General
The NOTIFIER Spartan-25 (NSP-25C) is a 25 point address-
able Fire Alarm Control Panel (FACP) with built-in Digital
Alarm Communicator Transmitter (DACT). This control panel
supports up to 25 addressable devices in any combination of
detectors and modules and then reports these devices into
one of 5 available zones.
With simple programming, operation on standard wire, and
features such as drift compensation and maintenance alert,
the Spartan-25 is a preferred alternative to conventional con-
trol panels in both new and retrofit applications.
The JumpStart® (or auto-learn) feature and easy-to-set code-
wheel addressing of Honeywell Fire Systems (HFS) or equiva-
lent Notifier detectors and modules enable the system to be
quickly configured for fire protection without a programming
utility. The default programming can be easily modified on a
PC using the panel’s embedded web server.
The integral DACT transmits system status (alarms, troubles,
supervisories, etc.) for up to 5 zones to a remote monitoring
location via the public switched telephone network. Reporting
formats are contact ID, SIA 8 or SIA 20.
Features
• SBUS supports two N-ANN-80C Remote Annunciators
• JumpStart® auto-learn feature reduces installation time
and makes programming easy.
• Built-in digital communicator.
• IP communicator compatible
• Two programmable Style Y (Class B) notification appliance
circuits (NACs).
• Selectable strobe synchronization for System Sensor® or
Wheelock® devices.
• Two programmable Form-C relays and one Form-C trouble
relay.
• Drift compensation.
• Alarm verification per zone of detectors.
• Walk-test.
• Detectors and modules are code-wheel addressed for
faster installation time.
• Maintenance alert region.
• Uses standard wire (unshielded or twisted pair).
• Central Station reporting up to five zones.
• Custom programming performed through the control
panel’s built-in browser; no programming software is
required.
DCL Communication
• Single addressable DCL loop which meets ULC require-
ments (DCLA, DCLB, DCLC).
• 25 addressable device capacity (any combination of
addressable detectors and modules).
• Compatible with Honeywell Fire Systems (HFS) or equiva-
lent Notifier detectors and modules.
Notification Appliance Circuits (NACS)
• Two independently programmable output circuits. Circuits
can be configured for the following outputs:
– Style Y (Class B).
– Door Holder Service (cannot be used for notification
appliances).
– Aux Power Source (cannot be used for notification appli-
ances).
• Silence Inhibit and Auto-silence timer options.
• Continuous or Temporal code.
• Selectable strobe synchronization per NAC.
• Up to 2.0 A total output power, 1.0 A for auxiliary power and
door holder. Each circuit can source up to the total system
current 2.0 A.
Programming and Software
• Auto-learn JumpStart® feature for easy programming
reduces installation time.
• Custom programming can be performed through control
panel’s built-in browser. (Requires PC with MS Internet
Explorer or Mozilla Firefox and standard Cat5e Ethernet
cable)
• 5 programmable zones (combination of alarm / supervisory)