PTP 600 Series User Guide MOTOROLA POINT-TO-POINT WIRELESS SOLUTIONS
Accuracy While reasonable efforts have been made to assure the accuracy of this document, Motorola, Inc. assumes no liability resulting from any inaccuracies or omissions in this document, or from use of the information obtained herein. Motorola, Inc.
Safety Important safety information ............................................................ . . . . This section describes important safety guidelines that must be observed by personnel installing or operating PTP 600 equipment. WARNING To prevent loss of life or physical injury, observe the safety guidelines in this section. Power lines Exercise extreme care when installing antennas near power lines. Working at heights Exercise extreme care when working at heights.
Safety Grounding PTP-SYNC In order to meet the safety requirements for deployment in Australia and New Zealand (AS/NZS 60950-1), the PTP Sync unit, if deployed, must be grounded to a Protective Earth in accordance with Local Electrical Regulations. PIDU Plus It is recommended that the supplied Power Indoor Plus (PIDU Plus PTP 300/500/600 Series) is used to power the ODU. The use of other power sources may invalidate safety approval and affect your warranty.
Safety • The power source cannot provide more than the Energy Hazard Limit as defined by IEC/EN/UL6090, Clause 2.5, Limited Power (The Energy Hazard Limit is 240VA). Primary disconnect device The main power supply is the primary disconnect device. External cables Safety may be compromised if outdoor rated cables are not used for connections that will be exposed to the weather.
Table of Contents Contents ............................................................ . . . . Important safety information............................................................................................i Power lines.............................................................................................................................. i Working at heights..................................................................................................................
Contents Security advice............................................................................................................................. 9 Warnings, cautions, and notes ................................................................................................... 10 Warnings .............................................................................................................................. 10 Cautions ..............................................................................
Contents Adaptive modulation ......................................................................................................... 1-22 MIMO ................................................................................................................................ 1-23 Intelligent dynamic frequency selection ........................................................................... 1-24 Radar avoidance................................................................................................
Contents Configuring HTTPS/TLS....................................................................................................1-54 Exiting from the FIPS 140-2 mode....................................................................................1-54 Prerequisites .....................................................................................................................1-54 Chapter 2 Planning considerations ...............................................................................
Contents Mast or tower installation with E1/T1 .............................................................................. 2-30 Wall installation with E1/T1 .............................................................................................. 2-31 Mast or tower installation with UltraSync GPS unit......................................................... 2-32 Wall installation with UltraSync GPS unit ........................................................................
Contents Compliance with regulations ..............................................................................................4-2 System specifications ..........................................................................................................4-5 Safety compliance ...............................................................................................................4-7 European EMC immunity compliance...............................................................................
Contents PTP 49600 emissions and radio certifications .................................................................. 4-48 PTP 49600 available spectrum settings ............................................................................ 4-49 PTP 49600 system threshold, output power and link loss ................................................ 4-51 PTP 54600 reference information ...........................................................................................
Contents Checking the configuration.......................................................................................................5-2 IP addresses of the Master and Slave units ........................................................................5-2 Configuring the IP interface on the PC ...............................................................................5-2 Powering up and connecting the PIDU Plus .......................................................................
Contents Recommended kit ............................................................................................................. 5-36 PTP-SYNC unit rack or wall mounting .............................................................................. 5-37 Connecting up PTP-SYNC ................................................................................................. 5-39 Power-up, testing and fault finding...................................................................................
Contents System configuration ........................................................................................................6-19 Spectrum management .....................................................................................................6-22 QoS configuration .............................................................................................................6-39 Configuring the IP and Ethernet interfaces......................................................................
Contents Supported Management Information Bases (MIBs)........................................................ 6-113 Diagnostics alarms.......................................................................................................... 6-114 Configuring SNMP notifications ..................................................................................... 6-115 SMTP (Simple Mail Transport Protocol) .........................................................................
Contents Reboot ...............................................................................................................................7-27 Chapter 8 Connectorized PTP 600 series ...................................................................... 8-1 Product description...................................................................................................................8-2 Hardware ......................................................................................................
Contents ODU mounted indoors ...................................................................................................... 8-21 Chapter 9 FAQs ............................................................................................................ 9-1 General FAQs ............................................................................................................................ 9-2 Link encryption FAQs ...................................................................................
List of Figures List of Figures ............................................................ . . . . Figure 1-1 Typical PTP 600 Series bridge deployment .................................................................1-3 Figure 1-2 PTP 600 Series outdoor unit (ODU) with PTP-LPU .....................................................1-6 Figure 1-3 Mod record label..........................................................................................................
List of Figures Figure 2-10 PTP-LPU additional kit............................................................................................. 2-24 Figure 2-11 Simplified circuit diagram ....................................................................................... 2-25 Figure 2-12 Typical mast or tower installation ........................................................................... 2-28 Figure 2-13 Typical wall installation ................................................................
List of Figures Figure 4-23 PTP 58600 available spectrum in 15 MHz channel bandwidth ...............................4-81 Figure 4-24 PTP 58600 available spectrum in the 10 MHz channel bandwidth .........................4-81 Figure 4-25 PTP 58600 available spectrum in 5 MHz channel bandwidth .................................4-81 Figure 4-26 PTP 59600 available spectrum in 30 MHz channel bandwidth ...............................4-94 Figure 4-27 PTP 59600 available spectrum in 15 MHz channel bandwidth .......
List of Figures Figure 5-15 PTP-SYNC mounted on wall..................................................................................... 5-38 Figure 5-16 ODU PIDU Plus connection ..................................................................................... 5-43 Figure 5-17 Correct and incorrect PIDU cable dressing............................................................. 5-48 Figure 5-18 PIDU Plus drip loop configuration...........................................................................
List of Figures Figure 6-25 Telecoms page .........................................................................................................6-49 Figure 6-26 Software License Key page......................................................................................6-53 Figure 6-27 Current installation summary page .........................................................................6-54 Figure 6-28 Step 1: Interface Configuration page ..........................................................
List of Figures Figure 6-58 Step 4: Random Number Entropy Input page ....................................................... 6-103 Figure 6-59 Step 5: Enter The Wireless Link Encryption Key page.......................................... 6-104 Figure 6-60 Step 6: HTTP and Telnet Settings page................................................................. 6-105 Figure 6-61 Step 7: Commit Security Configuration page........................................................
List of Figures Figure 8-2 Connectorized PTP 600 Series Status page.................................................................8-3 Figure 8-3 Connectorized PTP 600 Series System Configuration page ........................................8-4 Figure 8-4 Connectorized PTP 600 Series Wireless Configuration page ......................................8-5 Figure 8-5 Connectorized PTP 600 Series Confirm Installation page...........................................
List of Figures phn-0896_009v003 xxiv UNDER DEVELOPMENT Feb 2010
List of Tables List of Tables ............................................................ . . . . Table 1-1 PTP 600 Series frequency variants................................................................................1-4 Table 1-2 Supported Superior Essex cable - available lengths and part numbers......................1-15 Table 1-3 Recommended outdoor connectors for ODU and LPU ................................................1-16 Table 1-4 Recommended outdoor connectors for Trimble GPS receiver .....
List of Tables Table 4-14 PTP 25600 radio certifications .................................................................................. 4-20 Table 4-15 PTP 25600 channel plan - FCC BRS-EBS Post-Transition Band................................ 4-22 Table 4-16 PTP 25600 - IP mode - threshold, power and link loss .............................................. 4-24 Table 4-17 PTP 25600 - TDM mode - threshold, power and link loss .........................................
List of Tables Table 4-48 PTP 58600 licenses and region codes .......................................................................4-70 Table 4-49 PTP 58600 RF specifications .....................................................................................4-77 Table 4-50 PTP 58600 EMC emissions compliance.....................................................................4-78 Table 4-51 PTP 58600 radio certifications ..................................................................................
List of Tables Table 6-9 User accounts attributes ............................................................................................. 6-92 Table 6-10 Identity-based user accounts attributes .................................................................... 6-94 Table 6-11 HTTP and Telnet attributes ..................................................................................... 6-106 Table 6-12 SNMP attributes in the Remote Management page................................................
About This User Guide About This User Guide ............................................................ . . . . This guide describes the planning, installation and operation of the Motorola PTP 600 Series of Point-to-Point Wireless Ethernet Bridges. It is intended for use by the link planner, system installer and the end user IT professional.
Revision history Revision history Version information The following shows the issue status of this document since it was first released.
General information General information Purpose Motorola Point-To-Point documents are intended to instruct and assist personnel in the operation, installation and maintenance of the Motorola Point-To-Point equipment and ancillary devices. It is recommended that all personnel engaged in such activities be properly trained by Motorola.
General information Text conventions The following conventions are used in the Motorola Point-To-Point documents to represent keyboard input text, screen output text and special key sequences. Input Characters typed in at the keyboard are shown like this. Output Messages, prompts, file listings, directories, utilities, and environmental variables that appear on the screen are shown like this.
Contacting Motorola Contacting Motorola Feedback We appreciate feedback from the users of our documents. This includes feedback on the structure, content, accuracy, or completeness of our documents. Send feedback to support.ptp@motorola.com. Motorola Point-to-Point Motorola, Inc., 1303 E. Algonquin Road, Postal Address: Schaumburg, Illinois 60196 U.S.A. Web Site: http://www.motorola.com/ptp Sales Enquiries: sales.ptp@motorola.com Web Support: http://www.motorola.
Contacting Motorola WiBB Technical Support telephone numbers Region and country Support telephone number North America: USA and Canada 866-961-9288 Europe, Middle East and Africa: Denmark 043682114 France 0157323434 Germany 06950070204 Italy 0291483230 Lithuania 800 030 828 Netherlands 0202061404 Norway 24159815 Portugal 0217616160 Spain 912754787 Russia 810 800 228 41044 Saudi Arabia 800 844 5345 South Africa 0800981900 United Kingdom 0203 0277499 All other countries +44 203
Contacting Motorola Region and country Support telephone number Chile 800-225-288 Columbia 01-800-912-0557 Mexico 001-800-942-7721 Peru 0800-70-086 All other countries +420 533 336 946 Asia, Pacific and China: Australia 800 457 439 Singapore 64 155 110 All other countries +420 533 336 946 Reporting problems If any problems are encountered when installing or operating this equipment, follow this procedure to investigate and report: 1.
Contacting Motorola Repair and service For unit repair or service, contact the PTP Global Technical Support Center for Return Material Authorization (RMA) and shipping instructions. The Global Technical Support Center is contacted at: http://www.motorola.com/ptp/support Further details of the RMA process are available at: http://www.motorola.com/ptp/support Warranty Motorola’s standard hardware warranty is for one (1) year from date of shipment from Motorola or a Motorola Point-to-Point Distributor.
