Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL WWW.LUMINSMART.COM LS-100544 Rev.
® U.S. Registered Trademark. Patents pending. Copyright © 2022 Coulomb, Inc. (DBA Lumin). All rights reserved.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL TABLE OF CONTENTS INTRODUCTION.................................................................................................................................................. 1 READ BEFORE USE ............................................................................................................................................. 2 Warnings ................................................................................................
This page intentionally left blank
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL INTRODUCTION Welcome! The Lumin Smart Panel (LSP) is a standalone product that extends the capability of an existing circuit breaker panel (or “electrical panel”) by providing measurement and remote control of up to twelve (12) circuits in a home or building. The function of the circuit breaker panel remains the same and is not impacted.
READ BEFORE USE The LSP interfaces with existing electrical panels and includes conduit/fittings for installation with surface-mount electrical panels. Verify the label model number is LSP-12-OR before performing an outdoor installation. Please review the product’s technical ratings and specifications (pg. 35) to confirm it is suitable for your application prior to installation.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL SYSTEM DESIGN CONSIDERATIONS • The LSP should be mounted so that the connected electrical panel is within reach of the LSP’s flexible conduit fitting. The fitting extends 13" beyond the left face or 9” beyond the right face of the LSP enclosure. Ensure that the electrical panel has adequate wiring space for LSP conductors and connections. Suitable junction boxes and conduit may be used to route and/or extend LSP conductors if needed.
INSTALLATION Items in the Box 1 Outdoor LSP with Conduit, Conduit Bushings & Wire Whips Attached Upper Outdoor Wall Mounting Brackets Lower Outdoor Wall Mounting Brackets 1 Pair of 200A Current Transformers (A second pair is optional) NOTE: Additional items include an antenna, installation hardware, and an LSP Circuit Label & CT Table.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL Required Materials (Not Included) Wire splice connectors Cable ties (Optional) Pen or marker Supply-side/line-side tap (Optional) Dual-pole breaker: 15 to 20 amps 3/4" Liquid-tight conduit and fittings (Optional Ethernet cable) (Optional) NOTE: Additional supplies may be required depending on the existing electrical panel installation. A NON-GFCI dual-pole breaker of 15 to 20 amps may be required to power the LSP.
Required Tools Utility knife 2” Knockout punch (2-3/8” hole size) Level Tape measure Wire stripper Pliers Stud-finder (Optional) Fish tape (Optional) Phillips screwdriver Flathead screwdriver Drill Multimeter (Optional) NOTE: A multimeter may be required for determining current transformer placement (see pg. 25).
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL Hardware Installation Overview STEP 1. Turn Off Main Feed and Remove Electrical Panel Cover STEP 2. Knock Out or Punch One Hole for 2” Conduit Fitting STEP 3. Determine LSP Mounting Position Relative to Conduit Routing STEP 4. Measure and Mark Hole Locations for Mounting STEP 14. Record Circuit Label/Name and Breaker Row (A/B) With Corresponding LSP Wire Number STEP 15. Repeat Steps 11-14 Until All LSP Line # Wires Are Connected STEP 16.
Hardware Installation Steps STEP 1. Turn Off Main Feed and Remove Electrical Panel Cover WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 2. Knock Out or Punch One Hole for 2” Conduit Fitting WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
STEP 3. Determine LSP Mounting Position Relative to Conduit Routing WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. NOTE: The LSP must be mounted in the vertical orientation shown (with the conduit exiting the LSP from the bottom).
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 4. Measure and Mark Hole Locations for Mounting Location of Mounting Holes and Slots (Large Arrows) Bracket Attachment Stud Locations (Small Dashed Arrows) Marking Hole Locations Using Brackets Tools: Tape measure, marker, stud-finder (optional), and level. NOTE: The LSP must be mounted in the vertical orientation shown.
