TD 93021US Installation Guide teleCARE IP Emergency Call System 17 July 2017 / Ver.
Installation Guide teleCARE IP Copyright TD 93021US © 2017 Ascom (US), Inc. This document may not be copied in whole or in part or otherwise reproduced without prior written consent from Ascom, except where specifically permitted under US and international copyright law. Disclaimer The information in this document is subject to change. Use this product only in accordance with the instructions provided in the installation and user guide manuals.
Installation Guide teleCARE IP Regulatory Compliance (US/CAN) Copyright TD 93021US Safety Compliance: The equipment described herein complies with: ANSI/UL 2560 Emergency Call Systems for Assisted Living and Independent Living Facilities CAN/CSA C22.2 No. 205 Signal Equipment Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.
Installation Guide teleCARE IP TD 93021US Contents 1 Introduction ..................................................................................................................................1 1.1 General ..................................................................................................................................1 1.2 Installation and Commissioning ...............................................................................................1 1.3 teleCARE IP With Speech ........
Installation Guide teleCARE IP TD 93021US 6.11 Toilet Cancel Module - Passive (NITC-XXP) ...........................................................................82 6.12 Pull Cord Module (NIPC2) Active and Passive .......................................................................83 6.13 Duty Selector (NIDS) ............................................................................................................94 6.14 Card Reader (NICR) ...........................................................
Installation Guide teleCARE IP 1 TD 93021US Introduction The installation guide covers the mechanical and electrical installation of the teleCARE IP Emergency Call System. The teleCARE IP “System Description” (TD 92608GB) should be read before reading this manual to gain a general understanding of the teleCARE IP system. Throughout this document there are “cross-references” in the text which indicate that further details can be found in another section of this document.
Installation Guide teleCARE IP 1.3 TD 93021US WARNING: teleCARE IP components, including all handsets, are not intended for use in oxygen enriched environments. WARNING: teleCARE IP components, including all handsets, are not intended for use in rooms where flammable (anesthetic) gases are used.
Installation Guide teleCARE IP TD 93021US 1.3.4 Innovaphone VoIP Gateway The teleCARE IP system uses the supplementary Innovaphone VoIP gateway to support VoIP speech functionality. The Innovaphone VoIP gateway is an IP based gateway providing the VoIP based solution which supports all the features of a traditional PBX. For the teleCARE IP VoIP the SIP Trunk must be used for the interface to the main PBX. The SIP trunk must be set to “Early offer”.
Installation Guide teleCARE IP 2 TD 93021US Practical Engineering Parameters In order to ensure the optimal performance of a teleCARE IP system it is important to consider certain parameters and limitations. The following tables show the most important practical values which can have an influence on the teleCARE IP system performance. WARNING: 2.1 Any deviation from the values and recommendations shown in the following tables can significantly reduce the performance of the teleCARE IP system.
Installation Guide teleCARE IP 2.3 TD 93021US VoIP Requirements (Supplementary) VoIP Considerations The Innovaphone VoIP gateway version 10 (or later) is required for teleCARE IP with speech, as the interface to the PBX. An interoperability test between the VoIP gateway and main PBX must be performed. The connection between the PBX and the Innovaphone can be PRI or SIP Trunk teleCARE IP only supports CODEC G.
Installation Guide teleCARE IP 3 TD 93021US System LAN Cabling 3.1 Ethernet Switch The 8-port Ethernet Switch, Ascom part number APS5001, shall be used with the teleCARE IP system and can be purchased through Ascom. WARNING: Use of any Ethernet Switch other than Ascom part number APS5001 violates the UL 2560 listing. 3.1.1 Ethernet Switch DIN Rail Mounting The Ethernet Switch shall be mounted on a 1.5in (35mm) DIN-rail, which can be mounted on a wall.
Installation Guide teleCARE IP TD 93021US 3.1.5 Ethernet Switch Operation When properly installed and operating, LED indicators on the Ethernet Switch will be observed as follows: 3.2 PWR (green) Illuminates steady when proper power is supplied to the Ethernet Switch. LINK (green) Each port has a LINK LED which indicates that a valid Ethernet link has been established. The LED flashes when data transfer is occurring.
