Installation & Operation Instructions

WIRELESS POWER PACK
LOAD CONTROLLER
INSTALLATION & OPERATION INSTRUCTIONS
CATALOG NUMBERS DESCRIPTIONS
SWX-950
POWER PACK LOAD CONTROLLER
SWX-950-D2
POWER PACK LOAD CONTROLLER W/ 0-10V
DIMMING
SWX-950-AX
POWER PACK LOAD CONTROLLER W/ AUXILIARY
LOW VOLTAGE CONTROL
SWX-950-AX-D2
POWER PACK LOAD CONTROLLER W/ 0-10V
DIMMING & AUXILIARY LOW VOLTAGE CONTROL
SWX-999
LOW VOLTAGE WIRING CHAMBER
SPECIFICATIONS
ELECTRICAL
OPERATING VOLTAGE
120/277 VAC,
Single Phase, 50/60 Hz
CLASS 2 OUTPUT RATINGS
18 VDC, 150 mA (-AX version)
RELAY CURRENT REQS
55 mA
LOAD RATINGS
20A @ 120 VAC -
General Purpose Plug Load
20A @ 120/277 VAC -
General Purpose, Tungsten, Magnetic
Ballast
16A @ 120/277 VAC -
Electronic Ballast, LED Driver
DC LOAD RATINGS
20A @ 28 VDC (MAX)
1A @ 5 VDC (MIN)
DIMMING LOAD
(Models with -D2 option only)
50mA, (0-10 VDC ballasts or drivers
compliant with IEC 60929 Annex E.2)
MOTOR LOAD
1 HP
ESD IMMUNITY
Tested to withstand electrostatic
discharge without damage or memory
loss
ENVIRONMENTAL
OPERATING TEMP
32°F to 122°F (0°C to 50°C)
RELATIVE HUMIDITY
0-95% Non-Condensing
Indoor Use Only
WIRELESS
RANGE
80’ line of site w/o obstruction
40’ with obstruction (walls/oors)
FREQUENCY
915 MHz ISM Band
WIRELESS LINKING
Simple 3 sec. Push Button Process
SECURITY
All Wireless Data is Encrypted
PHYSICAL
SIZE
3.00” H x 2.25” W x 1.88” D
(7.62 cm x 5.72 cm x 4.78 cm)
WEIGHT
6.00 oz.
COLOR
Blue
MOUNTING
1/2” Knockout
RELAY TEST BUTTON
LED STATUS INDICATOR
Bi-color White & Blue
OPERATION
OPERATING MODES
Occupancy & Vacancy
Partial On/Off (-D option)
TIME DELAY OPTIONS
1, 5, 10, 15, 20, 30 min.
CODE COMPLIANCE
These power packs can be used to
meet ASHRAE 90.1, IECC, & Title 24
energy code requirements
FEATURES
à Wirelessly Links to Sensors & Wall
Stations
à Pairs in Seconds up to 50 Remote
Devices
à Switches Up to 20A Line Voltage
Loads
à Electronically Timed Switching
Ensures Long Relay Life
à Integrated Test/Programming Button
à Configurable Time Delays and
Operational Modes (e.g. Occupancy/
Vacancy)
à Optional 0-10V Dimming Output for
Partial On & Partial Off Operation
à Optional Low Voltage Sensor & Wall
Station Wired Connectivity
à Plenum Rated (UL 2043)
OVERVIEW
SENSORWORX wireless power pack controllers switch on/off power to a connected lighting
load as directed by wirelessly linked sensors and wall controls. Additionally, the unit’s
0-10V dimming option enables dimming control. This wireless power pack also has optional
auxiliary low voltage connections for achieving hybrid wired/wireless architectures.
The SENSORWORX wireless power pack is rated to switch fully loaded circuits and utilizes
a powerful microprocessor to optimize its switching timing, ensuring long relay life even
when controlling high-inrush LED lighting. As with all SENSORWORX products, these power
packs are easy to install and incorporate features which reduce contractor labor time. An
elongated chase nipple with snaps for quick installation and an optional snap-on low voltage
wire chamber make for a hassle free contractor experience. All SENSORWORX products are
proudly made in the USA.
BASIC OPERATION
A received wireless message indicating occupancy from one or more wirelessly linked
sensors will trigger the pack’s integrated relay to close. When congured for Vacancy
operation, an ON switch message is required from a wirelessly linked wall station to initially
trigger lights. Once closed, line voltage will ow through the relay and turn on the connected
lighting load. The wireless power pack maintains a master time delay that is reset every
time a linked sensor reports occupancy. Lights will be switched off once there hasn’t been an
occupancy message reported for the duration of the time delay.

Summary of content (8 pages)