STEP 5. Secure Mounting Brackets to Wall Tools: Drill, stud-finder (optional), screws (x4), and washers (x4) NOTE: Ensure the outer screws of the upper bracket are securely threaded into studs, sheathing, brick, masonry, or other suitable structural anchors. For masonry applications (including brick) use the appropriate fasteners included in the installation hardware. Exterior cladding such as vinyl or aluminum siding are examples of unsuitable anchors.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 6. Attach LSP Antenna and Guide LSP Wire Whip into Electrical Panel Attach Antenna Wire Whip Conduit Bushing WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
STEP 7. Secure LSP to Wall/Bracket and Electrical Panel WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. Tools: Drill, washer, and nuts (x3) NOTE: Lift the LSP to align with the mounting holes and secure it to the mounting brackets utilizing the hardware provided. Use two nuts with the upper bracket.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 8. Connect LSP Equipment Grounding Conductor (EGC) to Ground Bar EGC to Ground Bar WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. GROUND WIRE MUST BE INSTALLED FOR SAFETY. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. UN FIL DE TERRE DOIT ÊTRE INSTALLÉ POUR LA SÉCURITÉ.
STEP 9. Identify A-Row and B-Row Breakers A B A B A B NOTE: For purposes of Lumin installation, the top row of breakers will always be classified as “A”. The second row of standard breakers will be “B”. The alternating A-B-A-B pattern continues down the rows of breakers. Exception: All breaker rows are designated “A” in panels with two-wire single-phase power rather than three-wire single-phase (split phase).
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 10. Connect LSP Power Circuit and Label Breaker “Neutral” (White) “Line A” (Black) to A-Row Breaker “Line B” (Red) to B-Row Breaker A B A B A B WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
STEP 11. Select Circuit Breaker to Connect to LSP, Turn Off, and Disconnect Load Disconnect Load Wire Turn Off Circuit WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. Tools: Screwdriver NOTE: Breaker labels should be marked to indicate that the load connects to the LSP.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 12. Connect One LSP Wire Labeled “Line 1 Breaker” to Circuit Breaker Load Wire “Line 1 Breaker” WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
STEP 13. Connect Corresponding LSP Wire Labeled “Line 1 Load” to Load and Turn Circuit Breaker Back On Load Wire “Line 1 Breaker” “Line 1 Load” WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 14. Record Circuit Label/Name and Breaker Row (A/B) With Corresponding LSP Wire Number Refrigerator Single-pole circuit Range Double-pole circuit Range NOTE: Record the circuit label/name and breaker row (A or B) with the corresponding LSP line number in the LSP Circuit Label & CT Table provided with the LSP (ex.
STEP 15. Repeat Steps 11-14 Until All LSP Line # Wires Are Connected x 12 “Line # Breaker” “Line # Load” WARNING: HIGH VOLTAGE. AVERTISSEMENT: HAUTE TENSION. Tools: Screwdriver, wire stripper, and wire splice connectors NOTE: All LSP wires labeled “Breaker” must connect to a breaker. Lines 1-6 (6 AWG wire) can connect to circuit breakers rated up to 60 amps and lines 7-12 (10 AWG wire) can connect to circuit breakers rated up to 30 amps (see pg. 35).
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 16. Determine Placement of Current Transformers (CTs) DO NOT INSTALL CTS UNTIL PROPER LOCATION AND PHASING HAVE BEEN DETERMINED. Each LSP is supplied with one set of two (2) 200-amp current transformers (CTs). The LSP is equipped with leads for these main CTs as well as leads for an optional set of auxiliary CTs which is available for purchase from Lumin.
STEP 17. Phase Conductors Monitored by Current Transformers REMINDER: For the purpose of a Lumin installation, the top* row of breakers in an electrical panel is always designated “A”. Whichever feeder leg supplies breaker Row A will be designated “A.” NOTE: Lumin CTs are designated either “A” or “B”. Placing them on the incorrect leg of a circuit will result in erroneous consumption data.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 18. Testing for Crossover before Current Transformer Placement To determine A and B feeders when a main circuit breaker is present, test for AC voltage between the left lug and the left bus bar*. If the bus bar is not accessible, test between the left lug and the terminal on the top left circuit breaker. See Figure C. If V between these points ≈ 240, the main breaker is a crossover type.
STEP 19. Connecting Current Transformers Prior to installation, measure the CT leads’ routing path(s) in the electrical panel. Local electrical codes may require securing CT wiring at regular intervals. If the provided leads are not long enough, fashion CT wire extensions in the field. Scan the adjacent code for information on the proper extension procedures. When installing CTs, connect CTs labeled “Line A/B CT” to the 2-pin connector on the corresponding LSP lead first.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 20. Record Line Name(s) of Corresponding Current Transformers LSP LINE # BREAKER ROW (circle one) CIRCUIT BREAKER LABEL/NAME LSP LINE # A BREAKER ROW (circle one) CIRCUIT BREAKER LABEL/NAME A 1 7 B B A A 2 8 B B A A 3 9 B B A A 4 10 B B A A 5 11 B B A A 6 12 B B CURRENT TRANSFORMER (CT) Line A/B CTs Ex. Main Service Lines CURRENT TRANSFORMER (CT) Aux. A/B CTs (Optional) Ex.
