Install Instructions

DESCRIPTION
Circuit Setter Balance Valves are precision engineered valves
which function as precise system balance valves and highly
accurate variable orifice flow meters. Circuit Setter Balance
Valves are equipped with an easy to operate memory stop
feature. NPT and Sweat models are also equipped with a
drain port feature.
INSTALLATION INSTRUCTIONS
NPT and sweat style Circuit Setter Balance Valves are
equipped w
ith a 1/4" NPT plugged drain port. If the drain port
is to be used to drain a riser on the downstream side of a ter-
minal unit, it should be situated on the terminal unit side of
the riser when installing the Circuit Setter.
FOR INSTALLING SWEAT CONNECTION:
a) Clean tube ends and valve connections thoroughly per
good piping practices with a fine grade emery cloth or fine
grit sandpaper.
b) For soldering, use 95-5 (Tin-Antimony) s
older and a good
grade of flux.
c) Use a torch with a sharp pointed flame.
d) When sweating the joints, first adjusting the valve in the full
open position, then wrap the valve with a cool wet rag and
then direct the flame with care to avoid subjecting the valve
to excessive heat. Allow the valve to cool before touching
or operating.
SAFETY
INSTRUCTION
This safety alert symbol will be used in this manual to draw
attention to safety related instructions. When used, the safety
alert symbol means ATTENTION! BECOME ALERT! YOUR
SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE IN-
STRUCTIONS MAY RESULT IN A SAFETY HAZARD.
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
NOTE: Bell & Gossett does not
recommend Circuit Setter Plus
®
components to be used for potable water.
Maximum Maximum
Type
Limitations Limitations
Solder
1
/2" - 1"1
1
/4" - 2
1
/2"
Pressure Temp Pressure Temp
psi (kPa) °F (°C) psi (kPa) °F (°C)
95-5 300 (2069) 200 (93) 300 (2069) 175 (79)
TIN- 250 (1724) 225 (107) 250 (1724) 200 (93)
ANTIMONY 200 (1379) 250 (121) 175 (1207) 250 (121)
Circuit Setter Plus
®
Model MC
OPERATIONAL LIMITS
WORKING PRESSURE & TEMPERATURE LIMITS
(SOLDER TYPE LIMITS FOR ANSI STD. B16.18)
WARNING: Damage to the Circuit Setter or failure
of solder sealing joints may occur if these opera-
tional limits are exceeded. This can result in water leak-
age. Failure to follow this instruction can cause serious
personal injury and/or property damage.
1
/2 1SEZISTPN& TAEWS "1 OT "
1
/4" TO 2
1
/2" SWEAT & NPT SIZES
INSTRUCTION MANUAL
V58045B

Summary of content (4 pages)