Installation Guide teleCARE IP TD 93021US 3.2.1 Ethernet LAN Cable The cable required for the Ethernet LAN must comply with the specification TIA/IEA 568-A Category 5 or higher. This is a standard 4 x unshielded twisted pair (UTP) solid bare copper with a diameter of 24 AWG (0.5mm). Cable Type Wire Size Diameter / AWG TIA/IEA 568-A, Category 5 or higher (4 x UTP) 24 AWG (0.5mm) Max. Cable Length 328ft (100m) Table 1.
Installation Guide teleCARE IP TD 93021US When UTP category 5 cable (or higher) is used the length of any room bus cable should not exceed 98.4ft (30m), irrespective of the load. Below 98.4ft (30m), the maximum acceptable length of the room bus cable depends on the load. 17 July 2017 / Ver.
Installation Guide teleCARE IP 4 TD 93021US System Power The teleCARE IP system power supply shall be sourced from an external 24Vdc power supply, utilizing a dedicated 2-wire power distribution bus. The external power requirement for teleCARE IP is 24Vdc, with an acceptable range of 21.6Vdc to 26.4Vdc. WARNING: 4.1 Use of any Power Supply other than those which are specified in this manual violates the UL 2560 listing.
Installation Guide teleCARE IP TD 93021US WARNING: • Batteries must be secured within the HPFF8 cabinet enclosure. • Batteries must be lead acid and must comply with UL 2054. (See Section 4.3 Secondary Power.) • Before applying power, inspect the Power Supply Board (Figure 1 in the Power Supply Installation Guide) to ensure that SW1 is set to the Open position, to configure the unit for 24Vdc operation.
Installation Guide teleCARE IP TD 93021US Note: • The maximum charging current under discharge is 0.7 amperes. • Expected battery life is 5 years. However, it is recommended to change the batteries in 4 years, or less if needed. Red (DC) Green (AC) Power Supply Status ON ON Normal operating condition. ON OFF Loss of AC, Stand-by battery supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output. Table 3.
Installation Guide teleCARE IP TD 93021US • Make certain that the AC circuit breaker is off before making any wiring connections between the circuit breaker and the power supply. • Always de-energize the power supply prior to servicing. • When servicing, the AC mains circuit breaker should be in the off position and locked out to prevent accidental activation. • This power supply is intended for indoor use only. Do not expose the unit to rain or moisture.
Installation Guide teleCARE IP TD 93021US Caution: Connect the negative (-) lead of the teleCARE IP System to the 4L1 terminal and the positive (+) lead to the 4L2 terminal. Re-energize the power supply. 4.2.2 Power Supply (Seismic) Operation and Maintenance The HPFF8 Power Supply should be tested at least once a year for proper operation. Under normal load conditions, the DC output voltage should be checked for proper voltage level, which is 24Vdc for the teleCARE IP system.
Installation Guide teleCARE IP TD 93021US LED Label Condition Power On 1 PWR ON 2 AUX TRBL Note 1 Loss or Brownout Normal Excessive load or short Normal BAT TRBL Note 2 3 Charger Fault No battery or <20.
Installation Guide teleCARE IP 6 4.3 TD 93021US To restore a SIG4 – SIG1 blinking LED to normal, press SW2 on the Control Circuit Board or, power cycle the HPFF8 OFF/ON. Secondary Power Secondary Power for the teleCARE IP system shall be provided by two lead acid Batteries installed in the primary power supply. The batteries are each rated for 12Vdc, 7 ampere hours (AH) and can be purchased through an electrical supplier such as Graybar.
Installation Guide teleCARE IP 4.5 TD 93021US Power Supply Unit (24Vdc) with Multiple Power Buses The output of the power supply unit can be divided over multiple buses. This method is recommended as it will reduce the power cable lengths. Figure 6. Multiple power buses 4.5.1 Power Supply Basic Installation The 24Vdc power is carried on a two-wire bus that loops from room controller to room controller. The minimum wire size for the 24Vdc power supply bus is 18 AWG (1mm). Figure 7.
Installation Guide teleCARE IP TD 93021US 4.5.2 Power Supply for Systems with Slave Corridor Lamps Each slave corridor lamp receives its power supply (5.5Vdc) directly from the room bus. The room controller can support four corridor lamps. Figure 8. Power supply (24Vdc) for room controllers with room bus powered (5.5Vdc) corridor lamps 4.
