Datasheet

"Expandable" range with display XD26 Part number 88970161
"High-performance" expandable solution with display
Extended memory: 120 lines in LADDER language and up to 700 "typical" blocks in FBD language
LCD with 4 lines of 18 characters and configurable backlighting
Selective parameter setting: You can choose the parameters that can be adjusted on the front panel
Analogue inputs 0-10 V DC or 0-20 mA/Pt 100 with converters (see page 50)
Open to XN network communication extensions and digital I/O or analogue extensions
General environment characteristics for CB, CD, XD, XB, XR and XE product types
Certifications
UL, CSA
GL: except for 88 970 32x (pending)
Conformity with the low voltage directive
In accordance with 73/23/EEC:
EN (IEC) 61131
-
2 (Open equipment)
Conformity with the EMC directive
In accordance with 89/336/EEC:
EN (IEC) 61131
-2 (Zone B)
EN (IEC) 61000
-6-2,
EN (IEC) 61000
-6-3 (*)
EN (IEC) 61000
-6-4
(*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B: using in metallic
cabinet)
Earthing
None
Protection rating
In accordance with IEC/EN 60529:
IP40 on front panel
IP20 on terminal block
Overvoltage category
3 in accordance with IEC/EN 60664
-1
Pollution
Degree: 2 in accordance with IEC/EN 61131
-2
Max operating Altitude
Operation: 2000 m
Transport: 3,048 m
Mechanical resistance
Immunity to vibrations IEC/EN 60068
-2-6, Fc test
Immunity to shock IEC/EN 60068
-2-27, Fa test
Resistance to electrostatic discharge
Immunity to ESD IEC/EN 61000
-4-
2, level 3
Resistance to HF interference
Immunity to radiated electrostatic fields
IEC/EN 61000
-4-3,
Immunity to fast transients (burst immunity)
IEC/EN 61000
-4-
4, level 3
Immunity to shock waves
IEC/EN 61000
-4-5
Radio frequency in common mode
IEC/EN 61000
-4-
6, level 3
Voltage dips and breaks (AC)
IEC/EN 61000
-4-11
Immunity to damped oscillatory waves
IEC/EN 61000
-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022/11 group 1
(*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) + 88 970 241 class A (class B in metallic cabinet)
Operating temperature
-
20→+55°C(+40°Cinanon
-ventilated enclosure) in accordance with IEC/EN 60068-2-
1 and IEC/EN 60068
-2-2
Storage temperature
-
40→+70°CinaccordancewithIEC/EN60068
-2-
1 and IEC/EN 60068
-2-2
Relative humidity
95% max. (no condensation or dripping water) in accordance with IEC/EN 60068-2-30
Mounting
On symmetrical DIN profile, 35 x 7.5 mm and 35 mm x 15 or panel (2 x 4 mm Ø)
Screw terminals connection capacity
Flexible wire with ferrule =
1 conductor: 0.25 to 2.5 mm
2
(AWG 24...AWG 14)
2 conductors 0.25 to 0.75 mm
2
(AWG 24...AWG 18)
Semi
-rigid wire =
1 conductor: 0.2 to 2.5 mm
2
(AWG 25...AWG 14)
Rigid wire =
1 conductor: 0.2 to 2.5 mm
2
(AWG 25...AWG 14)
2 conductors 0.2 to 1.5 mm
2
(AWG 25...AWG 16)
Tightening torque =
0.5 N.m (4.5 lb
-in) (tighten using screwdriver diam. 3.5 mm)
Processing characteristics of CB, CD, XD & XB product types
LCD display
CD, XD: Display with 4 lines of 18 characters
Programming method
Ladder or function blocks/SFC (Grafcet)
Program size
Ladder: 120 lines
Function blocks:
CB, CD: typically 350 blocks
XB, XD: typically 700 blocks
Program memory
Flash EEPROM
Removable memory
EEPROM
Data memory
368 bits/200 words
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
16/12/2011 www.crouzet.com

Summary of content (4 pages)