Submittal

LAARS M4-LHS
Control for
Condensing,
Non-Condensing,
Modulation and
Stage-Fired Boilers
CA009200
Submittal Data
Date:
Project #:
Engineer:
Prepared By:
Bid Date:
Project Name:
Location:
Contractor:
Features
Operates two groups of boilers -
condensing and non-condensing -
each with independent configura-
tion - to achieve the highest
system efficiency
Chooses condensing or non-
condensing groups based on
system temperature
Controller works with either stage-
fired or modulated boilers
Controls 0-5V, 1-5V, 0-10V, 2-10V
and 4-20mA boilers, or stage-fired
boilers, in any combination
Lo/Hi/Lo/Hi sequencing fires lag
boiler after the lead boiler reaches
full fire capacity - Lo/Lo/Hi/Hi
sequencing provides an opportu-
nity for higher boiler efficiency to
bring on the lowest firings stages
of all the boiler before moving any
of them to higher firing rates
Parallel or normal modulation
provides efficient, smooth, and
adjustable modulation that can fit
most applications whether the
boilers are to sequence normally
(one after another) or in parallel
Each boiler can be set for one of
three rotation modes; timed (one
hour to sixty days), manual, or
last-on/last-off
Each boiler can be set individually
to be automatically operated, fully
on, manually adjusted, off or be
considered a standby boiler. The
standby boiler is used as a
backup with an adjustable standby
delay. This feature is great for
using less efficient boilers (with
lower initial purchase cost) for
periods of high demand only
Soft-off feature, lag delay and last
stage hold assist in minimizing
boiler short-cycling
Adjustable ignition start point and
modulation start point
Adjustable purge delay feature to
match the boiler's pre-purge time
Adjustable minimum and maxi-
mum system temperature protect
boilers or system
Communicates with EMS (energy
management system) by adding
the XSIG 4-20mA interface
module, and has shutdown and
prove inputs for the EMS
Domestic hot water with or without
priority
Outdoor reset allows the controller
to adjust system water tempera-
ture based on outdoor air
temperature for fuel savings
Built-in day/night schedule with
adjustable night setback for fuel
savings
External setback signal is accepted
for applications that do not follow a
pre-detemined schedule
Summer shutdown with domestic
water override
Brightly lit LCD, visible with no
ambient light
Graphics that display in plain English
Graphical history displayed on the
screen shows system and outdoor
temps for last 24 hours
Settings can be copied from one
boiler to another for easy program-
ming
Memory and backup with lithium
battery to store information for 100
days
Locking NEMA-1 enclosure -
controller has an integral program-
ming switch that can only be
accessed when wiring cover has
been unlocked and removed
UL Listed, tested per standard 916
Standard
Equipment
Multiple boiler control, used to
lead-lag modulating, stage-fired,
condensing and non-condensing
boilers
Controls up to four stages (one
modulating boiler is one stage)
Ready to use with Laars X-BAC
BACnet interface module
Ready to use with up to two
M4EXT extension modules for
control of up to 16 modulating
stages
Ready to use with XSIG module to
accept external 4-20mA control
signal
Outdoor reset or setpoint control
System water temperature sensor
System water temperature sensor
well
Outdoor air temperature sensor
Outdoor air temperature sensor clip
®