Security advice Security advice Motorola systems and equipment provide security parameters that can be configured by the operator based on their particular operating environment. Motorola recommends setting and using these parameters following industry recognized security practices. Security aspects to be considered are protecting the confidentiality, integrity, and availability of information and assets.
Warnings, cautions, and notes Warnings, cautions, and notes The following describes how warnings and cautions are used in this document and in all documents of this Motorola document set. Warnings Warnings precede instructions that contain potentially hazardous situations. Warnings are used to alert the reader to possible hazards that could cause loss of life or physical injury. A warning has the following format: WARNING Warning text and consequence for not following the instructions in the warning.
Caring for the environment Caring for the environment The following information describes national or regional requirements for the disposal of Motorola supplied equipment and for the approved disposal of surplus packaging. In EU countries The following information is provided to enable regulatory compliance with the European Union (EU) directives identified and any amendments made to these directives when using Motorola equipment in EU countries.
Chapter 1 Chapter 1 Product description ............................................................ . . . . This chapter provides a high level description of the PTP 600 product. It describes in general terms the function of the product, the main product variants and typical deployment. It also describes the main hardware components.
Product function Chapter 1 Product description Product function The PTP 600 Series Bridge has been developed to provide Point-to-Point data connectivity via a wireless Ethernet bridge operating at broadband data rates. The PTP 600 Series Bridge offers true non-line-of-sight (NLOS) operation by using a combination of Orthogonal Frequency Division Multiplexing (OFDM) modulation and Multiple-Input Multiple-Output (MIMO) techniques.
User Guide: PTP 600 Series Typical deployment Typical deployment The PTP 600 Series Bridge consists of an identical pair of units deployed one at each end of the link. The radio link operates on a single frequency channel in each direction using Time Division Duplex (TDD). One unit is deployed as a master and the other as a slave. The master unit takes responsibility for controlling the link in both directions. The PTP 600 Series Bridge is aimed at a wide range of applications.
Product variants Chapter 1 Product description Product variants Frequency variants The PTP 600 Series has been developed to operate within license exempt frequency bands as well as the licensed 2.5 GHz band in the USA. The frequency variants are listed in Table 1-1. Table 1-1 PTP 600 Series frequency variants Variant Region Frequency Variable Coverage Bandwidth Raster 2496-2568 MHz 5, 10, 15, 30 MHz 5.5 MHz 2572-2614 MHz 5, 10, 15, 30 MHz 6 MHz 2618-2690 MHz 5, 10, 15, 30 MHz 5.
User Guide: PTP 600 Series Variant Region Product variants Frequency Variable Coverage Bandwidth Channel Channel Raster 58600 FCC ISM Band 5725-5850 MHz 30 MHz 10 MHz PTP Russia 5825-5925 MHz 5, 10, 15 MHz 6 MHz 30 MHz 10 MHz 5, 10, 15 MHz 6 MHz 30 MHz 10 MHz 59600 India 5875-5925 MHz NOTE For PTP 25600, channel widths of 30 MHz are available where allowed by local regulations and subject to some restrictions on channel choice.
Outdoor unit (ODU) Chapter 1 Product description Outdoor unit (ODU) The ODU is a self-contained unit. It houses both radio and networking electronics. The ODU for the PTP 600 Series should only be deployed using the supplied PIDU PTP 300/500/600 Series. Figure 1-2 shows an installation example of a PTP 600 Series ODU with a Motorola lightning protection unit (PTP-LPU).
User Guide: PTP 600 Series Outdoor unit (ODU) Mounting brackets The ODU is supplied with a bracket for mounting it to a pole of 50mm (2”) to 75mm (3”) in diameter. For more details on mounting, see Chapter 3 The bracket allows for adjustment in both azimuth and elevation. The bracket may be split to allow the pole mount section of the bracket to be mounted to the pole first. This allows the installer to take the weight of the unit and secure it, one handed, with a single mounting bolt.
Outdoor unit (ODU) Chapter 1 Product description Alternatively, the network connection to a PTP 600 Series can be made using a 1000BaseSX Fiber Optic cable connected directly to the ODU. In this case power is still provided over the 1000BaseT Ethernet connection. In the case of Fiber Optic cable failure the PTP 600 Series will automatically fall back to the copper Ethernet connection (provided the cable length <=100m [330 ft]).
User Guide: PTP 600 Series PIDU Plus PTP 300/500/600 Series PIDU Plus PTP 300/500/600 Series The PIDU Plus PTP 300/500/600 Series (Figure 1-4) is used to generate the ODU supply voltage from the mains supply (or from an external DC source) and inject this supply voltage into the 1000BaseT Ethernet connection to the ODU. The PIDU is connected to the ODU and network equipment using CAT5e cable with standard RJ45 connectors.
PIDU Plus PTP 300/500/600 Series Chapter 1 Product description ODU, LAN and recovery At the bottom of the PIDU is an entry point for the PIDU Plus to ODU cable, the 1000BaseT Ethernet network port and the Recovery switch. Figure 1-5 PIDU Plus recovery switch location The Recovery switch is used to recover the unit from configuration errors or software image corruption. To put an ODU into recovery mode, the Recovery switch should be pressed, then the power applied.
User Guide: PTP 600 Series PIDU Plus PTP 300/500/600 Series Mains connection The input supply range for the PIDU Plus is 90V-264V AC, 47-63Hz. Mains connection to the PIDU Plus is made using a standard “figure of eight” mains lead as shown in Figure 6.
PIDU Plus PTP 300/500/600 Series Chapter 1 Product description Figure 1-7 Relationship between DC voltage and cable length CAUTION The maximum distance from the ODU to the connected network equipment is 100m (330 ft) when using 1000BaseT. Powering distances over 100m (330 ft) are only applicable when using a 1000BaseSX (Fiber Optic) connection.
User Guide: PTP 600 Series PIDU Plus PTP 300/500/600 Series Figure 1-8 External DC supply only Figure 1-9 External DC supply and AC supply phn-0896_009v003 Feb 2010 UNDER DEVELOPMENT 1-13
PIDU Plus PTP 300/500/600 Series Chapter 1 Product description Figure 1-10 External DC supply and redundant AC supply Remote LEDs and recovery switch The PIDU Plus provides a facility to connect remote LEDs and Recovery switch allowing the PIDU Plus to be mounted inside an enclosure. At the left hand end of the PIDU Plus under the ODU connection cover can be found a PCB header and three jumpers.
User Guide: PTP 600 Series Cables and connectors Cables and connectors Outdoor connections The term ‘drop cable’ refers to the cable that is used for all connections that terminate outside the building, that is for connections between the ODU, LPUs (if installed), GPS receiver (if installed) and the ODU port of the PIDU Plus. Supported Superior Essex cable The only type of outdoor drop cable supported by Motorola is Superior Essex CAT5e, which is UV resistant and has a screened shield.
Cables and connectors Chapter 1 Product description Connectors and glands for outdoor use The recommended connectors and glands to be used for connecting the supported Superior Essex cable to the ODU or LPU are specified in Table 1-5.
User Guide: PTP 600 Series Cables and connectors Indoor connections The cable used for indoor connections, for example from the PIDU Plus to the network, can be any standard screened or unscreened CAT5e cable. The recommended connectors and glands to be used for indoor cables are specified in Table 1-5.
PTP and lightning protection Chapter 1 Product description PTP and lightning protection The PIDU Plus meets the low level static discharge specifications identified in European EMC immunity compliance on page 4-9 but does not provide lightning or surge suppression. The amount of lightning protection is dependent on regulatory requirements and the end user requirements.
User Guide: PTP 600 Series Wireless operation Wireless operation Time division duplex PTP 600 series links use a duplexing scheme known as Time Division Duplex (TDD). TDD operates by only allowing one end of the link to transmit at any one time. This allows both link directions to operate on the same radio frequency, although this is not mandatory.
Wireless operation Chapter 1 Product description Figure 1-12 The TDD cycle of events Time Frame 1 Frame 2 Frame Duration Master Burst Duration Propagation Delay Master Tx Burst Slave Rx Master Rx Master Tx Burst Slave Tx Burst Slave Burst Duration Propagation Delay Processing Delay Processing Delay The Master PTP 600 automatically controls the structure of the TDD Frame, optimizing Burst Duration and Frame Duration for either maximum capacity or minimum latency depending on the setting of L
User Guide: PTP 600 Series Wireless operation TDM traffic TDM Traffic mode is optimized to provide the lowest possible latency. TDM Traffic mode additionally implements a more conservative approach to adaptive modulation, leading to lower error rates in fading channels at the expense of slightly lower link capacity. TDM Traffic mode is an appropriate choice for delay intolerant data without reliable transmission (for example voice over IP data).
Wireless operation Chapter 1 Product description o When link mode optimization is set to TDM Traffic see Link mode optimization on page 1-20). o When TDD synchronization is enabled (see Time division duplex synchronization on page 1-25). o In regions where radar avoidance is operational (see Radar avoidance on page 1-24). OFDM and channel bandwidth The PTP 600 series transmits using Orthogonal Frequency Division Multiplexing (OFDM). This wideband signal consists of many equally spaced sub-carriers.
User Guide: PTP 600 Series Wireless operation The PTP 600 series provides an adaptive modulation scheme where the receiver constantly monitors the quality of the received signal and notifies the far end of the link of the optimum modulation mode with which to transmit. In this way, optimum capacity is achieved at all times. This is one of a number of features which allows the PTP 600 to operate in challenging none line of sight radio channels.
Wireless operation Chapter 1 Product description Intelligent dynamic frequency selection The PTP 600 series uses an interference mitigation technique known as Intelligent Dynamic Frequency Selection (i-DFS). Both the PTP 600 Master and PTP 600 Slave continually monitor for interference on all channels and then select the best frequency of operation. This is a dynamic process where the PTP 600 can continually move channels in response to changes in interference.
User Guide: PTP 600 Series Wireless operation NOTE On system installation or start-up, this extends the initial scan time of the Master unit by 60 seconds. To address the requirement to provide aggregate uniform loading of the spectrum across all devices, the channel selection algorithm will choose a channel at random from a list of useable channels. The channel selection algorithm is initiated at link initialization and when radar interference is detected.
Wireless operation Chapter 1 Product description This type of interference may be eliminated if the TDD frames of the two links are synchronized such that ODUs which share a mast are configured to always transmit together and always receive together. An ODU will never be transmitting when an ODU sharing the same mast is receiving.
User Guide: PTP 600 Series Wireless operation Performance considerations when enabling TDD synchronization In certain configurations, the TDD frame can adapt to allocate more of the frame to a particular link direction. This is called adaptive TDD. It works by the PTP 600 automatically and independently adjusting the Burst Duration in each link direction as the level of offered traffic in each direction changes. This was discussed in more detail in Link symmetry on page 1-21.