Installation Guide teleCARE IP 5 TD 93021US Control Equipment This section describes the installation instructions for the following products: • “Room Controller (NIRC3)” (details on page 19) • “Blank Front Cover for the Room Controller” (details on page 21) • “Voice Piggy Back (NIVP)” (details on page 29) • “Corridor Lamp (NICL2)” (details on page 43) • “System Manager (NISM2)” (details on page 51) 5.
Installation Guide teleCARE IP TD 93021US The Room Controller (NIRC3) has been tested and found to comply with the emission levels for a Class B device as described in EN55022:2010. The input power for the NIRC3 shall be supplied over an external 24Vdc power supply bus,. The external power supply input requirement is 24Vdc ± 10%. The power input has an on-board, self-resetting fuse. The NIRC3 has four room buses. Each room bus has four wires, consisting of: data, voice, power (5.5V DC) and ground (0V).
Installation Guide teleCARE IP TD 93021US 5.2.2 NIRC3 Parts The NIRC3 includes a housing, a translucent dome cover, and a printed circuit board which has four connectors for LED boards. The LED board (must be ordered separately) is available in five colors: red, green, yellow, white, and blue. The LEDs are used for the signaling of calls, staff presence, and faults. Figure 12. Room controller (NIRC3) parts 5.2.
Installation Guide teleCARE IP TD 93021US 5.2.4 Installing the Room Controller When installing the Room Controller the first step is to separate the top section (cover, PC board, and lamp dome) from the housing. To do that simply grip the top edge of the cover and pull it away from the housing, as shown in the following illustration: Figure 14. Separating the top section from the housing 5.2.
Installation Guide teleCARE IP TD 93021US 5.2.6 Room Controller Housing The room controller housing is designed to be surface mounted. It can be mounted over a back box or fixed directly on to a wall surface. The same housing is used for the IP room controller with LED lamps and with blank cover and for the corridor lamp. Figure 16. Room controller housing 5.2.7 Mounting the Housing over a Back Box Place the housing over the back box so that the long sides are at the top and bottom.
Installation Guide teleCARE IP TD 93021US Make sure the long sides are horizontal, then tighten the back box fixing screws to secure the housing. Figure 18. Fixing the housing 5.2.8 Mounting the Housing without a Back box The housing can be mounted on a flat surface, without a back box, using four suitable screws in the outer fixing holes, as shown in the illustration below.
Installation Guide teleCARE IP 5.3 TD 93021US Preparing the Room Bus and Power Cables It is important to prepare the cables appropriately and to guide the wires correctly inside the housing in order to avoid the wires pressing on the printed circuit board which could result in damage and also prevent the top section from closing properly. The following instructions apply to the room bus cables, the power supply cable, and the corridor lamp cables. 5.3.
Installation Guide teleCARE IP TD 93021US 5.3.2 Room Controller (NIRC3) Connections The electrical connections on the component side of the room controller printed circuit board are shown in the following drawing of the NIRC3 circuit board. LED Lamp Board Through-Board Connectors Transceiver piggyback (NIRX) extension connectors Room bus 0 2 x USB 2.
Installation Guide teleCARE IP TD 93021US 5.3.3 Room Controller (NIRC3) Printed Circuit Board Back View Through-Board Connection Holes for the LED Lamp NIRC3 MAC address label Product label with part number and serial number Figure 22. NIRC3 printed circuit board back view On the back of the NIRC3 printed circuit board there are four sets of through-board connection holes for LED lamp boards. Details of for connecting the LED lamp boards are given in section 5.7, LED Lamp Boards (NILD2), page 38. 5.3.
Installation Guide teleCARE IP TD 93021US The multi color status LED on the NIRC3 will indicate the following: NIRC3 - Status color Status Steady blue Normal operation Steady orange Starting-up Fast blue flashing Application start-up Steady orange Image installation mode Remarks for about 22 seconds after power on or reboot.
Installation Guide teleCARE IP 5.4 TD 93021US Voice Piggy Back (NIVP) The teleCARE IP Voice Piggy Back module (NIVP) is a printed circuit module which is piggy back mounted on the teleCARE IP Room Controller 3 (NIRC3). Figure 25. Voice Piggy Back - NIVP The NIVP has four half duplex speech channels allowing four speech sessions at the same time, one speech session for each room bus. Each speech channel has an LED indicator which illuminates when a speech session is in progress.
