User's Manual

Installation Instructions
DataSource915-PIT
Blue Tower Communications Inc
www.bluetowercomms.com
US Office - 201 Shannon Oaks Circle, Suite 200, Cary, NC 27511 Tel +1 919-654-7352
© 2009 Blue Tower Communications Inc. The information contained herein is the property of Blue Tower Communications Inc and is supplied without liability for errors or omissions. No part may be
reproduced or used except as authorized by contract or other written permission. All other company names, brand names, and product names are the property of their respective holder(s).
P/N 72006001 IM Rev 0A Page 1 of 2
Description
DataSource915-PIT is for PIT INSTALLATIONS ONLY. It attaches to the
following water meter registers:
Single pulse,
Master Meter Dual-Pulse,
Electronic encoded AMCO Scancoder,
Electronic encoded (ECR),
Electronic encoded Neptune / Schlumberger ARB V,
Electronic encoded ProRead/AutoDetect/E-Coder
TM
registers.*
*With E-Coder registers DataSource915-PIT will read register ID and
reading only.
DataSource915-PIT sends meter data via radio frequency (RF) signal to a
receiving unit; HandTrackIT
®
, FastTrackIT
®
or CellTrackIT
®
.
Required Tools & Equipment
The following items are recommended for proper DataSource915-PIT
installation:
3M
®
Type UY2 gel-filled splice connectors and crimping pliers.
Suitable water resistant PU or Acrylic Potting Compound.
Computer running Windows XP
®
, 2000
®
, 98
®
or NT
®
.
ConFigIT
®
device (Mod Strike 14 or higher) and ConFigIT
software version 6.5.07 or higher.
ConFigIT cable, part number 330-190-10 (Lemo) or 320-300-10
(9-pin Dtype).
4 AA batteries or power cable.
HandTrackIT, FastTrackIT, or CellTrackIT receiver with
connecting cable.
Mounting Instructions
Mount DataSource915-PIT upright facing the direction of the receiver.
Avoid placing DataSource915-PIT on any metal walls or large metal
objects. Do not place DataSource915-PIT closer than 3 inches to metal pit
or vault lids.
Configuration & Installation Procedure
1. Connect DataSource915-PIT to the meter register using 3M Type
UY2 gel-filled splice connectors and gel cap crimping pliers.
2. If the default settings (see ‘Factory Default Settings’ section) are
suitable for the installation then:
DataSource915-PIT can be activated without ConFigIT by using
a small bar or horseshoe magnet. Ensure that the magnet is
held vertically over the center of DataSource915-PIT just below
the stripe.
3. If the default settings need to be changed, use the ConFigIT device
and software:
After performing as READ, select the register required from the
pull down list.
To use DataSource915-PIT with ProRead, AutoDetect or E-
Coder register, set meter interface mode to ‘AutoDetect’.
To use ID printed on the side of DataSource915-PIT case,
select ‘Use current ID’ button.
To enter new ID, select ‘Programmed by User’ button and enter
ID in the cell below button.
Set leak detection threshold to required value.
Turn on DataSource915-PIT by setting Transmit Interval
(default setting is every 5 seconds) to 5 or 10 secs for
FastTrackIt, 10 secs or greater for HandTrackIt. The transmit
interval for CellTrackIt operation depends on the required
sample rate.
4. Apply potting compound to the MIF wire cavity and ensure that the
Gel Caps are completely covered.
5. Ensure that the MIF wire terminations at the meter are waterproofed
in accordance with the Meter manufactures installation procedures.
6. Mount DataSource915-PIT as described in “Mounting Instructions”
section above.
7. Verify that the signal is received with the appropriate receiving
device from the desired location.
8. Verify that the reading corresponds to the visual indication on the
meter register.
NOTE: Max reading (pulse) = 16,777,215
Max reading (encoder) = 9,999,999 - left most digits are dropped.
9. If appropriate check that encoder status is reported as 0. Encoder
error codes are shown in the Encoder Status table below.
Error Codes
Tamper
Single pulse mode allows tamper readings of 1 through 63 which
indicates a count of the tamper wire disconnections. The value should be
recorded at the time of connection and any subsequent increments should
be investigated.
Dual-Pulse mode does not allow tamper detection because all wires are
used to count pulses.
Encoder Status
The encoders will display the following codes:
Error Code
Description
64 No communication from register
65 Open wheel in register
66 Shorted wheel in register
68 Undefined data error from register
Leak
Error Code
Description
128 Leak Flag
Wire Connections
1 2 3
1 2 3
Single Pulse Meters
Manufacturer
Model
Wire 1
Pulse
Wire 2
Ground
Wire 3
Tamper
AMCO/ ABB
PSM-T Green Blue Blue
AMCO/ ABB
Pulsar Red Black Black
Master Meter
Single-Pulser Black Green Green
Badger
®
RTR 3-wire Green Red Black
Badger
DSI-IL & RTR 2-wire
Red Black Black
Metron-
Farnier Spectrum Red Green Green