Wireless operation Chapter 1 Product description Figure 1-14 PTP-SYNC application The PTP-SYNC is a compact indoor unit mounted on a wall or a shelf or (using an optional rack mounting adaptor) in a standard 19 inch rack. The PTP-SYNC is powered using standard PTP 600 power-over-Ethernet from the PIDU. One PTP-SYNC unit is required for each synchronized link. How PTP-SYNC works TDD synchronization using the PTP-SYNC operates as follows: 1.
User Guide: PTP 600 Series Wireless operation 3. The PTP-SYNC unit measures the difference between the TDD frame timing and the 1 Hz time reference, 4. The PTP-SYNC signals this time difference to the ODU, 5. The ODU uses the measured time difference as an input to a control loop that synchronizes TDD timing with the timing reference and thus indirectly with the network-wide master. Timing reference PTP-SYNC requires a 1 Hz timing reference signal.
Wireless operation Chapter 1 Product description • The recommended GPS receiver continues to provide accurate timing even after the number of received satellite has dropped down to one, leading to significantly better availability of the reference signal, • The PTP-SYNC offers the possibility of creating synchronised single-hub networks where no GPS receiver is required.
User Guide: PTP 600 Series Wireless operation PTP-SYNC front panel The PTP-SYNC front panel is illustrated in Figure 1-15. The annotated interfaces are described in Table 1-6. Figure 1-15 PTP-SYNC front panel Table 1-6 PTP-SYNC front panel interfaces Number Description Function 1 GPS/SYNC IN Input from GPS receiver module. 2 SYNC OUT Output to cascaded GPS-SYNC units. 3 USB Input for software upgrades. Contact Motorola for instructions. 4 1PPS IN Coaxial alternative to GPS/SYNC IN.
Wireless operation Chapter 1 Product description Table 1-7 PTP-SYNC indicator LEDs Indicator Function GPS Off Description No GPS satellite data being received at either the GPS/SYNC IN or 1PPS IN port. SYNC On steady or blink GPS satellite data being received. Off No data being received at the SYNC OUT port. STATUS On steady or blink Data being received at the SYNC OUT port. Off No power. On steady Power but no satellite lock.
User Guide: PTP 600 Series Ethernet bridging Ethernet bridging Ethernet frames The PTP 600 series provides wireless Ethernet bridging between two fixed locations. To be more precise, it forwards Ethernet frames as a two-port transparent heterogeneous encapsulation bridge, meaning that each bridge forwards frames between two dissimilar interfaces (Ethernet and wireless), encapsulating Ethernet MAC frames within a PTP MAC frames for transmission at the wireless interface.
Ethernet bridging Chapter 1 Product description Management function The management function of the PTP 600 Series is logically equivalent to a separate protocol stack with virtual point of attachment at the Ethernet interface. This is illustrated in Figure 1-16.
User Guide: PTP 600 Series Ethernet bridging Networking information The PTP 600 Series operates as a transparent Ethernet bridge. Although each unit requires an IP address, this IP address is for management purposes only, and it plays no part in the forwarding of bridged Ethernet frames. IP addresses are assigned during initial configuration.
Telecoms circuits Chapter 1 Product description Telecoms circuits The PTP 600 link provides native support for one or two E1 links, or one or two T1 links. The link relays unstructured E1 or T1 data and provides accurate timing transfer.
User Guide: PTP 600 Series Telecoms circuits Further reading Installation details are provided in Installing E1 and T1 on page 5-50. E1/T1 circuits are configured using the web pages described in Section Configuring the telecoms circuits on page 6-49 and Telecoms interface on page 6-57.
System management Chapter 1 Product description System management Management agent PTP 600 equipment is managed through an embedded management agent. Management workstations, network management systems or PCs can be connected to this agent using standard management protocols multiplexed with user traffic at the Ethernet data port. Web interface The PTP 600 management agent contains a web server.
User Guide: PTP 600 Series System management Transport layer security The PTP 600 management agent allows HTTP traffic at the web interface to be encrypted using Transport Layer Security (TLS). PTP 600 uses AES to encrypt HTTP traffic. Operation of HTTPS/TLS is enabled by purchase of an optional AES upgrade as described in Upgrading the PTP 600 on page 6-77. TLS operation requires installation of a key of keys, a private key, a related public key certificate, and an entropy value.
System management • Chapter 1 Product description Read only. Identity-based user accounts are enabled in the User Accounts page of the web-based interface. Best-practice passwords PTP 600 allows passwords to be checked for compliance with password best practice. When checking is enabled, passwords must comply with the following: • Passwords are case sensitive • Passwords must contain at least: • o One uppercase letter. o One lowercase letter. o One numeral. o One special character.
User Guide: PTP 600 Series System management Supported notifications The supported notifications are as follows: • Cold start • Wireless Link Up/Down • DFS Channel Change • DFS Impulse Interference • Authentication Failure • Ethernet Link Up/Down Supported alarms PTP 600 supports the following diagnostic alarms: • Region Code • Install Status • Install Arm State • Unit Out Of Calibration • Incompatible Region Codes • Incompatible Master And Slave • Ethernet Configuration Mismatch
System management • Chapter 1 Product description Link Mode Optimization Mismatch The web-based interface may be used to enable or disable generation of each supported SNMP notification or diagnostic alarm.
User Guide: PTP 600 Series • SHA-1, DES, • MD5, AES, • SHA-1, AES. System management Use of AES privacy requires the PTP 600 AES upgrade described in AES license on page 1-48. The ODU will allow the creation of users configured with AES privacy protocol, regardless of license key. However, a user configured to use AES privacy protocol will not be able to transmit and receive encrypted messages unless the license key enables the AES capability.
System management Chapter 1 Product description Name templateMD5_AES templateSHA_AES SecurityName templateMD5_AES templateSHA_AES AuthProtocol usmHMACMD5AuthProtocol usmHMACSHAAuthProtocol PrivProtocol usmAESPrivProtocol usmAESPrivProtocol StorageType nonVolatile nonVolatile PTP 600 creates the initial user and template users with localised authentication and privacy keys derived from the passphrase string “123456789”.
User Guide: PTP 600 Series System management ViewName internet restricted Subtree 1.3.6.1 1.3.6.
System management Chapter 1 Product description Table 1-10 Default data fill for access table Object Entry 1 Entry 2 GroupName initial initial ContextPrefix “” “” SecurityLevel authNoPriv noAuthNoPriv ContextMatch exact exact ReadViewName internet restricted WriteViewName internet “” NotifyViewName internet restricted StorageType nonVolatile nonVolatile Access to critical security parameters The SNMPv3 management interface does not provide access to critical security parameters
User Guide: PTP 600 Series System management Email alerts The management agent can be configured to generate alerts by electronic mail when any of the following events occur: • Wireless Link Up/Down • DFS Channel Change • DFS Impulse Interference • Ethernet Link Up/Down • Region Code • Install Status • Install Arm State • Unit Out Of Calibration • Incompatible Region Codes • Incompatible Master And Slave • Ethernet Configuration Mismatch • No Wireless Channel Available • SNTP Sync
System management Chapter 1 Product description AES license PTP 600 provides optional encryption using the Advanced Encryption Standard (AES). Encryption is not available in the standard PTP 600 system. AES upgrades are supplied as an access key purchased from your Motorola Point-toPoint distributor or solutions provider. The access key authorizes AES operation for one ODU. Two access keys are needed to operate AES on a link.
User Guide: PTP 600 Series System management Critical security parameters Critical security parameters (CSPs) are as follows: • Key of keys. • AES encryption keys for the wireless interface. • Private key for the HTTPS/TLS interface. • Entropy value for the HTTPS/TLS interface. • User account passwords for the web-based interface. CSPs can be erased (zeroised) using the Zeroise CSPs page of the web-based interface or by selecting the Zeroise CSPs option in Recovery mode.
System management Chapter 1 Product description Software upgrade The management agent supports application software upgrade using either the webbased interface or the SNMP interface. PTP 600 software images are digitally signed, and the ODU will accept only images that contain a valid Motorola PTP digital signature. The ODU always requires a reboot to complete a software upgrade. NOTE Obtain the application software and this user guide from the support website BEFORE warranty expires.
User Guide: PTP 600 Series System management Recovery mode options Options in recovery mode are as follows: • Load new main application software. • Reset all configuration data to factory default. This option resets IP and Ethernet configuration, and erases (zeroizes) critical security parameters. • Reset IP and Ethernet configuration to factory default. • Erase (zeroize) critical security parameters. • Reboot with existing software and configuration.
FIPS 140-2 Chapter 1 Product description FIPS 140-2 PTP 600 provides an optional secure cryptographic mode of operation validated to Level 2 of Federal Information Processing Standards Publication 140-2. PTP 600 operates in the FIPS mode when all of the following are true: • The ODU software image is validated for FIPS operation. • The ODU license key has AES encryption enabled. • The ODU license key has FIPS operation enabled.
User Guide: PTP 600 Series FIPS 140-2 Hardware security The ODU has compatible hardware security if the part number suffix is no earlier than the minimum listed in Table 1-11.
FIPS 140-2 Chapter 1 Product description Configuring HTTPS/TLS The HTTPS/TLS interface is configured using the Security Wizard. See Configuring FIPS 140-2 mode on page 6-108 for further details of using the Security Wizard. Exiting from the FIPS 140-2 mode To exit from the FIPS 140-2 mode, do any of the following: • Load a PTP 600 license key that has FIPS operation disabled and reboot. • Load PTP 600 software that is not FIPS-validated and reboot. • Zeroise CSPs and reboot.
Chapter 2 Chapter 2 Planning considerations ............................................................ . . . . This chapter provides information to help the user to plan a PTP 600 link. Each frequency variant has specific licensing restrictions that affect frequency range, channel bandwidth, maximum power and radar avoidance. Link planning must take account of obstructions, site selection, path loss and wind loading.
Spectrum planning Chapter 2 Planning considerations Spectrum planning The PTP 600 may use one of four alternative methods of spectrum planning. The choice of methods depends upon whether or not the region mandates radar detection. Regions without mandatory radar detection In regions that do not mandate DFS (Radar Detection), the frequencies may be configured symmetrically or asymmetrically (different transmit and receive frequencies).
User Guide: PTP 600 Series Licenses and region codes Licenses and region codes The PTP 600 Series uses a system of region codes to control the operation of the radio link. The user must ensure the product is configured to conform to local regulatory requirements by installing a License Key for the correct region code. CAUTION For the connectorized model, when using external antennas of higher gain than the appropriate integrated antenna, the regulations may require the maximum Tx power to be reduced.
Radar avoidance and bandwidth operation Chapter 2 Planning considerations Radar avoidance and bandwidth operation Channel barring Where regulatory restrictions apply to certain channels these channels are barred. RTTT avoidance may be necessary in all channel bandwidths. The number of channels barred is dependant on the channel raster selected. For example see the effect of the UK RTTT channel restrictions in the 30 MHz bandwidth (Figure 2-1), where blocks in red indicate channels that are barred.
