Electronic Rack eHandle User Manual
Contents 1: Introduction ................................ ................................................................ ................................................ 3 2: eHandle Overview ................................ ................................................................ ...................................... 4 2.1 Specifications and Functions ................................................................................................ .................................... 4 2.
1: Introduction 1.1 The SmartZone G5 eHandle products are intended to provide access control solutions solution with a series of electronic locking options for Panduit Standard Cabinets monitored and controlled through the Panduit SmartZone G5 PDU. 1.2 1.3 There are five configuration options available for the eHandle family products as the following: SKU No P P/N Description EA9502 EH01 eHandle RFID (125kHz / 13.
Electronic Rack eHandle User Manual 2: eHandle Overview 2.
Functions of each type of Handles P/N eHandle Types EH01 RFID Card Reader EH02 RFID Card+Keypad Description ‐ eHandle RFID (125kHz /13.56MHz) with integral humidity sensor ‐ Support Single factor RFID card authentication ‐ Remote lock/unlock capability ‐ eHandle RFID (125kHz /13.56MHz) 13.56MHz) and Keypad with integral humidity Reader sensor ‐ Support Dual Authentication ‐ Remote lock/unlock capability ‐ Need to provide an option in firmware to hide the pin with * when pin is typed.
Electronic Rack eHandle User Manual The sensor assembly includes harness harness, sensors and accessories.
2.3 eHandle General Features 2.3.1 eHandle Compatibility 1. The eHandle system is compatible with all applicable SmartZone G5 PDUs SmartZone G5 1.0 without PowerShare support (with required firmware upgrade). SmartZone G5 1.5 with PowerShare support. Future SmartZone G5 PDU versions support. 2. Any eHandle is compatible in fit and function with any SmartZone G5 deployment without disrupting the operation of the existing G5 PDU and Sensor configuration. 3.
Electronic Rack eHandle User Manual 4.2 Panel thickness range: 1mm to 2.5mm thick 4.3 Flat CAM Grip range: 15.5mm 4.4 The physical location of the center of the Driver Shaft must be central to the cutout, 25mm below the top of the panel cutout. 4.5 Recommended mechanical interface between the Driver Shaft and the door locking mechanism Driver Shaft Critical Dimensions Cross sectional width: 7.9mm +0/-0.1 Cross sectional height: 7.9mm +0/-0.1 Shaft Protrusion Depth: 3.
4.8 eHandle Support Right-Hand Hand or Left Left-Hand installation. 4.9 The Harness shall be routed to the side of the eHandle opposite the latch area. 2.3.2 eHandle Lock Function The eHandle keypad includes the following features: Input keys to support (10) inputs: be numbered from 0 to 9 inclusive be individual input keys be all metal construction be tactile when pressing keys Key identification numbers and font to be printed in accordance with the published Panduit Branding Guidelines.
Electronic Rack eHandle User Manual 2.3.3 Integrated LED Indicators Integrated LED indicators are available on all configurations. Different colors of warning and status of function can be selected by users. Status LED has the following default configuration which can be controlled by eHandle.
Beacon LED has the following default configuration. Function Locate LED Status Blinking Color Blue, Green, Default Green White, Magenta Critical Description Identify rack location. High Intensity. Customized color. Blinking Red Red Any critical alarm in the system Blinking Yellow Yellow Any warning alarm in the system Solid Blue, Green, Led Off Visual indicator on the PDU, Customized color.
Electronic Rack eHandle User Manual 3: eHandle Installation Instruction 3.1 Types of SmartZone G5 eHandle EH01: - eHandle RFID (125kHz / 13.56MHz) with integral humidity sensor EH02: - eHandle RFID (125kHz / 13.
3.
Electronic Rack eHandle User Manual 3.3 eHandle Lock Mounting Option for Front and Rear Door 3.3.1 If needed, remove any existing lock mechanism. Save the Cam (latch) for later steps. NOTE: The eHandle’s lock requires a cut-out of 150x25mm. Reference Figure below for the following steps. 3.3.2 Position the lock body within the cut-out and flush to the outer face of the cabinet door. Use the 12mm Top Mounting Screws and Top Mounting Bracket to secure the lock to the door. 3.3.
