User's Manual

1 of 4 LPN00212X0003A7
CS Series With Cree SmartCast™ Technology
CS14, CS18 LED Linear Luminaire
8' and 4' Luminaires
INSTALLATION INSTRUCTIONS
INSTRUCTIONS D’INSTALLATION
• The CS Series LED linear luminaire is for
suspended, with cable or threaded rod, or
surface mount applications using appropriate
tong hangers. Reference individual mounting
accessory installation instructions for specific
mounting types.
• Designed for use in 120–277V, 50-60 Hertz
protected circuit (fuse box, circuit breaker) and
supply wire shall be rated minimum 12AWG,
600V, 90 C rated).
TO INSTALL:
NOTE: When removing luminaire from packaging, keeping
protective plastic wrap on fixture during installation and
construction.
FOR PLASTIC TONG HANGERS (TM):
NOTE: Center hole can accommodate 1/2" diameter rod
maximum.
STEP 1:
Remove cross brace and securely insert it into the “+” shaped
openings in the plastic tong hanger. See Figures 1 & 2. For single
units or end row fixtures, place the plastic tong hanger assembly
into center spine no more than 18" from each end of fixture and
twist approximately 45 degrees until the plastic tong hanger
assembly is securely in place and approximately 90 degrees to
the length of fixture. See Figure 3.
STEP 2:
For continuous row installation, continue with next fixture using
a minimum of one tong hanger per unit. Each bracket should be
properly snug and be difficult to slide along the back spine.
1
2
Cross Brace
Cross Brace
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. DANGER- Risk of shock- Disconnect power before installation.
DANGER – Risque de choc – Couper l’alimentation avant
l’installation.
2. This luminaire must be installed in accordance with the NEC or your
local electrical code. If you are not familiar with these codes and
requirements, consult a qualied electrician.
Ce produit doit être installé conformément à NEC ou votre code
électrique local. Si vous n’êtes pas familier avec ces codes et ces
exigences, veuillez contacter un électricien qualié.
3. Check to make sure that all the xture connections have been properly
made and the xture is grounded to avoid potential electrical shocks.
4. Do not handle energized module with wet hands or when standing on
wet or damp surfaces, or in water.
5. Suitable for damp locations.
Convient aux emplacements humides.
SAVE THESE INSTRUCTIONS FOR FUTURE
REFERENCE
WARNING - Maximum connected load with a single power supply shall
not exceed maximum ampacity rating of #12 AWG THHN through-wire
conductors. Use only lighting controls with relay or FET-based outputs,
or lighting controls with neutral connection. Reference www.cree.com/
lighting for recommended dimming control options. Avoid handling
LEDs directly. Not intended for use in environments containing airborne
corrosive agents such as chemical solvents, cleaners, or cutting uids