User Guide: PTP 600 Series Variable channel bandwidth operation Variable channel bandwidth operation The selection of Channel Bandwidth depends upon the PTP frequency variant: • For PTP 25600, PTP 45600, PTP 54600, PTP 58600 and PTP 59600, Channel Bandwidth may be 30, 15, 10 or 5 MHz. • For PTP 48600 and PTP 49600, Channel Bandwidth may be 20, 10 or 5 MHz. The 30MHz channel widths are available where allowed by local regulations and subject to some restrictions on channel choice.
Site planning Chapter 2 Planning considerations Site planning Site selection criteria The following are guidelines for selecting the installation location of the ODU and PIDU Plus for a PTP 600 Series.
User Guide: PTP 600 Series Site planning Wind loading Antennas and electronic equipment mounted on towers or pole mounted on buildings will subject the mounting structure to significant lateral forces when there is appreciable wind. Antennas are normally specified by the amount of force (in pounds) for specific wind strengths. The magnitude of the force depends on both the wind strength and size of the antenna.
Site planning Chapter 2 Planning considerations Table 2-2 Lateral force – metric Largest Surface Area (sq m) Lateral Force (kg) at wind speed (m/s) 30 40 50 60 70 PTP 600 Series Integrated 0.130 12 22 34 49 66 PTP 600 Series Connectorized 0.093 9 16 24 35 48 NOTE When the connectorized version of 600 Series is used with external antennas, the figures from the antenna manufacturer for lateral force should be included to calculate to total loading on the mounting structure.
User Guide: PTP 600 Series Link planning Link planning Range and obstacles The PTP 600 Series are designed to operate in Non-Line-of-Sight (NLoS) and Line-ofSight (LoS) environments. The PTP 600 Series will operate at ranges from 100 m (330 ft) to 200 km (124 miles), within 3 modes: 0-40km (0-25 miles), 0-100km (0-62 miles) and 0-200km (0-124 miles). Operation of the system will depend on obstacles in the path between the units.
Path loss considerations Chapter 2 Planning considerations Path loss considerations Path loss is the amount of attenuation the radio signal undergoes between the two ends of the link. Calculating path loss The path loss is the sum of the attenuation of the path if there were no obstacles in the way (Free Space Path Loss), the attenuation caused by obstacles (Excess Path Loss) and a margin to allow for possible fading of the radio signal (Fade Margin).
User Guide: PTP 600 Series Path loss considerations For minimum error rates on TDM links, the maximum modulation mode should be limited to 64QAM 0.75. The values for (BPSK) are static receive sensitivity measurements. The other values are static receive sensitivity measurements with an AMOD threshold applied. The AMOD threshold applied is for a benign radio channel.
Planning synchronized networks Chapter 2 Planning considerations Planning synchronized networks Using PTP LINKPlanner for synchronized networks TDD synchronization should be planned using LINKPlanner. This will provide the necessary TDD Frame parameter values which are required to complete a synchronized installation. Please refer to the Link Planner User Guide.
User Guide: PTP 600 Series Planning synchronized networks Figure 2-2 TDD synchronization configuration – standalone with UltraSync phn-0896_009v003 Feb 2010 UNDER DEVELOPMENT 2-13
Planning synchronized networks Chapter 2 Planning considerations Figure 2-3 TDD synchronization configuration – standalone with PTP SYNC Master Slave Mode = Master, TDD Sync Device = PTP Sync PTP Sync Site Ref = GPS/1PPS Ext Cluster Master Slave = Cluster Master PTP 600 ODU PIDU LPU GPS Receiver Drop cable LPU LPU Outside Inside ODU OUT GPS/ PTP-SYNC SYNC IN SYNC OUT PIDU IN ODU AC supply 100-240 V ac PIDU LAN Customer network phn-0896_009v003 2-14 UNDER DEVELOPMENT Feb 2010
User Guide: PTP 600 Series Planning synchronized networks Figure 2-4 TDD synchronization configuration – cluster with PTP SYNC and GPS phn-0896_009v003 Feb 2010 UNDER DEVELOPMENT 2-15
Planning synchronized networks Chapter 2 Planning considerations Figure 2-5 TDD synchronization configuration – cluster with PTP SYNC and no GPS Master Slave Mode = Master, TDD Sync Device = PTP Sync PTP Sync Site Ref = Internal Cluster Master Slave = Cluster Master Master Slave Mode = Master, TDD Sync Device = PTP Sync PTP Sync Site Ref = Internal Cluster Master Slave = Cluster Slave Master Slave Mode = Master, TDD Sync Device = PTP Sync PTP Sync Site Ref = Internal Cluster Master Slave = Cluster Slave
User Guide: PTP 600 Series System threshold, output power and link loss System threshold, output power and link loss For details of the system threshold, output power and link loss for each frequency variant in all modulation modes for all available channel bandwidths, refer to: • PTP 25600 system threshold, output power and link loss on page 4-24 • PTP 45600 system threshold, output power and link loss on page 4-33 • PTP 48600 system threshold, output power and link loss on page 4-43 • PTP 49600 s
Lightning protection Chapter 2 Planning considerations Lightning protection This section provides instructions for protecting PTP 600 installations against lightning strike. The purpose of lightning protection is to protect structures, equipment and people against lightning by conducting the lightning current to ground via a separate preferential solid path.
User Guide: PTP 600 Series Lightning protection Lightning protection zones Lightning protection zones are determined by using the ‘rolling sphere method’ (Figure 2-6). Assess locations on masts, towers and buildings to determine if the location is in Zone A or Zone B: • Zone A: In this zone a direct lightning strike is possible. Do not mount the ODU and antenna in this zone.
Lightning protection Chapter 2 Planning considerations The rolling sphere method An imaginary sphere, typically 50 meters in radius, is rolled over the structure (Figure 2-6). Where the sphere rests against the ground and a strike termination device (such as a finial or ground bar) all the space under the sphere is considered to be in the zone of protection (Zone B). Similarly, where the sphere rests on two finials the space under the sphere is considered in the zone of protection.
User Guide: PTP 600 Series Lightning protection LPU configuration options The PTP LPU can be installed in one of the following configurations: • Option 1: Back-to-back with the ODU using the supplied brackets delivered part of the installation of a link. This is the configuration recommended by Motorola. • Option 2: Using the U-Bolt bracket supplied with the PTP LPU Kit. Typical examples of these two configurations are shown in Figure 2-7 and Figure 2-8.
Lightning protection Chapter 2 Planning considerations Figure 2-8 Example of PTP-LPU configuration option 2 (U-bolt) A second Lightning protection Unit should be mounted at the building entry point and must be grounded. LPU kit Standard kit with two LPUs The standard PTP-LPU kit (Figure 2-9) contains two LPUs, grounding cables and a 600mm ODU to LPU cable pre-fitted with glands. The Motorola part number for this kit is WB2907AA.
User Guide: PTP 600 Series Lightning protection Figure 2-9 PTP LPU full kit The cable between the two LPUs (top and bottom) should be of the recommended type (see Cables and connectors on page 1-15) and terminated as shown in Figure 5-1.
Lightning protection Chapter 2 Planning considerations Additional kit with one LPU Some installation options, for example PTP-SYNC with Trimble GPS receiver, may require an additional single LPU kit (Figure 2-10). Figure 2-10 PTP-LPU additional kit LPU installation wiring Figure 2-11 shows the correct installation wiring for a PTP 600 with lightning protection.
User Guide: PTP 600 Series Lightning protection Figure 2-11 Simplified circuit diagram phn-0896_009v003 Feb 2010 UNDER DEVELOPMENT 2-25
Site installation diagrams Chapter 2 Planning considerations Site installation diagrams This section contains diagrams to show how the components of PTP 600 sites are installed and connected with LPU.
User Guide: PTP 600 Series Site installation diagrams NOTE If a coaxial (or other) cable is already cross-bonded to the mast or tower, the same cross bonding points on the mast or tower must be used for the CAT 5e cable.
Site installation diagrams Chapter 2 Planning considerations Typical mast or tower installation Figure 2-12 shows a typical PTP 600 Series mast or tower installation using PTP-LPU Surge protection for a configuration without a GPS sync unit or E1/T1 ports. This installation requires 4 Motorola PTP-LPU surge arrestors (2 kits).
User Guide: PTP 600 Series Site installation diagrams Typical wall installation Figure 2-13 shows a typical PTP 600 Series wall installation using PTP-LPU surge protection for a configuration without a GPS sync unit or E1/T1 ports. This installation requires 4 Motorola PTP-LPU surge arrestors (2 kits).
Site installation diagrams Chapter 2 Planning considerations Mast or tower installation with E1/T1 Figure 2-14 shows a typical PTP 600 Series mast or tower installation using PTP-LPU surge protection for a configuration that includes E1/T1 ports. This installation requires 8 Motorola PTP-LPU surge arrestors (4 kits).
User Guide: PTP 600 Series Site installation diagrams Wall installation with E1/T1 Figure 2-15 shows a PTP 600 Series wall installation using PTP-LPU surge protection for a configuration that includes E1/T1 ports. This installation requires 8 Motorola PTP-LPU surge arrestors (4 kits).
Site installation diagrams Chapter 2 Planning considerations Mast or tower installation with UltraSync GPS unit Figure 2-16 shows a PTP 600 Series mast or tower installation using PTP-LPU surge protection for a configuration that includes an UltraSync GPS sync unit. This installation requires 4 Motorola PTP-LPU surge arrestors (2 kits). This installation also requires: UltraSync GPS sync unit from MemoryLinkl – 1 per link (1 Motorola kit).
User Guide: PTP 600 Series Site installation diagrams Wall installation with UltraSync GPS unit Figure 2-17 shows a PTP 600 Series wall installation using PTP-LPU surge protection for a configuration that includes an UltraSync GPS sync unit. This installation requires 4 Motorola PTP-LPU surge arrestors (2 kits). This installation also requires one UltraSync GPS sync unit from MemoryLink per link (1 Motorola kit).
Site installation diagrams Chapter 2 Planning considerations Mast or tower installation with UltraSync GPS unit and E1/T1 Figure 2-18 shows a PTP 600 Series mast or tower installation using PTP-LPU surge protection for a configuration that includes an UltraSync GPS sync unit and E1/T1 ports. This installation requires 8 Motorola PTP-LPU surge arrestors (4 kits). This installation also requires: UltraSync GPS sync unit from MemoryLinkl – 1 per link (1 Motorola kit).
