Installation Manual

1 | Overview
2 | SDI2 address settings
The module’s address switches provide a tens and ones value
for the module’s address. For single-digit address numbers 1
through 9, set the tens switch to 0 and the ones digit to the
appropriate number. Figure 2.1 shows the address switches
setting for addresses 1 and 11.
Set the address switches per the control panel configuration. If
multiple B308 modules reside on the same system, each B308
module must have a unique address.
3.1 | Mount the module in the enclosure
Mount the module into the enclosure’s 3-hole mounting
pattern using the supplied mounting screws and mounting
bracket. Refer to Figure 3.1.
Figure 3.1: Mounting the module in the enclosure
3.2 | Mount and wire the tamper switch
You can connect an optional enclosure door tamper switch
for one module in an enclosure.
Installing the optional tamper switch:
1. Mount the ICP-EZTS Tamper Switch (P/N: F01U009269)
into the enclosure’s tamper switch mounting location.
For complete instructions, refer to EZTS Cover and Wall
Tamper Switch Installation Guide (P/N: F01U003734).
2. Plug the tamper switch wire onto the module’s tamper
switch connector. Refer to Figure 1.1.
3.3 | Wire to the control panel
When you wire the module to a control panel, you can use either
the module’s terminal strip labeled with PWR, A, B, and COM,
or the module’s interconnect wiring connectors (wire included).
Interconnect wiring parallels the PWR, A, B, and COM terminals
on the terminal strip. Figure 1.1 indicates the location of both
the terminal strip and the interconnect connectors on the
module.
Refer to Figures 3.2, 3.3, and 3.4.
NOTICE!
Use either the terminal strip wiring or interconnect
wiring connector to the control panel. Do not use
both. When connecting multiple modules, you can
combine terminal strip and interconnect wiring
connectors in series.
3 | Installation
After you set the address switches for the proper address,
install the module in the enclosure, and then wire it to the
control panel.
Callout ― Description
1 ― Module with mounting bracket installed
2 ― Enclosure
3 ― Mounting screws (3)
Figure 3.2: Using terminal strip or interconnect cable wiring
D9412GV4 shown)
Callout ― Description
1 ― Terminal strip wiring (SDI2)
2 ― Interconnect cable (P/N: F01U079745) (included)
Figure 3.3: Installing multiple modules using the SDI2 terminal
strip (D9412GV4 shown)
Callout ― Description
1 ― Bosch control panel
2 ― B308 modules
Figure 3.4: Installing multiple modules using the SDI2
interconnect wiring connector (D9412GV4 shown)
Callout ― Description
1 ― Bosch control panel
2 ― B308 modules
CAUTION!
Remove all power (AC and battery) before making any
connections. Failure to do so might result in personal
injury and/or equipment damage.
NOTICE!
The module reads the address switch setting only
during power up. If you change the switches after
you apply power to the module, you must cycle the
power to the module to enable the new setting.
Two address switches determine the address for the B308
Octo-output Module. The control panel uses the address for
communications. The address also determines the output
numbers. Use a slotted screwdriver to set the two address
switches.
Figure 2.1: Address switches
= Outputs 11 to 18
= Outputs 111 to 118
2.1 | Valid addresses and output numbers per
control panel
Valid B308 addresses are dependent on the number of outputs
allowed by a particular control panel.
Control
panel
Valid B308
addresses
Corresponding output
numbers
B9512G 01 - 59 11 - 18, 21 - 28, 31 - 38, 41 -
48, 51 - 58, 61 - 68, 71 - 78,
81 - 88, 91 - 98, 101 - 108,
111 - 118, 121 - 128, 131 -
138, 141 - 148, 151 - 158,
161 - 168, 171 - 178, 181
- 188, 191 - 198, 201 - 208,
211 - 218, 221 - 228,
231 - 238, 241 - 248, 251 -
258, 261 - 268, 271 - 278,
281 - 288, 291 - 298, 301
- 308, 311 - 318, 321 - 328,
331 - 338, 341 - 348, 351 -
358, 361 - 368, 371 - 378,
381 - 388, 391 - 398, 401
- 408, 411 - 418, 421 - 428,
431 - 438, 441 - 448, 451 -
458, 461 - 468, 471 - 478,
481 - 488, 491 - 498, 501
- 508, 511 - 518, 521 - 528,
531 - 538, 541 - 548, 551 -
558, 561 - 568, 571 - 578,
581 - 588, 591 - 598
B8512G 01 - 09 11 - 18, 21 - 28, 31 - 38, 41 -
48, 51 - 58, 61 - 68, 71 - 78,
81 - 88, 91 - 98
B6512 01 - 09 11 - 18, 21 - 28, 31 - 38, 41 -
48, 51 - 58, 61 - 68, 71 - 78,
81 - 88, 91 - 96
B5512 01 - 05 11 - 18, 21 - 28, 31 - 38,
41 - 48, 51 - 58
B4512 01 - 03 11 - 18, 21 - 28, 31 - 38
D9412GV4 01 - 12 11 - 18, 21 - 28, 31 - 38,
41 - 48, 51 - 58, 61 - 68,
71 - 78, 81 - 88, 91 - 98,
101 - 108, 111 - 118,
121 - 128
D7412GV4 01 - 06 11 - 18, 21 - 28, 31 - 38,
41 - 48, 51 - 58, 61 - 64
D7212GV4 01 - 02 11 - 18, 21 - 24
To determine the output numbers for each address, multiply
the address number by 10 for the base number, and then use
numbers 1 through 8 in the ones place for the output numbers.
For examples, refer to Section 8.
The B308 Octo-output Module is a supervised device that
provides 8 programmable outputs (Form C relays) and connects
to control panels through the SDI2 bus. Each output provides
dry contact switching rated for a maximum of 1.0 A at 24 VDC.
The outputs are accessed through on-board screw terminal
connections. The address switches are used to set the module’s
SDI2 address. Control panel programming determines each
output’s response to specific events. The B308 receives serial
data from the control panel and activates outputs in response
to control panel conditions and settings. Outputs can be
programmed for remote control from a control panel keypad.
Figure 1.1: Board overview
Callout ― Description
1 ― SDI2 interconnect wiring connectors
(to control panel or additional modules)
2 ― SDI2 terminal strip
(to control panel or additional modules)
3 ― Tamper switch connector
4 ― Terminal strip (outputs)
5 ― Heartbeat LED (blue)
6 ― Address switches