LECTUS select ARD‑SELECT‑BP | ARD‑SELECT‑BPK | ARD‑SELECT‑BO | ARD‑SELECT‑BOK | ARD‑SELECT‑WP | ARD‑SELECT‑WPK | ARD‑SELECT‑WO | ARD‑SELECT‑WOK | ARA‑SELECT‑WWA | ARA‑SELECT‑SWA en Installation manual 1 2 3 4 5 6 7 8 9 C 0 E
LECTUS select Table of contents | en 3 Table of contents 1 Safety 4 1.1 FCC Class B 5 2 General 6 2.1 Introduction 6 2.2 Disposal 7 2.3 Components 7 2.4 Functional requirements 2.4.1 OSDP 11 2.4.2 Phg_crypt 11 2.4.3 Firmware overview 11 2.5 RFID technology 12 2.6 Transponder data 13 2.7 Reading distances 14 3 Installation 16 3.1 General 16 3.1.1 Mechanical structure of the flush-mount version 16 3.1.
en | Safety 1 LECTUS select Safety – Read, observe and keep the instructions - the entire safety and operating instructions must be read and correctly followed before the readers are operated. – Take all warnings into account - follow all warnings on the devices and in the operating instructions. – Power sources - the readers should only be operated with the recommended power sources. If you are unsure whether you can use a specific power supply, contact your dealer.
LECTUS select Safety | en 5 Danger! - The device must be operated in a fully assembled state only. - Before connecting the device to the power supply, make sure that the connected operating voltage does not exceed the permitted values according to the technical specifications.
en | General LECTUS select 2 General 2.1 Introduction This installation manual is aimed at authorized service providers. The installation manual contains instructions on the installation and configuration of the Bosch Security Systems proximity reader LECTUS select. 1 2 3 4 5 6 7 8 9 C 0 E Figure 2.1: LECTUS select readers 2021-01 | 01 | F.01U.389.837 Installation manual Bosch Security Systems B.V.
LECTUS select 2.2 General | en 7 Disposal Old electrical and electronic equipment This product and/or battery must be disposed of separately from household waste. Dispose such equipment according to local laws and regulations, to allow their reuse and/or recycling. This will help in conserving resources, and in protecting human health and the environment. 2.3 Components x1 Quantity Bosch Security Systems B.V.
en | General LECTUS select Quantity 2021-01 | 01 | F.01U.389.837 Component 1 Quick installation guide 2 Safety instructions Installation manual Bosch Security Systems B.V.
LECTUS select 2.4 General | en 9 Functional requirements The LECTUS select reader reads data from contactless RFID credentials and sends the data to a higher-level control center. This is where the evaluation takes place as to whether a credential is authorized or not. The result is sent back to the reader, which then provides a visual and an acoustic signal. Communication between the reader and the control center takes place via an encrypted RS485 bus.
en | General LECTUS select Surface-mount version 80.4 mm 88 mm 56 mm 22 mm 1 mm 93.4 mm 21.2 mm 101 mm 56 mm 3.5 mm 16.2 mm 41 mm Accessories for surface-mount version: ARA-SELECT-SWA, ARA-SELECT-WWA Flush-mount version 19 mm 2 mm 16 mm 101 mm 88 mm Wall bracket for flush mounting (part included) The wall bracket is included in the reader delivery. 7 mm 71.6 mm 56 mm 14.5 mm 73 mm 26.2 mm 25.7 mm 56 mm 60 mm 50.5 mm 3.5 mm 2021-01 | 01 | F.01U.389.
LECTUS select 2.4.1 General | en 11 OSDP The following readers support OSDP V2 protocol: Commercial Type Number (CTN) Description ARD-SELECT-BO Black, OSDP ARD-SELECT-WO White, OSDP ARD-SELECT-BOK Black, OSDP, Keypad ARD-SELECT-WOK White, OSDP, Keypad OSDP protocol is common within the Bosch Access Control Systems product portfolio. 2.4.
2.5 en | General LECTUS select RFID technology The LECTUS select readers support the following RFID technology: – LEGIC prime / Advant – MIFARE Classic /DESFire / EV 1 The RFID technology that can be used is dependent on the reader configuration and the reader firmware. 2021-01 | 01 | F.01U.389.837 Installation manual Bosch Security Systems B.V.
LECTUS select 2.6 General | en 13 Transponder data The support of the transponder media listed below depends on the respective variant or reading technology (hardware platform) and the respective reader firmware. The following non-exhaustive list includes transponder media that is supported by the reader.
en | General 2.7 LECTUS select Reading distances The normal reading distance depends on the respective reading system, the installation environment and the type of data carrier. Direct mounting on metal might reduce the optimal reading distance.
LECTUS select General | en 15 Influencing (reducing) the reading distance The reading distance can be influenced due to different reasons. On the one hand this is influenced by the medium (i.e. the data carrier) and on the other hand by the ambient conditions of the antenna and the data carrier. The following is a list of points that can reduce the reading distance: – "Shade" or shield the data carrier with metal, such as EC card in your wallet, key fob on your key ring, etc. – No optimal coupling, i.
en | Installation LECTUS select 3 Installation 3.1 General When choosing the installation location, please note: The readers can interfere with each other or be negatively influenced by other systems and sources of interference. The readers can still disturb each other at a distance of approx. two to three times the reading distance. High-energy sources of interference in the range of the modulation and carrier frequencies can also interfere with the transmission. 3.1.