User Guide: PTP 600 Series Site installation diagrams Wall installation with UltraSync GPS unit and E1/T1 Figure 2-19 shows a PTP 600 Series wall installation using PTP-LPU surge protection for a configuration that includes an UltraSync GPS sync unit and E1/T1 ports. This installation requires 8 Motorola PTP-LPU surge arrestors (4 kits). This installation also requires: UltraSync GPS sync unit from MemoryLinkl – 1 per link (1 Motorola kit).
Protection of the GPS receiver for PTP-SYNC Chapter 2 Planning considerations Protection of the GPS receiver for PTP-SYNC If PTP-SYNC is the selected TDD synchronization method, with a GPS receiver as the timing reference source, then the GPS receiver must be protected as described in this section. CAUTION Ensure that the GPS receiver module is mounted in a position where all lightning protection requirements can be met.
User Guide: PTP 600 Series Protection of the GPS receiver for PTP-SYNC Figure 2-20 GPS receiver mounted on equipment building Mounting the GPS receiver module on a metal tower or mast If mounting the GPS receiver module on a metal tower or mast (Figure 2-21), select a position that meets the following requirements: • It must have an un-interrupted view of the sky. • It must not be mounted any higher than is necessary to receive an adequate signal from a GPS satellite.
Protection of the GPS receiver for PTP-SYNC Chapter 2 Planning considerations The grounding requirements of a tower or mast mounted GPS receiver module are: • The metal tower or mast must be correctly grounded. • The cable screen must be bonded to the tower at the top and bottom ends. • Additional grounding at intermediate points of the cable may be required if the cable is longer than 15m (50 feet).
Chapter 3 Chapter 3 Legal information ............................................................ . . . . This chapter provides legal notices including software license agreements. CAUTION Intentional or unintentional changes or modifications to the equipment must not be made unless under the express consent of the party responsible for compliance. Any such modifications could void the user’s authority to operate the equipment and will void the manufacturer’s warranty.
Motorola Inc. end user license agreement Chapter 3 Legal information Motorola Inc. end user license agreement In connection with Motorola’s delivery of certain proprietary software or products containing embedded or pre-loaded proprietary software, or both, Motorola is willing to license this certain proprietary software and the accompanying documentation to you only on the condition that you accept all the terms in this End User License Agreement (“Agreement”).
User Guide: PTP 600 Series Motorola Inc. end user license agreement Conditions of use Any use of the Software and Documentation outside of the conditions set forth in this Agreement is strictly prohibited and will be deemed a breach of this Agreement. 1. Only you, your employees or agents may use the Software and Documentation. You will take all necessary steps to insure that your employees and agents abide by the terms of this Agreement. 2.
Motorola Inc. end user license agreement Chapter 3 Legal information Title and restrictions If you transfer possession of any copy of the Software and Documentation to another party outside of the terms of this agreement, your license is automatically terminated. Title and copyrights to the Software and Documentation and any copies made by you remain with Motorola and its licensors.
User Guide: PTP 600 Series Motorola Inc. end user license agreement Right to use Motorola’s name Except as required in “Conditions of use”, you will not, during the term of this Agreement or thereafter, use any trademark of Motorola, or any word or symbol likely to be confused with any Motorola trademark, either alone or in any combination with another word or words.
Motorola Inc. end user license agreement Chapter 3 Legal information Disclaimer MOTOROLA DISCLAIMS ALL WARRANTIES OF ANY KIND, WHETHER EXPRESS, IMPLIED, STATUTORY, OR IN ANY COMMUNICATION WITH YOU. MOTOROLA SPECIFICALLY DISCLAIMS ANY WARRANTY INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILTY, NONINFRINGEMENT, OR FITNESS FOR A PARTICULAR PURPOSE. THE SOFTWARE AND DOCUMENTATION ARE PROVIDED “AS IS.
User Guide: PTP 600 Series Motorola Inc. end user license agreement U.S. government If you are acquiring the Product on behalf of any unit or agency of the U.S. Government, the following applies. Use, duplication, or disclosure of the Software and Documentation is subject to the restrictions set forth in subparagraphs (c) (1) and (2) of the Commercial Computer Software – Restricted Rights clause at FAR 52.227-19 (JUNE 1987), if applicable, unless being provided to the Department of Defense.
Motorola Inc. end user license agreement Chapter 3 Legal information Survival of provisions The parties agree that where the context of any provision indicates an intent that it survives the term of this Agreement, then it will survive. Entire agreement This agreement contains the parties’ entire agreement regarding your use of the Software and may be amended only in writing signed by both parties, except that Motorola may modify this Agreement as necessary to comply with applicable laws.
User Guide: PTP 600 Series Motorola Inc. end user license agreement Trademarks Java™ Technology and/or J2ME™ : Java and all other Java-based marks are trademarks or registered trademarks of Sun Microsystems, Inc. in the U.S. and other countries. UNIX® : UNIX is a registered trademark of The Open Group in the United States and other countries.
Motorola Inc. end user license agreement Chapter 3 Legal information BZIP2 license “bzip2" and associated library "libbzip2", are copyright (C) 1996-2000 Julian R Seward. All rights reserved. Redistribution and use in source and binary forms, with or without modification, are permitted provided that the following conditions are met: • Redistributions of source code must retain the above copyright notice, this list of condition sand the following disclaimer.
User Guide: PTP 600 Series Motorola Inc. end user license agreement zlib.h license Interface of the 'zlib' general purpose compression library version 1.2.3, July 18th, 2005. Copyright (C) 1995-2005 Jean-loup Gailly and Mark Adler. This software is provided 'as-is', without any express or implied warranty. In no event will the authors be held liable for any damages arising from the use of this software.
Hardware warranty Chapter 3 Legal information Hardware warranty Motorola’s standard hardware warranty is for one (1) year from date of shipment from Motorola or a Motorola Point-to-Point Distributor. Motorola warrants that hardware will conform to the relevant published specifications and will be free from material defects in material and workmanship under normal use and service.
User Guide: PTP 600 Series Limit of liability Limit of liability IN NO EVENT SHALL MOTOROLA BE LIABLE TO YOU OR ANY OTHER PARTY FOR ANY DIRECT, INDIRECT, GENERAL, SPECIAL, INCIDENTAL, CONSEQUENTIAL, EXEMPLARY OR OTHER DAMAGE ARISING OUT OF THE USE OR INABILITY TO USE THE PRODUCT (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR ANY OTHER PECUNIARY LOSS, OR FROM ANY BREACH OF WARRANTY, EVEN IF MOTOROLA HAS BEEN ADVISED OF THE POSSI
Limit of liability Chapter 3 Legal information phn-0896_009v003 3-14 UNDER DEVELOPMENT Feb 2010
Chapter 4 Chapter 4 Reference information ............................................................ . . . . This chapter describes the reference information and regulatory notices that are common to all PTP 600 products and those that are specific to each frequency variant.
PTP 600 general reference information Chapter 4 Reference information PTP 600 general reference information Compliance with regulations Changes or modifications not expressly approved by Motorola could void the user’s authority to operate the system. This system has achieved Type Approval in various countries around the world. This means that the system has been tested against various local technical regulations and found to comply.
User Guide: PTP 600 Series PTP 600 general reference information Radio and television interference If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Reorient or relocate the Outdoor Unit (ODU). • Increase the separation between the affected equipment and ODU.
PTP 600 general reference information Chapter 4 Reference information Registration of links UK Registration of Links – OfCom, The application form may be found at: http://www.ofcom.org.uk/radiocomms/isu Eire Registration of Links – Commission for Communication Regulation, The application form may be found at: http://www.comreg.
User Guide: PTP 600 Series PTP 600 general reference information System specifications Table 4-1 PTP 600 management specifications Management Specification Power status Status Indication Ethernet Link Status Data activity Web server and browser for setup Audio tone feedback during installation , plus Installation graphical installation tool suitable for laptop and PDA computing devices Web server for confirmation Radio Performance and Via web server and browser, SNMP Management Alarms Via configu
PTP 600 general reference information Chapter 4 Reference information NOTE Practical Ethernet rates will depend on network configuration, higher layer protocols and platforms used. Over the air throughput will be capped to the rate of the Ethernet interface at the receiving end of the link. Table 4-3 PTP 600 physical specifications Integrated Dimensions Specification Width 14.5” (370mm), Height 14.5” (370mm), Depth 3.75” (95mm) Weight 12.1 lbs (5.
User Guide: PTP 600 Series PTP 600 general reference information Table 4-5 PTP 600 telecoms interface specifications Telecoms Interfaces Jitter and Wander Surge Protection and Power Cross Specification 2 E1 balanced 120R or 2 T1 balanced 100R over a CAT5 screened twisted pair cable Compliant with G.823/ G.824. Compliant with GR1089, EN60950. Table 4-6 PTP 600 PTP-SYNC physical specifications PTP-SYNC Specification Width excluding ears 6.69in (174mm) Dimensions Width including ears 7.
PTP 600 general reference information International Chapter 4 Reference information CB certified & certificate to IEC 60950 phn-0896_009v003 4-8 UNDER DEVELOPMENT Feb 2010
User Guide: PTP 600 Series PTP 600 general reference information European EMC immunity compliance Complies with European EMC Specification EN301 489-1 with testing carried out to the detailed requirements of EN301 489-4. NOTE For EN 61000-4-2: 1995 Electro Static Discharge (ESD), Class 2, 8 kV air, 4 kV contact discharge, the PTP 600 has been tested to ensure immunity to 15kV air and 8kV contact.
PTP 600 general reference information Chapter 4 Reference information Electromagnetic energy Standards Relevant standards (USA and EC) applicable when working with RF equipment are: • ANSI IEEE C95.1-1991, IEEE Standard for Safety Levels with Respect to Human Exposure to Radio Frequency Electromagnetic Fields, 3 kHz to 300 GHz.
User Guide: PTP 600 Series PTP 600 general reference information Power density exposure limit Install the radios for the PTP 600 family of PTP wireless solutions so as to provide and maintain the minimum separation distances from all persons. The applicable power density exposure limit from the standards (see Electromagnetic energy on page 4-10 ) is: 10 W/m2 for RF energy in the 2.4-, 5.2-, 5.4-, 5.8- and 5.9 GHz frequency bands.
PTP 600 general reference information Chapter 4 Reference information Calculated distances and power compliance margins Table 4-8 shows calculated minimum separation distances d, recommended distances and resulting margins for each frequency band and antenna combination. These are conservative distances that include compliance margins. At these and greater separation distances, the power density from the RF field is below generally accepted limits for the general population.
User Guide: PTP 600 Series Band 5.9 GHz Antenna PTP 600 general reference information Max Average Transmit Power in Burst (Watt) Equation Variables Recommended Distance (m) P (Watt) G (factor) S (W/m2) d (m) Compliance Margin External 6ft Dish 0.32 0.26 6310 10 3.07 10 External sectored antenna (60°) 0.32 0.26 50.1 10 0.28 1 3.6 Integrated 0.32 0.16 200 10 0.63 2 4.0 External 2ft Flat Plate 0.32 0.16 631 10 1.0 5 5.0 External 6ft Dish 0.32 0.16 6310 10 3.