4: eHandle WEB Configuration 4.1 ID User Authorization Authorization/Add Card Once connected, users can be assigned HID cards to complete authentication & authorization authorization. Please go to PDU web by ip address (can get from PDU screen) screen), and enter a username and password to log in. Username: admin Password: 12345678 ID User Authorization/Add Card 1. The Administrator can use Web Interface or SNMP to create user entry with an associated ID card.
Electronic Rack eHandle User Manual 2. Input the Card ID, user name, PIN and date, then click save to add a Card. 3. Each code can be assigned a User Name up to 31 characters long. Note: User name is related to filed name. 4. Expiration time is only applicable to temporary users. After the expiry Date/Time, the expired ID code will no longer be valid. (start when it’s created). 5. Click Save to complete Add Card. If authentication failed, the LED will blink Red three times.
4.2 Rack Access Settings For Rack Access Settings, please go o to Smart Rack Access Control>Actions>Rack Rack Access Settings. Settings Select Aisle Control. Two options can be selected which are Hot/Cold Combined and Hot/Cold Standalone. Hot/Cold Standalone– When hen this is selected selected, aisle control is individual. Hot aisle can control hot aisle, cold aisle can control cold aisle. Hot/Cold Combined – When hen this is selected selected, one aisle can be controlled by opposite aisle.
Electronic Rack eHandle User Manual 4.4 Keypad Settings For Keypad Settings, please go to Smart Rack Access Control>Actions>Keypad Settings. Keypad Settings can be achieved through WEB interface or SNMP. 1) PIN Code length 1 to 15 numeric digits 0 to 9 (default is blank), can be updated in WEB and SNMP, no entry in the MIB. 2) Each PIN code can be assigned a Name up to 31 characters long.
3) Each code de can be entered in a hidden way such a *(invisible by the user) or readable (plain text). This is configurable by pin mode in WEB GUI (Graphical User Interface). When pin mode is active, pin is hidden and displayed as *. When pin mode is disables, pin is visible. 4) Hidden codes are reset to blank if the user changes from Hidden mode to Readable mode. 5) 6 PIN entry uses a 5 second key to key press timeout. 6) Click Save to complete Keypad Settings. 4.5 Remote Control 4.5.
Electronic Rack eHandle User Manual Clicking Lock/Unlock/ on the interface can realize the remote control of the eHandle on site. But actually clicking Unlock on the interface, the Status on the panel is LOCK. Clicking Lock on the interface, the Status on the panel is CLOSED.
Handles can be unlocked by remote control. Once Authentication is received and lock mechanism is opened. Lock mechanism stays open for AUTOLOCK TIME seconds. LED BLINK GREEN for AUTOLOCK TIME. 4.5.2 Any attempt to use this card will be recorded in PDU event log.. Both of event log and data log can be downloaded.
Electronic Rack eHandle User Manual 4.6 Beacon Settings Please go to Smart Rack Access Control>Actions>Beacon Settings. Rack can be located and LED color (vertical) can be set in Beacon Settings. Locate and Standby options can be selected in the dropdown. Locate – This is employed to locate the rack in the data center. When locate is selected beacon will blink with user selected color, helping the user to identify the rack in data center Standby- This is the standby option for beacon.
4.7 Status LED Settings Please go to Smart Rack Access Control>Actions> Control>Actions>Status LED Settings. In function of Standby On, LED stays solid and the default color is Green. 4 Colors Green, Blue, Magenta and White can be selected. Standby off is also lso an option for users.
Electronic Rack eHandle User Manual eHandle status is shown in PDU Security section. When swiping HID card to unlock the eHandle, the status still shows Lock.
5: FCC Statement 1. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference and (2) This device must accept any interference received, includ including ing interference that may cause undesired operation. 2. Any changes hanges or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
Electronic Rack eHandle User Manual Declaration of Conformity 1.The product conforms to RIFD specifications and technical standards. 2.The product conforms to DOC declaration. 3.The product meets the basic requirements and other relevant provisions of the 2014/53 / EU directive. 4.The product is allowed to be used in all EU member states.