Installation Guide teleCARE IP TD 93021US The following illustration shows the NIVP voice piggy back module mounted on the NIRC3: NIVP Figure 27. Voice piggy back module mounted on the NIRC3 17 July 2017 / Ver.
Installation Guide teleCARE IP 5.5 TD 93021US Connection Terminals The 4-pole and the 2-pole connector terminals required for the room bus and the 24Vdc power supply are not supplied with the IP room controller. The connectors are available as accessories and must be ordered separately. 5.5.1 4-Pole Connector Terminal (NICT-4AA) Figure 28. 4-pole connector terminal The 4-pole connector terminal is used for connecting the room bus.
Installation Guide teleCARE IP TD 93021US Figure 31. Inserting a wire in the connection point Check that a good connection has been made by gently pulling on the wire after it has been inserted. The wire should stay fixed in the terminal. Four wires are required for the room bus, passive bus, and light relay outputs, so repeat the above illustrated procedure on the remaining three wires. Figure 32.
Installation Guide teleCARE IP TD 93021US 5.5.2 2-Pole Connector Terminal (NICT-2BA) Figure 34. 2-pole connector terminal The 2-pole connector terminal is used for connecting the 24Vdc power supply when a separate power supply is used. It is also used for the 24Vdc power supply from the room controller to the corridor lamp. The 2-pole terminal connector has two screw terminals. Each terminal accepts one wire (up to wire size 15 AWG (1.4mm) or two wires (each up to 18 AWG (1mm).
Installation Guide teleCARE IP TD 93021US Max. 2 x 18 AWG (1mm) Figure 37. Connector terminal with looped wiring Note: The maximum size of each wire when two wires are inserted in one screw terminal of the 2-pole connector terminal is 18 AWG (1mm). 17 July 2017 / Ver.
Installation Guide teleCARE IP 5.6 TD 93021US Connecting the IP Room Controller Printed Circuit Board When preparing the wiring for connecting the printed circuit board of the IP room controller make sure that the power supply wires and the room bus wires are stripped of the cable outer jacket and that the wires are long enough, as described in section 5.3, Preparing the Room Bus and Power Cables on page 25. It is best to arrange the wires and cables neatly and securely inside the housing.
Installation Guide teleCARE IP TD 93021US Use the Wire Holding Clip Figure 39. Connecting a room bus to the NIRC3 5.6.3 Connecting Multiple Room Buses The IP room controller supports four room buses and each has a 4-pole connection terminal which is wired as described in section 5.5.1 on page 31. The connection points on the room controller PCB for the room buses are shown in section 5.3.2 on page 26. Use the Wire Holding Clips Figure 40. Connecting multiple room buses to the NIRC3 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US 5.6.4 Connecting LAN Cable The LAN cable has an RJ45 plug which connects to the socket on the room controller printed circuit board shown in section 5.3.2 on page 26. The LAN cable should not be guided through the wiring clips inside the room controller housing. It should be plugged directly into the RJ45 connector on the printed circuit board with enough cable to avoid straining the LAN connection.
Installation Guide teleCARE IP 5.7 TD 93021US LED Lamp Boards (NILD2) The LED lamp board contains four high intensity LED lamps which are used in the corridor lamp of the room controller and corridor lamp. The three pins in the back side of the board are used to connect the LED lamp board through holes in the back side of the room controller or corridor lamp printed circuit board. The room controller and the corridor lamp each accept up to four LED lamp boards. Figure 43.
Installation Guide teleCARE IP TD 93021US 5.7.1 Auxiliary Lamp Connection - NILD2 The green LED board (NILD2-GAA) has a galvanically isolated relay contact that can be used to connect to an auxiliary lamp. It has a maximum switching capacity of 0.4A at 60V peak. NILD2 To auxiliary power supply Max. 0.4A at 60V peak Figure 45.
Installation Guide teleCARE IP TD 93021US 5.7.2 Connecting the Wires to the NILD2-GAA The 2-pole connector terminal on the green LED lamp board (NILD2-GAA) has two terminals with one connection point at each terminal. A connection point accepts one solid wire of maximum wire size of 24 AWG (0.5mm). To connect the wires first strip 1/4 in. (6mm) of the insulation from the end of each wire which is to be connected.