PTP 600 general reference information Chapter 4 Reference information phn-0896_009v003 4-14 UNDER DEVELOPMENT Feb 2010
User Guide: PTP 600 Series PTP 600 general reference information Environmental specifications Table 4-9 PTP 600 environmental specifications Category Specification ODU: -40°F (-40°C) to 140°F (+60°C) PIDU Plus (indoor deployment): 32°F (0°C) to 104oF (+40°C) Temperature PIDU Plus (outdoor deployment within weatherproofed cabinet): -40°F (-40°C) to 140°F (+60°C) PTP-SYNC: -40°F (-40°C) to 140°F (+60°C) Wind Loading 150mph Max (242kph). See Wind loading on page 2-7 for a full description.
PTP 25600 reference information Chapter 4 Reference information PTP 25600 reference information This section contains reference information that is specific to the PTP 25600 frequency variant. PTP 25600 examples of regulatory limits Table 4-10 shows how the regulatory limits currently apply in specific countries. Operators should note that regulations are subject to change. Table 4-10 PTP 25600 examples of regulatory limits Region Examples of Regulatory Limits at 2.
User Guide: PTP 600 Series PTP 25600 reference information PTP 25600 licenses and region codes PTP 25600 units may be operated in any of the regions listed in Table 4-11. When shipped, PTP 25600 units are configured with a license key for region code 16. An alternative license key is provided in the PTP 600 Installation Guide for region code 18. NOTE For a PTP 25600 in region code 16, the EIRP limit is approximately 63 dBm + 10 x Log(360/Antenna Azimuth BW).
PTP 25600 reference information Chapter 4 Reference information PTP 25600 regulatory compliance The PTP 25600 complies with the regulations that are in force in the USA. The relevant notifications are specified in this section. U.S. Federal Communication Commission (FCC) notification This device complies with Part 27 of the US FCC Rules and Regulations. Use of this product is limited to operators holding Licenses for the specific operating channels.
User Guide: PTP 600 Series PTP 25600 reference information PTP 25600 radio system specifications Table 4-12 contains radio system specifications for the PTP 25600. Table 4-12 PTP 25600 RF specifications Radio Technology Specification Lower: 2.496-2.568 GHz RF Band Middle: 2.572-2.614 GHz Upper: 2.618-2.690 GHz Channel Selection Manual selection.
PTP 25600 reference information Chapter 4 Reference information Radio Technology Specification Sensitivity at higher modes may be reduced during high Weather Sensitivity winds through trees due to Adaptive Modulation Threshold changes. Error Correction FEC PTP 25600 emissions and radio certifications Table 4-13 lists the EMC emissions specifications under which the PTP 25600 has received type approval. Table 4-14 lists the radio specifications under which the PTP 25600 has received type approval.
User Guide: PTP 600 Series PTP 25600 reference information PTP 25600 available spectrum settings The supported 2.5GHz frequency range is split into three bands, according to the bands specified in the FCC BRS-EBS Post-Transition Band plan (only for PTP 25600 and region code 16): • Lower: 2496 MHz to 2572 MHz with a 5.5MHz channel raster (76 MHz total). • Middle: 2572 MHz to 2614 MHz with a 6 MHz channel raster (42 MHz total). • Upper: 2618 MHz to 2690 MHz with a 5.5 MHz channel raster (76 MHz total).
PTP 25600 reference information Chapter 4 Reference information Table 4-15 PTP 25600 channel plan - FCC BRS-EBS Post-Transition Band Block Channel Channel Centre Frequencies (MHz) Bandwidth (MHz) Lower 5 2499.25, 2504.75, 2510.25, 2515.75, 2521.25, 2526.75, Band 2532.25, 2537.75, 2543.25, 2548.75, 2554.25, 2559.75, Segment 2565.25 10 2502, 2507.5, 2513, 2518.5, 2524, 2529.5, 2535, 2540.5, 2546, 2551.5, 2557, 2562.5 15 2504.75, 2510.25, 2515.75, 2521.25, 2526.75, 2532.25, 2537.75, 2543.
User Guide: PTP 600 Series PTP 25600 reference information NOTE The PTP 25600 frequency variant supports three portions of the BRS spectrum allocation. These are configurable at installation and constrain the wireless to operate in a limited portion of the Spectrum. The three frequency bands are as shown in Figure 4-1: Band 1: channels A, B, C and D (16.5 MHz blocks) Band 2: channels A through G (6 MHz blocks) Band 3: channels E, F, G and H (16.
PTP 25600 reference information Chapter 4 Reference information PTP 25600 system threshold, output power and link loss PTP 25600 system threshold, output power and maximum link loss are given in Table 4-16 (IP mode) and Table 4-17 (TDM mode). These figures assume that antenna gain is 23 dBi.
User Guide: PTP 600 Series PTP 25600 reference information Table 4-17 PTP 25600 - TDM mode - threshold, power and link loss Output Threshold Value (dBm) Power Maximum Link Loss (dB) (dBm) Channel Bandwidth 5 10 15 20 All 5 10 15 20 MHz MHz MHz MHz Bands MHz MHz MHz MHz BPSK 0.63 single -97.6 -95.1 -93.0 -90.4 +23 156.6 154.1 152.0 149.4 QPSK 0.63 single -91.6 -89.1 -88.2 -85.2 +23 150.6 148.1 147.2 144.2 QPSK 0.87 single -88.3 -85.6 -85.1 -81.5 +23 147.
PTP 45600 reference information Chapter 4 Reference information PTP 45600 reference information This section contains reference information for the PTP 45600 frequency variant. PTP 45600 examples of regulatory limits Table 4-18 shows how the regulatory limits currently apply in specific countries. Operators should note that regulations are subject to change. Table 4-18 PTP 45600 examples of regulatory limits Region US Federal NTIA Examples of Regulatory Limits at 4.
User Guide: PTP 600 Series PTP 45600 reference information PTP 45600 radio system specifications Table 4-20 contains radio system specifications for the PTP 45600. Table 4-20 PTP 45600 RF specifications Radio Technology Specification RF Band 4.400-4.600 GHz Channel Selection Manual selection. By intelligent Dynamic Frequency Selection (i-DFS) or Dynamic Frequency Control manual intervention; automatic selection on start-up and continual adaptation to avoid interference.
PTP 45600 reference information Chapter 4 Reference information Radio Technology Specification Sensitivity at higher modes may be reduced during high Weather Sensitivity winds through trees due to Adaptive Modulation Threshold changes Error Correction FEC PTP 45600 emissions and radio certifications Table 4-21 lists the EMC emissions specifications under which the PTP 45600 has received type approval. Table 4-22 lists the radio specifications under which the PTP 45600 has received type approval.
User Guide: PTP 600 Series PTP 45600 reference information PTP 45600 available spectrum settings The available spectrum settings for the PTP 45600 are illustrated in this section. The PTP 45600 product variant does not apply any band edge power reduction. Region code 23 Adjustment of the lower centre frequency allows the operator to slide the available frequency settings up and down the 4.5 GHz band in steps of 2 MHz.
PTP 45600 reference information Chapter 4 Reference information Figure 4-3 PTP 45600 available spectrum in 20 MHz channel bandwidth (RC 23) Figure 4-4 PTP 45600 available spectrum in 15 MHz channel bandwidth (RC 23) phn-0896_009v003 4-30 UNDER DEVELOPMENT Feb 2010
User Guide: PTP 600 Series PTP 45600 reference information Figure 4-5 PTP 45600 available spectrum in 10 MHz channel bandwidth (RC 23) Figure 4-6 PTP 45600 available spectrum in 5 MHz channel bandwidth (RC 23) Region code 24 (NTIA) In the 20 MHz (Figure 4-7) channel bandwidth, the PTP 45600 variant operates on a 20 MHz channel raster. In the 10 MHz (Figure 4-8) channel bandwidth, the PTP 45600 variant operates on a 10 MHz channel raster. The channel raster is set to even centre frequencies.
PTP 45600 reference information Chapter 4 Reference information Figure 4-7 PTP 45600 available spectrum in 20 MHz channel bandwidth (RC 24) Figure 4-8 PTP 45600 available spectrum in 10 MHz channel bandwidth (RC 24) phn-0896_009v003 4-32 UNDER DEVELOPMENT Feb 2010
User Guide: PTP 600 Series PTP 45600 reference information PTP 45600 system threshold, output power and link loss PTP 45600 system threshold figures are given in Table 4-23 (IP mode) and Table 4-24 (TDM mode). These figures assume that antenna gain is 23 dBi.
PTP 45600 reference information Chapter 4 Reference information Table 4-24 PTP 45600 - TDM mode - threshold, power and loss per modulation mode Threshold Value (dBm) Channel Bandwidth Output Power (dBm) Maximum Link Loss (dB) All 5 10 15 20 30 Bands MHz MHz MHz MHz MHz 20 30 MHz MH z MH z -93.7 -92.0 -90.4 -88.0 +27 166.6 163.7 162.0 160.4 158.0 -90.4 -89.1 -87.8 -86.0 -83.1 +27 158.1 155.4 153.3 151.6 149.5 QPSK 0.87 single -88.1 -85.4 -83.3 -81.6 -79.
User Guide: PTP 600 Series PTP 48600 reference information PTP 48600 reference information This section contains reference information for the PTP 48600 frequency variant. PTP 48600 examples of regulatory limits Table 4-25 shows how the regulatory limits currently apply in specific countries. Operators should note that regulations are subject to change. Table 4-25 PTP 48600 examples of regulatory limits Region US Federal NTIA Examples of Regulatory Limits at 5.
PTP 48600 reference information Chapter 4 Reference information PTP 48600 licenses and region codes PTP 48600 units may be operated in any of the regions listed in Table 4-26. When shipped, PTP 48600 units are configured with a license key for region code 15. An alternative license key is provided in the PTP 600 Installation Guide for region code 23. If the link is to be installed in any other permitted region, the user must obtain a new license key from the reseller or distributor.
User Guide: PTP 600 Series PTP 48600 reference information PTP 48600 radio system specifications Table 4-27 contains radio system specifications for the PTP 48600. Table 4-27 PTP 48600 RF specifications Radio Technology Specification RF Band 4.710-5.000 GHz Channel Selection Manual selection. By intelligent Dynamic Frequency Selection (i-DFS) or Dynamic Frequency Control manual intervention; automatic selection on start-up and continual adaptation to avoid interference.
