cooling Heating kW kW For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS NOMINAL CAPACITY (3) Cooling NOMINAL INPUT Cooling EER ENERGY LABEL Cooling ANNUAL ENERGY Cooling CONSUMPTION For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS NOMINAL CAPACITY (3) Cooling Heating NOMINAL INPUT Co
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 2 Specifications 1 2 TECHNICAL SPECIFICATIONS For indoor units only: INDOOR UNITS DIMENSIONS Unit WEIGHT MATERIAL SOUND LEVEL FAN HEAT EXCHANGER AIR FILTER TEMPERATURE CONTROL PIPING CONNECTIONS 4 Unit Unit Sound pressure (cooling/heating) (1) Sound power (cooling only) (2) Air flow rate (cooling/heating) Speed Type Qty x motor output External static pressure (H-L) Drive Type Rows x stages x fin pitch Face area INSULATION MATERIAL Heat insul
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 2 Specifications 1 2 ELECTRICAL SPECIFICATIONS For indoor units only: CURRENT Nominal running current Max. running current Nominal running current Max.
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 3 Dimensional drawings 1 FDYMP71-100L7 1 2 3 4 5 6 7 8 9 668 (Suspension position) Liquid pipe connection J9.52 Flare connection Gas pipe connectionJ A Flare connection Remote control wiring connection Power supply connection Drain pipe connection VP25 (O.D. J 32, I.D.
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 4 Piping diagrams 1 FDYMP71-125L7 4 Refrigerant flow Cooling Heating Heat exchanger Refrigerant pipe connection port diameters Model FDYMP71L7V1 FDYMP100L7V1 FDYMP125L7V1 Gas J15.9 Liquid J9.52 J19.1 J9.
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 5 Wiring diagrams 1 5 FDYMP71∼125L7 Outdoor Indoor Notes Wired remote control 1. When using the central remote control, see manual for connection to the unit. 2. The infrared remote control model varies according to the combination system. See technical data and catalogs before connecting.
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 6 6-1 Sound level Sound level data 1 6 Sound pressure level 230V, 50Hz Model Cooling/Heating FDYMP71L7V1 Measuring location High Low 37/37 33/33 Location of microphone Unit Suction FDYMP100L7V1 39/39 Sound power level (H) (cooling) 6-1 63 Discharge 34/34 65 Microphone FDYMP125L7V1 6-2 41/41 35/35 66 Sound pressure spectrum Sound pressure level (dB) FDYMP100L7 Sound pressure level (dB) FDYMP71L7 Octave band center frequency
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 6 Sound power spectrum FDYMP71L7 FDYMP100L7 Sound power level (dB) 6-3 Sound level Sound power level (dB) 1 6 6-3 Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW25047-2 3TW25057-2 NOTES FDYMP125L7 Sound power level (dB) 1 2 3 Octave band center frequency (Hz) 3TW25067-2 10 • Split - Sky Air • Indoor Units Data is valid at low ESP operation high tap condition.
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 7 Fan characteristics 1 FDYMP71L7 7 ESP (Pa) Fan curve 71 class motor Air flow (m3/min) 3TW25048-1 FDYMP100L7 ESP (Pa) Fan curve 100 class motor Air flow (m3/min) 3TW25058-1 FDYMP125L7 ESP (Pa) Fan curve 125 class motor Air flow (m3/min) • Split - Sky Air • Indoor Units 3TW25068-1 11
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 1 8 8-1 8 8-1 Accessories Optional accessories Item Remote control Adapter for wiring (interlock for fresh air intake fan) Adaptor for external ON/OFF and monitoring Wiring adapte (electrical heater and hour meter Installation box Remote ON/OFF, forced OFF Wired type 71-100-125 Class BRC1D517 KRP1B59 KRP4A51 EKRP1B2 KRP1B947A EKR0R0 3TW25049-4B * Electrical heater and humidifier are field supply.
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 9 9-1 Control systems Wired remote control 1 9 BRC1D527 9-1 5 x 10 (Round end slit) 6.
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 10 1 10 Center of gravity FDYMP71-125L7 A B 71 - 100 Class Model 920 420 125 Class 1320 600 4TW25049-3 11 Safety device settings FDYMP71-125L7 Model FDYMP Safety devices Fan motor thermal fuse (°C) 71 100 125 152±2 152±2 152±2 3TW21009-2C 14 • Split - Sky Air • Indoor Units
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 12 Installation instructions Drain pipe work Computerised control (forced OFF and ON/OFF operation) Indoor unit installation 1TW25049-2 1 12 15 • Split - Sky Air • Indoor Units • Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 How to clean the air filter Service of switch box Refrigerant piping work Drain pipe work Installation instructions • Split - Sky Air • Indoor Units Names and functions of parts Selecting installation site
• Concealed Ceiling Unit • R-407C • FDYMP71-125L7V1/W1 12 Installation instructions 1 12 Filter fixing plate Filter Detail A Scale 1/1 Only for 125 class Only for 71 & 100 class Filter holding plate Only for 125 class Detail B Scale 1/1 3TW25044-2 NOTES 16 1 Filter must slide in the filter fixing plates (see detail A) 2 Filter holding plate must be mounted correct (see detail B) • Split - Sky Air • Indoor Units