Installation Guide teleCARE IP TD 93021US 5.7.3 Installing the LED Lamp Boards on the IP Room Controller Board On the back side of the IP room controller PCB there are the four sets of through-board connections for the LED lamp boards. Each through-board connector has three holes which accept the three connecting pins on the LED lamp board. Through-Board Connection Holes for the LED Lamp Boards LED Lamp Board Guide Marks Figure 48.
Installation Guide teleCARE IP TD 93021US With the three pins inserted and the LED lamp board lined up with the guide marks, firmly press the LED lamp board into the IP room controller PCB. Repeat the procedure on the other required LED lamp boards. Figure 50. NIRC3- room controller PCB with 4 LED lamp boards Caution: The maximum load on each external LED circuit is 60mA. 5.7.
Installation Guide teleCARE IP 5.8 TD 93021US Corridor Lamp (NICL2) The room controller (NIRC3) can support four corridor lamps. Each Corridor Lamp is connected to one of the room buses of the Room Controller and it always has the fixed address 5. Figure 52. The teleCARE IP corridor lamp The Corridor Lamp consists of a back box, a printed circuit module, a cover plate, and translucent dome cover that can accept up to four LED boards, as shown in the following illustration: Figure 53.
Installation Guide teleCARE IP TD 93021US 5.8.1 Installing the Corridor Lamp When installing the Corridor Lamp the first step is to separate the top section (cover, PC board, and lamp dome) from the housing. To do that simply grip the top edge of the cover and pull it away from the housing, as shown in the following illustration: Figure 54. Separating the top section from the housing 5.8.
Installation Guide teleCARE IP TD 93021US With the printed circuit board released from the holding clip, partly rotate the circuit board and remove it from the housing. 5.8.3 Corridor Lamp Housing The corridor lamp has the same housing as used for the IP room controller which is designed to be surface mounted. Refer to section 5.2.6, Room Controller Housing on page 23 for details of mounting the housing. Figure 56. IP room controller housing 5.8.
Installation Guide teleCARE IP TD 93021US 5.8.5 4-Pole Connector Terminal Figure 58. 4-pole connector terminal The 4-pole connector terminal is used for connecting the room bus. It has a screw-less “spring-cage” connection technique and each terminal has two connection points. The designation of the required four wires is as shown in the following illustration. 5.5 Vdc DATA VOICE GND Figure 59.
Installation Guide teleCARE IP TD 93021US 5.8.7 LED Lamp Boards for the Corridor Lamp Note: The LED lamp boards are not delivered as part of the corridor lamp and therefore, must be ordered separately. The LED lamp board contains four high intensity LED lamps which are used for the signaling of various types of calls including staff presence, and system faults.
Installation Guide teleCARE IP TD 93021US 5.8.8 Connecting the LED Lamp Boards To connect the LED lamp board, insert the three pins of the LED lamp board into the appropriate three holes in the back side of the corridor lamp PCB. Insert the Pins of the LED Lamp Board in the Holes in the corridor lamp PCB Align the LED Lamp Board with the Guide Marks on the corridor lamp PCB Figure 62.
Installation Guide teleCARE IP TD 93021US 5.8.9 External Corridor Lamp Inputs The NICL2 corridor lamp can be used as a passive external LED corridor lamp (not connected to a room bus). It has a 6-pole input/output connector which can accept inputs from an external source (such as an NIRC3 room controller). Cut Conductor “S1” Figure 64.
Installation Guide teleCARE IP TD 93021US Restoring the Room Bus Section on the NICL2 To restore the NICL2 to the default configuration when the conductor “S1” has been cut, put a drop of solder on the gold plated contacts of “S1” using a soldering iron. Figure 66. Restoring to the default NICL2 configuration 17 July 2017 / Ver.
Installation Guide teleCARE IP 5.9 TD 93021US System Manager (NISM2) The teleCARE IP System Manager (NISM2) is an Ascom ELISE3 application. The ELISE3 module serves as the interface to a 100base-T Ethernet LAN and it contains a Linux based web server. The NISM2 is the management tool for centrally managing the teleCARE IP system. It is used to setup and maintain the teleCARE IP system and it also includes a staff GUI for creating and maintaining staff assignments.