PTP 48600 reference information Chapter 4 Reference information Radio Technology Specification Sensitivity at higher modes may be reduced during high Weather Sensitivity winds through trees due to Adaptive Modulation Threshold changes Error Correction FEC PTP 48600 emissions and radio certifications Table 4-28 lists the EMC emissions specifications under which the PTP 48600 has received type approval. Table 4-29 lists the radio specifications under which the PTP 48600 has received type approval.
User Guide: PTP 600 Series PTP 48600 reference information PTP 48600 available spectrum settings The available spectrum settings for the PTP 48600 are illustrated in this section. Region codes 15 and 23 Adjustment of the lower centre frequency allows the operator to slide the available frequency settings up and down the 4.8 GHz band in steps of 1 MHz. In the 20 MHz (Figure 4-9) channel bandwidth, the PTP 48600 variant operates on a 10 MHz channel raster.
PTP 48600 reference information Chapter 4 Reference information Figure 4-10 PTP 48600 available spectrum in 15 MHz channel bandwidth (RC 15 and 23) Figure 4-11 PTP 48600 available spectrum in the 10 MHz channel bandwidth (RC 15 and 23) phn-0896_009v003 4-40 UNDER DEVELOPMENT Feb 2010
User Guide: PTP 600 Series PTP 48600 reference information Figure 4-12 PTP 48600 available spectrum in 5 MHz channel bandwidth (RC 15 and 23) Region code 24 (NTIA) In the 20 MHz (Figure 4-13) channel bandwidth, the PTP 48600 variant operates on a 20 MHz channel raster. In the 10 MHz (Figure 4-14) channel bandwidth, the PTP 48600 variant operates on a 10 MHz channel raster. The channel raster is set to even centre frequencies.
PTP 48600 reference information Chapter 4 Reference information Figure 4-14 PTP 48600 available spectrum in 10 MHz channel bandwidth (RC 24) phn-0896_009v003 4-42 UNDER DEVELOPMENT Feb 2010
User Guide: PTP 600 Series PTP 48600 reference information PTP 48600 system threshold, output power and link loss PTP 48600 system threshold figures are given in Table 4-30 (IP mode) and Table 4-31 (TDM mode). These figures assume that antenna gain is 22 dBi.
PTP 48600 reference information Chapter 4 Reference information Table 4-31 PTP 48600 - TDM Mode - threshold, power and loss per modulation mode System Threshold (dBm) Channel Bandwidth 5 10 Modulation MHz MHz Mode 15 MH z 20 MHz Output Power (dBm) 5, 10, 15 Maximum Link Loss (dB) 20 MHz MHz 5 10 MHz MHz 15 20 MHz MHz BPSK 0.63 single -98.6 -95.5 -93.3 -91.9 +27 +27 169.6 166.5 164.3 162.9 QPSK 0.63 single -91.4 -88.8 -87.8 -85.7 +27 +27 162.4 159.8 158.8 156.
User Guide: PTP 600 Series PTP 49600 reference information PTP 49600 reference information This section contains reference information for the PTP 49600 frequency variant. PTP 49600 examples of regulatory limits Table 4-32 shows how the regulatory limits currently apply in specific countries. Operators should note that regulations are subject to change. Table 4-32 PTP 49600 examples of regulatory limits Region Examples of Regulatory Limits at 5.
PTP 49600 reference information Chapter 4 Reference information NOTE Region codes 14 and 18 Max Power depends upon Antenna Gain: If Antenna Gain < 26 dBi then Max Power = 24 dBm If Antenna Gain >= 26 dBi then Max Power = (50 – Antenna Gain) dBm PTP 49600 regulatory compliance The PTP 49600 complies with the regulations that are in force in the USA and Canada. The relevant notifications are specified in this section.
User Guide: PTP 600 Series PTP 49600 reference information PTP 49600 radio system specifications Table 4-34 contains radio system specifications for the PTP 49600. Table 4-34 PTP 49600 RF specifications Radio Technology Specification RF Band 4.900-4.990 GHz Channel Selection Manual selection. By intelligent Dynamic Frequency Selection (i-DFS) or Dynamic Frequency Control manual intervention; automatic selection on start-up and continual adaptation to avoid interference.
PTP 49600 reference information Chapter 4 Reference information Radio Technology Specification Sensitivity at higher modes may be reduced during high Weather Sensitivity winds through trees due to Adaptive Modulation Threshold changes Error Correction FEC PTP 49600 emissions and radio certifications Table 4-35 lists the EMC emissions specifications under which the PTP 49600 has received type approval. Table 4-36 lists the radio specifications under which the PTP 49600 has received type approval.
User Guide: PTP 600 Series PTP 49600 reference information PTP 49600 available spectrum settings The available spectrum settings for the PTP 49600 are illustrated in this section. In the 20 MHz (Figure 4-15), 10 MHz (Figure 4-16) and 5 MHz (Figure 4-17) channel bandwidths, the PTP 49600 variant operates on a 5 MHz channel raster. The channel raster is set to even centre frequencies. NOTE These tables contain data for one typical region code.
PTP 49600 reference information Chapter 4 Reference information Figure 4-17 PTP 49600 available spectrum in the 5 MHz channel bandwidth phn-0896_009v003 4-50 UNDER DEVELOPMENT Feb 2010
User Guide: PTP 600 Series PTP 49600 reference information PTP 49600 system threshold, output power and link loss PTP 49600 system threshold figures are given in Table 4-37 (IP mode) and Table 4-38 (TDM mode). These figures assume that antenna gain is 22 dBi.
PTP 49600 reference information Chapter 4 Reference information Table 4-38 PTP 49600 - TDM mode - threshold, power and loss per modulation mode Output Threshold Value Power (dBm) (dBm) Maximum Link Loss (dB) Channel Bandwidth Modulation 5 10 MHz MHz Mode 20 MH z All 5 10 Bands MHz MHz 20 MHz BPSK 0.63 single -98.6 -95.5 -91.9 +24 166.6 163.5 159.9 QPSK 0.63 single -91.4 -88.8 -85.7 +24 159.4 156.8 153.7 QPSK 0.87 single -87.9 -85.2 -81.9 +24 155.9 153.2 149.
User Guide: PTP 600 Series PTP 54600 reference information PTP 54600 reference information This section contains reference information for the PTP 54600 frequency variant. PTP 54600 examples of regulatory limits Table 4-39 shows how the regulatory limits currently apply in specific countries. Operators should note that regulations are subject to change. Table 4-39 PTP 54600 examples of regulatory limits Region Examples of Regulatory Limits at 5.
PTP 54600 reference information Chapter 4 Reference information NOTE In regions other than EU/USA, specific local regulations may apply. It is the responsibility of the installer/user to check that the equipment as deployed meets local regulatory requirements. PTP 54600 licenses and region codes PTP 54600 units may be operated in any of the regions listed in Table 4-40. When shipped, PTP 54600 units are configured with a license key for region code 26.
User Guide: PTP 600 Series Region License / code Regulation PTP 54600 reference information Channel Frequencies DFS 5650 - 5725 Bandwidth Max Power Notes 15 MHz 27 dBm 5650 MHz is EIRP reserved for MHz 10 MHz 25 dBm EIRP 5 MHz the use of weather radars.
PTP 54600 reference information Chapter 4 Reference information This device complies with part 15.407 of the US FCC Rules and Regulations and with RSS-210 Issue 7 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
User Guide: PTP 600 Series PTP 54600 reference information PTP 54600 European Union notification The PTP 54600 product is a two-way radio transceiver suitable for use in Broadband Wireless Access System (WAS), Radio Local Area Network (RLAN), or Fixed Wireless Access (FWA) systems. It is a Class 1 device and uses operating frequencies that are harmonized throughout the EU member states.
PTP 54600 reference information Chapter 4 Reference information PTP 54600 radio system specifications Table 4-41 contains radio system specifications for the PTP 54600. Table 4-41 PTP 54600 RF specifications Radio Technology Specification RF Band 5.470-5.725 GHz By dynamic frequency control and manual intervention Channel Selection Automatic detection on start-up and continual adaptation to avoid interference. Dynamic Frequency Control Channel size Initial capture 10-15 sec.
User Guide: PTP 600 Series PTP 54600 reference information Radio Technology Specification Over-the-Air Encryption Proprietary scrambling mechanism. Sensitivity at higher modes may be reduced during high Weather Sensitivity winds through trees due to Adaptive Modulation Threshold changes Error Correction FEC PTP 54600 emissions and radio certifications Table 4-42 lists the EMC emissions specifications under which the PTP 54600 has received type approval.
PTP 54600 reference information Chapter 4 Reference information PTP 54600 available spectrum settings The available spectrum settings for the PTP 54600 are illustrated in this section. Adjustment of the lower centre frequency allows the operator to slide the available frequency settings up and down the 5.4 GHz band in steps of 2 MHz. In the 30 MHz channel bandwidth (Figure 4-18), the PTP 54600 variant operates on a 10 MHz channel raster.
User Guide: PTP 600 Series PTP 54600 reference information Figure 4-19 PTP 54600 available spectrum in 15 MHz channel bandwidth Figure 4-20 PTP 54600 available spectrum in 10 MHz channel bandwidth Figure 4-21 PTP 54600 available spectrum in 5 MHz channel bandwidth phn-0896_009v003 Feb 2010 UNDER DEVELOPMENT 4-61
PTP 54600 reference information Chapter 4 Reference information PTP 54600 system threshold, output power and link loss PTP 54600 system threshold, output power and maximum link loss are given in Table 4-44 (IP mode) and Table 4-45 (TDM mode). These figures assume that antenna gain is 23 dBi.
User Guide: PTP 600 Series PTP 54600 reference information Table 4-45 PTP 54600 - TDM mode - threshold, power and loss per modulation mode Output Threshold Value (dBm) Power Maximum Link Loss (dB) (dBm) Channel Bandwidth 5 10 15 Modulation MHz MHz MHz Mode 30 MH z All 5 10 15 Bands MHz MHz MHz 30 MHz BPSK 0.63 single -98.2 -94.6 -92.3 -88.9 +25 169.2 165.6 163.3 159.9 QPSK 0.63 single -89.7 -88.3 -86.4 -81.4 +24 159.7 158.3 156.4 151.4 QPSK 0.87 single -86.
PTP 54600 reference information Chapter 4 Reference information PTP 54600 FCC antenna restrictions In FCC regions, external antennas from the list in Table 4-46 can be used with the Connectorized version of the PTP 54600. These are approved by the FCC for use with the product and are constrained by the following limit for Single/Dual Polarization Parabolic Dish Antennas: up to 34.9 dBi (33.4 dBi for 5 MHz bandwidth) per polarization or antenna.
User Guide: PTP 600 Series PTP 54600 reference information Manufacturer Antenna Type Gabriel Gabriel 2-foot High Performance Dual Gain Parabolic (dBi) Dish 28.1 Y 34.3 Y 28.5 Y 28.5 Y 31.2 Y 34.8 Y 34.8 Y 28.4 Y 31.1 Y 28.4 Y 34.7 Y 34.7 Y 28.1 Y 29 Y 31.1 Y 31.
