Installation manual NÜO PASS 42106 | 42142
NÜO PASS Manual Introduction Features GENERAL FEATURES NÜO PASS (Ref. no. 42106 and 42142) --Combined biometrics reader with proximity. --High resolution 500 dpi optical fingerprint sensor. --Maximum security proximity reader for MIFARE Plus® cards and MIFARE® DESFire® EV1, MIFARE® Classic and MIFARE Ultralight® cards available on demand. --Proximity card reader from a distance of 3 to 5 cm.
NÜO PASS Manual Introduction Features Technical Specifications TECHNICAL SPECIFICATIONS NÜO PASS: INPUT VOLTAGE 24 VDC (11 - 28 VDC) MAXIMUM POWER 5W READING DISTANCE 3 - 5 cm FINGERPRINT SENSOR TYPE Optical SENSOR RESOLUTION 500 dpi MAX. NO.
NÜO PASS Manual Introduction Features Wiring TYPE OF WIRING AND WIRING DISTANCE: The NÜO PASS incorporates a male overhead connector. NÜO PASS is supplied with a 3.5 metre piped cable with 4 wires (2 twisted pairs) and a female connector at one end to correctly connect it. The other end of the piped cable is connected to a single door controller or to the corresponding Wili following the simple colour coding. + A B BY B U S Orange O/W Green G/W 3.
NÜO PASS Manual Installation NÜO PASS Installation on built walls --STEPS PRIOR TO INSTALLATION: 1) Remove the front panel using the suction cup provided. The panel will be easier to remove if the suction cup is placed in a corner. 2) Unscrew the flush mount support. --INSTALLATION ON BUILT WALLS: 3) Using a level, make a hole in the wall with the dimensions detailed in the diagram. Pass the connecting cable through and grout the hole.
NÜO PASS Manual Installation NÜO PASS Installation in plasterboard (thickness 10 - 25mm) --INSTALLATION IN PLASTERBOARD (THICKNESS 10 - 25mm) 1) Follow the initial steps listed in page 6. 2) Make a hole in the plasterboard with the dimensions detailed in the diagram. 3) Insert the flush mount support and pass the cable through one of the holes, then secure it in place in the plasterboard using the tabs. 68 128 128 x 68 mm 4) Connect the cable to the assembly that was removed beforehand.
NÜO PASS Manual Installation NÜO PASS Installation on concrete walls --INSTALLATION ON CONCRETE WALLS: 1) Follow the initial steps listed in page 6. 2) Make 4 holes at the distance marked for Fischer 5mm wall plugs. 3) Secure the mounting box using the 4 Fischer wall plugs and the screws supplied. 70 130 Distance between holes 130 x 70mm Mounting box: 42170 4) Connect the wiring pipe and pass the cable through, connecting the equipment. 5) Tighten the screws and place the front panel.
NÜO PASS Manual Installation NÜO PASS Installation in other environments --INSTALLATION IN OTHER ENVIRONMENTS: 1) Follow the initial steps listed in page 6. 2) Make 4 M3 holes and another hole with the dimensions detailed in the diagram, taking the radii or chamfer dimensions into consideration. 3) Connect the cable to the equipment and fasten it using screws. 66 15.84 15.84 R1 8.5 58.7 26.5 (x4) Inserto S-M3 .5 R 18 126 63 62.2 56.49 118.7 118.69 45° 32.2 33 58.
NÜO PASS Manual Installation NÜO PASS Wiring NÜO PASS readers can be directly connected to two types of devices depending on the architecture of the installation: --Connection to a Wili. --Connection to a single door controller. The connection to be made for both types of devices is exactly the same. The colour code must be followed. For more detailed information, consult the equipment manuals referenced earlier.
Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipmentÿ Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.