Installation Guide teleCARE IP TD 93021US 5.9.1 NISM2 Electrical Connections The following illustration shows the appropriate electrical connections for teleCARE IP applications: COM Ports Ethernet LAN External Power Figure 68. NISM electrical connections Note: All other connections are not used in teleCARE IP applications. 5.9.2 Ethernet LAN Cable Connect the Ethernet LAN cable to the “LAN 1” port. 10baseT/100base T Ethernet LAN Connection Figure 69.
Installation Guide teleCARE IP TD 93021US 5.9.3 NISM2 Power Supply Connect the 24V power supply to the NISM2 at the "12-24V 1A” connector, as show in the following illustration: 24Vdc External Power Input Figure 70. Connecting the 24Vdc power supply IMPORTANT: For UL 2560 installations, the NISM2 can only be connected to the systems external 24Vdc power supply (see “System Power” on page 10). Do not connect to mains power! 5.9.
Installation Guide teleCARE IP TD 93021US The “Power supply” setting is located under “Common” on the “Advanced Configuration” page. There are four options available: • Internal PSU only • External PSU only • Internal and external PSU • Internal PSU and external battery Note: For UL 2560 installations, select “External PSU only”. When the correct power supply is set in the NISM Advanced Configuration, the power LED on the front of the NISM2 will show a steady blue indication.
Installation Guide teleCARE IP TD 93021US Figure 74. Paging system selection Select the appropriate paging protocol for the system to be connected (TAP or ESPA) to access the settings. 17 July 2017 / Ver.
Installation Guide teleCARE IP 6 TD 93021US Peripherals The switch modules all have the same basic format and can be mounted as a single unit on a single backplate or as a double unit on a double backplate. The switch modules have one, two or three buttons with LEDs and some switch modules have a buzzer. The functions of the buttons and buzzer are determined by the software when system is configured using the system manager (NISM). 6.
Installation Guide teleCARE IP 6.3 TD 93021US Backplates and Surface Mounting Spacer The teleCARE IP switch modules are designed to be mounted on flat walls using the teleCARE backplate. The backplate is designed to be mounted over flush fitted back boxes and an array of holes in the backplate allows it to be mounted over various international back boxes. As an alternative to the backplate a spacer is available for surface mounting the teleCARE switch modules, with or without a back box.
Installation Guide teleCARE IP TD 93021US Figure 68. Mounting the backplate (or spacer) on the back box The backplate should be placed over the back box with the side marked “TOP” at the top. Tighten the two screws that will hold the backplate in place. Figure 69. Securing the backplate (or spacer) to the back box 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US 6.3.2 Surface Mounting Spacer The surface mounting spacer is available for surface mounting the teleCARE IP switch modules, with or without a back box. The spacer can be mounted directly on to a flat wall surface or on a back box. Figure 70. Surface mounting spacer 6.3.3 Mounting the Spacer on a Back Box To mount the spacer on a back box, first remove the mounting screws from the back box.
Installation Guide teleCARE IP 6.4 TD 93021US Switch Module Electrical Connections It is important to ensure that a minimum of 14in (35cm) of free cable is pulled out of the back box at every location where teleCARE peripherals are to be installed. Figure 72. Connecting the switch module Refer to the relevant switch module description in the following sections for details of the electrical connections. 6.4.1 4-Pole Connector Terminal Figure 73.
Installation Guide teleCARE IP TD 93021US The designation of the passive bus wires is shown in the following illustration. 5.5Vdc IN0 IN1 OUT Figure 75. 4-pole connector terminal with the passive bus The designation of the light switching relay connections is shown in the following illustration. L1} L2} Figure 76. 4-pole connector terminal for the light relay 6.4.
Installation Guide teleCARE IP TD 93021US Figure 78. Inserting a wire in the connection point Check that a good connection has been made by gently pulling on the wire after it has been inserted. The wire should stay fixed in the terminal. Four wires are required for the room bus, passive bus and light relay outputs, so repeat the above illustrated procedure on the remaining three wires. Figure 79. Connector terminal complete with four wires 6.4.