STEP 21. Connect the LSP’s Grid Detection Circuit (GDC) Wires to the Grid Side of an Automatic Transfer Switch (ATS) or Microgrid Interconnect Device (MID) “Grid Line” (black) Connect black wire to a portion of the electrical system that will lose power in a grid outage “Grid Neutral” (White) WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 22. Replace Electrical Panel Cover and Turn On Main Feed WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
STEP 23. Attach Antenna and Turn On the LSP to Begin Configuration and Account Setup WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. Tools: Screwdriver NOTE: If the LSP cover has not been removed, remove it. Make sure the LSP’s antenna, which is included in the LSP box, is securely attached.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL STEP 24. LSP Configuration Configuration and Account Setup 1. After completing the hardware installation, ensure the LSP power switch is in the “ON” position (“I”). The blue and green indicator lights will begin blinking in unison, indicating that the LSP is ready for commissioning. 2. If feasible, make an Ethernet connection between the Lumin Smart Panel’s Ethernet port and a LAN port on the location’s router.
STEP 25. Reinstall LSP Cover Completed Exterior Wall Mount Installation WARNING: FOR ALL OUTDOOR INSTALLATIONS, OPERATING THE LSP WITH THE COVER REMOVED DURING INCLEMENT WEATHER (RAIN, SNOW, SLEET, DUSTY CONDITIONS, ETC) WILL VOID THE WARRANTY. THE NEMA RATING IS ONLY APPLICABLE WITH THE COVER INSTALLED. NORMAL OPERATION/INSTALLATION OF THE LSP INCLUDES THE INSTALLATION OF THE COVER.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL TROUBLESHOOTING AND REPAIRS End User If the LSP is not functioning as expected, ensure that the power switch is on, Internet service is available, antenna/Ethernet connection is secure, and breakers are switched on. See Operational Information (pg. 34) on how to read the LSP indicators for Internet connectively status. It is best to obtain assistance from a qualified installer for further troubleshooting of hardware issues.
OPERATIONAL INFORMATION LED Indicator Off On Red “Power” Red “Charged” Power Off or Not Present TPU Charging or Not Present Power On TPU Charged LED Indicator Off Both Blinking Just One Blinking Both Solid Green “Network” Blue “Online” Lumin Server Disconnected No Internet Connection via Wi-Fi Setup Mode. Wi-Fi connectivity is disabled.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL PRODUCT SPECIFICATIONS Type Installer Qualification INSTALLATION Surface-Mount; Indoor or Outdoor ELECTRICAL SYSTEM 120/240 VAC Split-Phase, 50–60Hz AC Voltage Local Electrical Codes and Lumin Certified Installer Supply Breaker Rating 15–20 A (non-GFCI) Supply Amperage 0.4 A (Maximum) Typical Time Required 1.
LIMITED WARRANTY FOR LUMIN SMART PANEL This Limited Warranty gives you specific legal rights and you may also have other rights, which vary from state to state. We warrant that during the warranty period, the product will be free from defects in materials and workmanship. We limit the duration and remedies of all implied warranties, including without limitation the warranties of merchantability and fitness for a particular purpose to the duration of this express limited warranty.
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL RADIO FREQUENCY STATEMENT This device complies with Part 15 of the FCC rules and with Innovation, Science and Economic Development Canada’s licence-exempt RSS(s). Operation is subject to the following two conditions: 1. 2. This device may not cause interference. This device must accept any interference, including interference that may cause undesired operation of the device.
NOTES 38
Lumin Smart Panel - Outdoor DOCUMENTATION AND INSTALLATION MANUAL NOTES 39
501 Locust Ave, Floor 1, Suite 2 Charlottesville, VA 22902 SUPPORT@LUMINSMART.COM 1-888-421-0616 WWW.LUMINSMART.COM ® U.S. Registered Trademark. Patents pending. Copyright © 2022 Coulomb, Inc. (DBA Lumin). All rights reserved.