PTP 54600 reference information Chapter 4 Reference information Manufacturer Antenna Type RadioWaves Radio Waves 4-foot Dual-Pol Parabolic, SPD4- Gain Parabolic (dBi) Dish 34.4 Y 34.8 Y 28.3 Y 31.4 Y 34.6 Y 27.9 Y 31.4 Y 33.9 Y 31.4 Y 33.9 Y 5.2 (34.4dBi) RadioWaves Radio Waves 4-foot Parabolic, SP4-5.2 (34.8dBi) RadioWaves Radio Waves 2-foot Parabolic, SP2-2/5 (28.3dBi) RadioWaves Radio Waves 3-foot Parabolic, SP3-2/5 (31.
User Guide: PTP 600 Series PTP 58600 reference information PTP 58600 reference information This section contains reference information that is specific to the PTP 58600 frequency variant. PTP 58600 examples of regulatory limits Table 4-47 shows how the regulatory limits currently apply in specific countries. Operators should note that regulations are subject to change. Table 4-47 PTP 58600 examples of regulatory limits Region Examples of Regulatory Limits at 5.
PTP 58600 reference information Region Chapter 4 Reference information Examples of Regulatory Limits at 5.8GHz Operation of this product is only allowed with a License Key for India Region 19 (36 dBm or 4W EIRP at 15 MHz and 10 MHz and 33 dBm or 2 W EIRP at 5 MHz channel bandwidth). Thailand Germany Operation of this product is only allowed with a License Key for Region 20 (30 dBm or 1W EIRP). Operation of this product is only allowed with a License Key for Region 22.
User Guide: PTP 600 Series PTP 58600 reference information phn-0896_009v003 Feb 2010 UNDER DEVELOPMENT 4-69
PTP 58600 reference information Chapter 4 Reference information PTP 58600 licenses and region codes PTP 58600 units may be operated in any of the regions listed in Table 4-48. PTP 58600 units are configured with a license key for region code 1. An alternative license key is provided in the PTP 600 Installation Guide for region code 25. For any other permitted region, obtain a new license key from the reseller or distributor.
User Guide: PTP 600 Series Region License / code Regulation 5 Singapore 6 Eire PTP 58600 reference information Frequencies DFS Channel Max Power Notes Bandwidth 5725 - 5850 5, 10, 15, 30 20 dBm MHz MHz EIRP 5725 - 5850 30 MHz MHz 33 dBm EIRP 15 MHz 31 dBm EIRP 10 MHz 30 dBm EIRP 5 MHz 27 dBm EIRP 7 Norway 5725 - 5795 Yes 30 MHz MHz 5815 - 5850 MHz 15 MHz 53 dBm 5795 MHz to EIRP 5815 MHz is 51 dBm EIRP 10 MHz 5 MHz assigned for Road Transport 50 dBm and Traffic
PTP 58600 reference information Region License / code Regulation 20 Thailand 22 Germany Chapter 4 Reference information Frequencies DFS Channel Max Power Notes Bandwidth 5725 - 5850 5, 10, 15, 30 30 dBm MHz MHz EIRP 5755 - 5850 Yes 30 MHz MHz 35 dBm EIRP 15 MHz 34 dBm EIRP 10 MHz 5 MHz 1dB reduction required in 30 MHz to achieve 32 dBm adjacent EIRP channel 29 dBm emissions EIRP 24 Bahrain 5725 - 5850 Yes 30 MHz MHz 33 dBm EIRP 15 MHz 31 dBm EIRP 10 MHz 30 dBm
User Guide: PTP 600 Series Region License / code Regulation PTP 58600 reference information Frequencies DFS Channel Max Power Notes 29 dBm (RTTT) Bandwidth 5 MHz EIRP phn-0896_009v003 Feb 2010 UNDER DEVELOPMENT 4-73
PTP 58600 reference information Chapter 4 Reference information PTP 58600 regulatory compliance The PTP 58600 complies with the regulations that are in force in the USA, Canada and Europe. The relevant notifications are specified in this section. PTP 58600 FCC and IC notification U.S. Federal Communication Commission (FCC) and Industry Canada (IC) Notification. This system has achieved Type Approval in various countries around the world.
User Guide: PTP 600 Series • PTP 58600 reference information Consult the dealer and/or experienced radio/TV technician for help. FCC IDs and Industry Canada Certification Numbers are listed below: Where necessary, the end user is responsible for obtaining any National licenses required to operate this product and these must be obtained before using the product in any particular country.
PTP 58600 reference information Chapter 4 Reference information European Union (EU) Waste of Electrical and Electronic Equipment (WEEE) directive The European Union's WEEE directive requires that products sold into EU countries must have the crossed out trash bin label on the product (or the package in some cases).
User Guide: PTP 600 Series PTP 58600 reference information PTP 58600 radio system specifications Table 4-49 contains radio system specifications for the PTP 58600. Table 4-49 PTP 58600 RF specifications Radio Technology Specification RF Band 5.725-5.850 GHz By dynamic frequency control and manual intervention Channel Selection Automatic detection on start-up and continual adaptation to avoid interference. Dynamic Frequency Control Channel size Initial capture 10-15 sec.
PTP 58600 reference information Chapter 4 Reference information Radio Technology Specification 125 miles (200km) optical line-of-sight Range 6 miles (10km) non-line-of-sight Over-the-Air Encryption Proprietary scrambling mechanism.
User Guide: PTP 600 Series PTP 58600 reference information Table 4-51 PTP 58600 radio certifications Region Specification (Type Approvals) USA FCC Part 15.247 CANADA RSS 210 Issue 7, Annex 8 UK IR 2007 Eire ComReg 02/71R1 EU EN302 502 v 1.2.
PTP 58600 reference information Chapter 4 Reference information PTP 58600 available spectrum settings The available spectrum settings for the PTP 58600 are illustrated in this section. Adjustment of the lower centre frequency allows the operator to slide the available frequency settings up and down the 5.8 GHz band in steps of 2 MHz. In the 30 MHz channel bandwidth (Figure 4-22), the PTP 58600 variant operates on a 10 MHz channel raster.
User Guide: PTP 600 Series PTP 58600 reference information Figure 4-23 PTP 58600 available spectrum in 15 MHz channel bandwidth Figure 4-24 PTP 58600 available spectrum in the 10 MHz channel bandwidth Figure 4-25 PTP 58600 available spectrum in 5 MHz channel bandwidth phn-0896_009v003 Feb 2010 UNDER DEVELOPMENT 4-81
PTP 58600 reference information Chapter 4 Reference information PTP 58600 Transmit Power Reduction at the Band Edges Operation at or near the 5.8 GHz band edges can results in a lower maximum transmit power. In some configurations the PTP 600 Series solution reduces the power when operating at the edge channels. The amount of reduction, if any, is dependant on the region code of the region of operation. This currently only affects systems configured with region code 1.
User Guide: PTP 600 Series PTP 58600 reference information PTP 58600 system threshold, output power and link loss PTP 58600 system threshold figures are given in Table 4-53 (IP mode) and Table 4-54 (TDM mode). These figures assume that antenna gain is 23 dBi.
PTP 58600 reference information Chapter 4 Reference information Table 4-54 PTP 58600 - TDM mode - threshold, power and loss per modulation mode Output Threshold Value (dBm) Power Maximum Link Loss (dB) (dBm) Channel Bandwidth Modulation 5 10 15 MHz MHz MHz Mode 30 MH z All 5 10 15 Bands MHz MHz MHz 30 MHz BPSK 0.63 single -95.1 -92.5 -90.8 -86.3 +25 166.1 163.5 161.8 157.3 QPSK 0.63 single -88.7 -87.8 -86.0 -80.6 +24 158.7 157.8 155.9 150.6 QPSK 0.87 single -85.
User Guide: PTP 600 Series PTP 58600 reference information PTP 58600 FCC antenna restrictions In FCC regions, external antennas from the lists in Table 4-55 and Table 4-56 can be used with the Connectorized version of the PTP 58600. These are approved by the FCC for use with the product and are constrained by the following limit for Single/Dual Polarization Parabolic Dish Antennas: up to 37.7 dBi per polarization or antenna.
PTP 58600 reference information Chapter 4 Reference information Manufacturer Antenna Type RFS RFS 1-foot Flat Panel, MA0528-23AN Gain Flat Parabolic (dBi) Plate Dish 23 Y 28 Y 28 Y (23dBi) RFS RFS 2-foot Flat Panel, MA0528-28AN (28dBi) Telectronics Teletronics 2-foot Flat Plate Antenna, ANT-P5828 (28dBi) Andrew Andrew 2-foot Parabolic, P2F-52 (29.4dBi) 29.4 Y Andrew Andrew 2-foot Dual-Pol Parabolic, PX2F- 29.4 Y 52 (29.4dBi) Andrew Andrew 3-foot Parabolic, P3F-52 (33.
User Guide: PTP 600 Series PTP 58600 reference information Manufacturer Antenna Type Gabriel Gabriel 2-foot Standard QuickFire Gain Flat Parabolic (dBi) Plate Dish 28.5 Y 28.5 Y 31.2 Y 34.8 Y 34.8 Y 37.7 Y 28.4 Y 31.1 Y 28.4 Y 34.7 Y 34.7 Y 37.7 Y 28.1 Y 29 Y Parabolic, QF2-52-N Gabriel Gabriel 2-foot Standard QuickFire Parabolic, QF2-52-N-RK Gabriel Gabriel 2.5-foot Standard QuickFire Parabolic, QF2.
PTP 58600 reference information Chapter 4 Reference information Manufacturer Antenna Type RadioWaves Radio Waves 3-foot Dual-Pol Parabolic, Gain Flat Parabolic (dBi) Plate Dish 31.1 Y 31.4 Y 34.4 Y 34.8 Y 37.5 Y 37.7 Y 28.3 Y 31.4 Y 34.6 Y 37.7 Y 27.9 Y 31.4 Y 33.9 Y 37.4 Y 31.4 Y 33.9 Y SPD3-5.2 (31.1dBi) RadioWaves Radio Waves 3-foot Parabolic, SP3-5.2 (31.4dBi) RadioWaves Radio Waves 4-foot Dual-Pol Parabolic, SPD4-5.2 (34.
User Guide: PTP 600 Series PTP 58600 reference information Manufacturer Antenna Type RFS RFS 6-foot HP Parabolic, SDF6-52AN or Gain Flat Parabolic (dBi) Plate Dish 37.4 Y 33.8 Y SDFX6-52AN (37.4dBi) StellaDoradus StellaDoradus 45 inch Parabolic Antenna, 58PSD113 Table 4-56 Sectored antennas for deployment in USA/Canada – 5.