Installation Manual

3.0
Fuse Link Specifications:
These BET‟s have a built in 26 gauge fuse link. If an
overcurrent condition were to occur, the chassis will act as a
fuse chamber, greatly reducing any threat to safety. Once
fuse links have been fused, they cannot be rehabilitated or
repaired.
4.0
Installation Data:
The Terminal should be installed to the network‟s standard
installation procedure. However, the following factors should
be considered.
4.1
Use care when unpacking the Terminal from its shipping
carton to avoid damage to the Terminal, modules, or
connectors.
4.2
Install the Terminal as close to the incoming entrance cable as
possible.
4.3
The Terminal can be mounted on any level, uniform vertical
surface. Install the Terminal where it will be accessible to
technicians at all times without the terminal obstructing
individuals or equipment.
Note: Although the Terminal is designed to withstand extreme
conditions, it is always best to avoid any unnecessary
problems by observing the following important notes: When
installing the Terminal, it is highly recommended that unit be
placed in a non-combustible area. (The environment
surrounding these devices should not contain flammable
materials such as curtains, carpeting, etc.)
If the installation for the telco equipment is not in an assigned
electrical room, it is advised to avoid areas with dust, moisture,
extreme environmental conditions, heavy traffic areas requiring
rolling machinery, pipes used to transport water, fuel, and
gases.
4.4
Avoid exposing the Terminal to chemicals or cleaning liquids,
which could damage various plastic components within the
device.
5.0
Installation Procedures:
Mount the Terminal to a surface using the supplied mounting
screws or approved network standards screws.
5.1
Outside Plant Termination (Incoming/Blue):
Terminals with an incoming 110 blocks should be terminated
as follows: Refer to figure 1 for 110 block Terminal
arrangements. The entrance cable should be routed through
the wire retaining rings located on the side of the Terminal.
The pairs should then be jumpered to the incoming/blue field
of the 110 blocks, using a 110-style tool such as the
Harris/Raycon D-814.
Caution: Do not use a screwdriver for attaching line pairs to
110 block terminals, as a screwdriver may spread the clip
beams and result in a faulty connection.
5.2
Distribution Termination (Outgoing/Green):
The procedure for terminating the distribution cable is the
same as indicated in 5.1, except the outgoing/green field is to
be terminated.
6.0
Grounding:
The Terminal has two locations to attach a ground wire
(located on the side or top face of the Terminal). A #6 AWG
wire should be connected from one of the Terminal ground
lugs to a local ground as per network standard methods. It
should be noted that incorrect bonding and grounding would
result in terminal and protection module failure.
7.0
Terminal Module Installation:
If the Terminal is purchased with the terminal modules
installed they will be inserted in the terminal panel in the detent
position. A distinctive “notch” in the three long pins of the
module indicates the detent position. This will connect the
incoming tip / ring as well as grounding circuits of the module.
Note: When the module is in detent position it will protect
only the incoming (outside plant) cable. The module must
be fully inserted to provide protection to both the central
office and customer premise side of the installation.
7.1
After all incoming and outgoing connections are completed;
fully insert the terminal module until the base of the module
meets the terminal block. This will connect the customer
premise (outgoing/green) side of the unit to the outside plant
(incoming/blue) side of the unit.
7.2
Fully test all connections.
8.0
Terminal Diagrams:
1880ENA1/NSC-12
1880ENA1/NSC-25
1880ENA1/NSC-50
In
Out
Blue
Green

Summary of content (2 pages)