Quick Start Guide

!
Required tools
Specifications
This guide contains the basic instructions for installing
the S700 intelligent access terminal.
For a complete description of the S700 and its
features, refer to the Technical Product Specification
at:
http://www.cemsys.com/S700
Hex security screwdriver Size H20
Pozi head screwdriver Size PZ1
9 to 28
Four analogue inputs - voltage supplied
Typcial: 2.4 / Peak: 4.8
RS485 serial comms / Wiegand protocol
10/100 Base-T TCP/IP CAT6 / RS485 serial comms
24 Vdc @ 2 A
-20 to +70 (-4 °F to +158 °F)Operating temperature (°C)
Dry contacts output
Comms to system host
Comms to exit reader
Inputs
Power (W)
Supply Voltage (Vdc)
Part Rating
IP65
IP rating
2.5 mm
3.0 mm
Flat head screwdriver
Flat head screwdriver
Adding the device to AC2000
Configuring device inputs
Card definitions
1. Open AC2000 | Device Configuration | Devices.
2. In the left pane, expand the Controller to which the terminal is being added.
3. Right-click the appropriate Device Group and select Add Device.
4. From the Device Type drop-down list, select the S700 model to install.
5. From the Configuration Mode drop-down list select the setting that matches
your hardware setup.
6. From the Device Number drop-down list select a device number.
7. Enter a unique description for the device in Device Location .
8. Enter the MAC Address of the device. To display the MAC Address
on the terminal select System Information | Network.
9. Enter the IP address of the device.
10. Click Add to complete the setup.
If inputs are used to trigger alarms or events in AC2000 AED they must first be configured
in the AC2000 Devices application. For more information, see AC2000 Setup Guide.
Ensure that the correct card definition for the chosen card technology is loaded on
the CDC.
2 Mounting the Terminal
1. Remove the four screws and spacers using a Pozi head screwdriver.
2. Remove the two yellow internal speaker wires from connector J6 on
the I/O board.
3. Lift the I/O board away from the back casing.
4. Drill the cable access holes using the guides on the back casing.
5. Drill the holes on the terminal casing to match the back box fixture points.
Opening the terminal
1. Set the terminal on a level surface.
2. Remove the four screws using
a hex security screwdriver.
3. Remove the front part of the
terminal, pivoting at the base.
4. Disconnect the ribbon cable from
the I/O board.
Removing the I/O board
Mounting the back casing to the back box
1. Using the drilled mounting holes, screw the back
casing to the back box.
2. Screw the I/O board to the back casing, ensuring to
replace the spacers.
3. Connect the internal speaker to the I/O board. The
yellow speaker wires can be wired to the J6 speaker
terminal in any order.
GND
0V
SUPPLY
INPUT
NO
RELAY 1
C NC NO
RELAY 2
C
NC
0V
0V
0V
SPEAKER
SPEAKER
SUPPLY INPUT
RS232 TX
RS232 RX
0V
0V
(0) DOOR POS
(1) LOCK POS
0V
SUPPLY INPUT
0V
(3)INTERLOCK
0V
(2)REX
DC OUTPUT
0V
SOUNDER
D1
D0
LED RED
LED GREEN
LED AMBER
0V
RS485 2A
DC OUTPUT
RS485 2B
1B
RS485
INPUT WIEGAND EXIT/DIU HOST
1A
RLY 2RLY 1
LABEL
J3 J7 J2
J6
J9
J10
RELAY
24V DC MAX.
@2A MAX.
SUPPLY INPUT
12V-24V DC NOM.
@2.5A MAX.
DC OUTPUT
12V @ 1A MAX.
D17
D16
J4
J7
DOOR
POSITION
LOCK
SENSE
REQUEST
TO EXIT
-
+
MAGNETIC
LOCK
PSU 12V (2.5A)
or 24V (1.25A)
-
+
GND
0V
SUPPLY
INPUT
NO
C
NC
NO
RELAY 2
C
NC
0V
0V
0V
SPEAKER
SPEAKER
SUPPLY INPUT
RS232 TX
RS232 RX
RLY 2
RLY 1
LABEL
0V
0V
(0) DOOR POS
(1) LOCK POS
(1) LOCK POS
0V
(3)INTERLOCK
0V
(2)REX
DC OUTPUT
0V
SOUNDER
D1
D0
LED RED
LED GREEN
LED AMBER
(1) LOCK POS
J3
J7
J6
J9
J10
RELAY
24V DC MAX.
@2A MAX.
SUPPLY INPUT
12V-24V DC NOM.
@2.5A MAX.
DC OUTPUT
12V @ 1A MAX.
WIE GAND
WIE GAND
WIE GAND
WIE GAND
INPUTS
EXIT/DIU HOST
SUPPLY INPUT
0V
0V
RS485 2A
DC OUTPUT
RS485 2B
1B
1A
J2
RS485
SW1
ANT 1
S700s Reader
S700e Reader
Wiring Configuration: S700e Host + S700s Exit
3a
In fail-secure configuration, if the terminal loses
power, the lock remains closed. A lock that requires
power to open, such as a mortice lock, must be
used.
Fail-secure Lock
If the terminal loses power, a fail-safe lock opens
allowing free access. Therefore, a lock that is
constantly powered, such as a maglock, must be
used.
Fail-safe Lock
DC Output
Third-Party Wiegand Readhead
GND
0V
SUPPLY
INPUT
NO
RELAY 1
C NC
NO
RELAY 2
C
NC
J9
-
+
MAGNETIC
LOCK
GND
0V
SUPPLY
INPUT
NO
RELAY 1
C NC NO
RELAY 2
C
NC
J9
-
+
MORTICE
LOCK
The terminal labelled DC
OUTPUT can ONLY be
used as an output to
power other devices,
such as exit readers and
third-party Wiegand
readheads.
DO NOT connect a
power supply to this
terminal.
0V
SUPPLY INPUT
SUPPLY INPUT
0V
(3)INTERLOCK
DC OUTPUT
0V
SOUNDER
D1
D0
LED RED
LED GREEN
LED AMBER
0V
RS485 2A
DC OUTPUT
RS485 2B
1B
RS485
INPUT
INPUT
WIEGAND
EXIT/DIU
HOST
1A
J3
J7
J2
Third-Party
Wiegand
Head
WIRING NOTES
Quick Installation Guide