LECTUS select 3.2 Installation | en 17 Installing data and supply lines When supplying the reader (especially over longer distances), ensure that the cable crosssection is adequate. Since the power consumption of the individual systems is partially pulsed, short-term voltage drops cannot be detected with a conventional multimeter (digital or analog). However, these voltage drops can cause a "POWER-ON-RESET" on the reader component, which can lead to communication problems.
en | Installation 3.3 LECTUS select Assembly preparation 1. Lay the connection cables according to the local conditions and prepare them for connection. 2. Remove the 8-pin screw / plug-in terminal from the reader module and connect the wires according to this graphic: 1 2 3 4 5 6 7 8 Notice! i The wiring must be carried out in a de-energized state.
LECTUS select 3.4 Installation | en 19 Assembling the reader Flush-mount version 1. Use the provided screws to screw the wall bracket onto a DIN device socket with a device screw distance of 60 mm. 2. Support the reader's tear detection by fixing the perforated tear-off tab with an additional locking screw. Bosch Security Systems B.V. Installation manual 2021-01 | 01 | F.01U.389.
en | Installation LECTUS select Surface-mount version 1. Screw the wall-mount frame to the wall using the screws. The connection cable can be inserted from above, below or directly from the wall. 2. Tear detection is supported by fixing the upper left screw. 2021-01 | 01 | F.01U.389.837 Installation manual Bosch Security Systems B.V.
LECTUS select Installation | en 3.5 Assembling the reader module 3.5.1 Configuring the reader (DIP switches) 21 Depending on the firmware function, the DIP switches of the reader module must be set accordingly. The reader has 6 DIP switches. Each switch is numbered from 1 to 6. With the DIP switches it possible to: – Set the address of the reader – Set the BUS termination – Set baud rate for phg_crypt protocol To change the reader configuration: 1. Power-off the reader. 2.
en | Installation LECTUS select Phg_crypt protocol Address 1 2 3 4 5 6 7 8 S1 ON - ON - ON - ON - S2 - ON ON - - ON ON - S3 - - - ON ON ON ON - S4 - - - - - - - ON S5 Adjustment of the baud rate: ON: 19200, OFF 9600 S6 Bus terminator resistor (default - OFF) Notice! i 3.5.2 For the phg_crypt protocol, address 0 is also valid (switches S1 to S4 set to OFF). Connecting and mounting the reader module 1.
LECTUS select 3.5.3 Installation | en 23 Unmounting the reader module 1. Unlock the locking bar. To do this, use the screwdriver with the blade max. 4 mm wide into the unlocking openings and press until the lock releases. 2. Pull out the unlocked locking bar and remove it from the reader module. 3. Push the reader module upwards to release it and lift it off forwards. 1 2 Notice! i 3.5.4 Any changes that are done to the DIP-switches while the power is on are not considered.
4 en | Care instructions LECTUS select Care instructions 1. Do not operate the reader with sharp objects (rings, fingernails, keys ... etc.) 2. For cleaning, do not use any corrosive or plastic-corrosive liquids such as gasoline, turpentine, nitrous solution, etc. Harsh detergents can damage or discolor the surface. 3. Do not use cleaning agents with mechanical effects such as scouring milk, scouring sponge, etc. 4. Only clean the reader with a soft, damp cloth and only use clear water.
LECTUS select 5 Technical specifications | en 25 Technical specifications Mechanical Dimensions (H × W × D mm) 88 × 101 × 35 mm (uninstalled) 88 × 101 × 21 mm (installed) Dimensions (H × W × D in) 3.5 × 4.0 × 1.4 in (uninstalled) 3.5 × 4.0 × 0.83 in (installed) Color white/silver | black/silver Material plastic Mounting type flush-mounted Weight (g) 137 g | 139 g Weight (lb) 0.302 lb | 0.
en | Technical specifications LECTUS select Connectivity Reader interfaces RS485 Protocol OSDP phg_crypt 2021-01 | 01 | F.01U.389.837 Installation manual Bosch Security Systems B.V.
LECTUS select 6 Certifications and approvals | en 27 Certifications and approvals Region Regulatory compliance/quality marks Europe CE Global RoHS USA FCC Countries of Eurasian EAC Customs Union Bosch Security Systems B.V. Installation manual 2021-01 | 01 | F.01U.389.
7 en | More information LECTUS select More information Visit the Bosch online product catalog for the latest technical documentation for this product. Manufacturing dates For product manufacturing dates, go to www.boschsecurity.com/datecodes/ and refer to the serial number on the product label. Support Access our support services at www.boschsecurity.com/xc/en/support/.
LECTUS select Bosch Security Systems B.V. More information | Installation manual 29 2021-01 | 01 | F.01U.389.
| More information 2021-01 | 01 | F.01U.389.837 LECTUS select Installation manual Bosch Security Systems B.V.
Bosch Security Systems B.V. Torenallee 49 5617 BA Eindhoven Netherlands www.boschsecurity.com © Bosch Security Systems B.V., 2022 Building solutions for a better life.