Installation Guide teleCARE IP TD 93021US 6.4.5 Disconnecting a Wire from the Connector Terminal First carefully place the point of a small screw driver (point approximately 0.10in (2.5mm) wide on the relevant orange colored release key of the connection terminals and press the key in firmly to open the spring-cage connector (1). With the release key pressed in pull the wire from the terminal (2) then remove the screw driver. Figure 81. Removing a wire from a connection point 6.4.
Installation Guide teleCARE IP TD 93021US 6.4.7 Mounting the Switch Module to the Surface Mounting Spacer To mount the switch module onto the spacer, place the lower edge of the switch module on the two lower snap fasteners of the spacer (1). Next place the switch module on to the two top fasteners (2) and press the switch module so that it snaps closed on the spacer. Figure 83. Mounting the switch module on the spacer 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US 6.4.8 Dismantling the Switch Modules To separate the switch module from the backplate, a screwdriver with a point of approximately 0.25in (6mm) wide should be used. Figure 84. Suitable screwdriver for dismantling switch modules Insert the point of the screwdriver into the groove at the side of the switch module between the faceplate and the back plate at about 0.4in (10mm) down from one of the top corners. Figure 85.
Installation Guide teleCARE IP TD 93021US 6.4.9 Dismantling a Switch Module from a Spacer Insert the point of the screwdriver into the groove at the side of the switch module between the faceplate and the spacer at about 0.40in (10mm) down from one of the top corners. Figure 87. Inserting the screwdriver Gently push and turn the screwdriver until the switch module releases from the spacer. Figure 88.
Installation Guide teleCARE IP TD 93021US 6.4.10 Dip Switch Settings Each room bus provides eight addresses for the connection of teleCARE IP switch modules. The lower four of these addresses are set by a DIP switch that is located on the PCB of the certain switch module. The upper four addresses cannot be set as they are dedicated to certain switch modules which have the appropriate address permanently set in the switch module.
Installation Guide teleCARE IP 6.5 TD 93021US Bedside Module (NIBM2) The Bedside Module (NIBM2) is designed for use in the teleCARE IP system. It is suitable for use with all teleCARE IP handsets and it supports teleCARE IP speech and entertainment. The NIBM2 has a Safe Release connection socket for the handset and it is available with three or one button. The NIBM2-G3S and NIBM2-W3S have three function buttons: red, green and yellow. The NIBM2-W1S and NIBM2-G1S have one red button. Figure 90.
Installation Guide teleCARE IP TD 93021US 4-Pole Connector for the Room Bus 4-Pole Connector for an External Call Input and Call LED Output Connector for the Speech Module Not supported with UL 2560 systems 4-Pole Connector for the Stereo Input from the Television Interface Dip switch for setting the Room Bus Address 0, 1, 2, or 3 4-Pole Connector for the Light Switching Relays Figure 91.
Installation Guide teleCARE IP TD 93021US 6.5.2 Light Switching Relay Maximum Load and Surge Damping Diode The teleCARE switch module NIBM2 with a socket and bed light control include 2 light switching circuits. Each circuit is suitable for switching a bi-stable 24Vdc relay. The maximum switching current for each relay must not exceed 0.3A at maximum 30Vdc. Figure 92.
Installation Guide teleCARE IP TD 93021US 6.5.3 External Call Contact with Call Lamp Output The external call connection allows an external normally open third-party contact to activate a teleCARE call in parallel to the red button of the bedside module. The 4-pole connector provides SWITCH and GND terminals for connection to a normally open contact of an external switching device. These terminals provide 5.5Vdc at 0.6mA, for monitoring the external device contact. The 4-pole connector also provides a +5.
Installation Guide teleCARE IP 6.6 TD 93021US Medical Rail Socket (NIMS2) The Medical Rail Socket (NIMS2) is a teleCARE IP peripheral. The NIMS2 is designed to be flush mounted by two screws in an opening in a medical rail. The NIMS2 supports teleCARE IP speech and stereo TV audio input from the television interface module. Figure 94. Medical Rail Module NIMS2 (top, front, bottom) The NIMS2 is connected to the teleCARE IP room bus by a 4-pin connector. The room bus connector includes the 5.
Installation Guide teleCARE IP TD 93021US 6.6.1 NIMS2 Electrical Connections and DIP Switch Settings The medical rail socket (NIMS2) is an “active peripheral” which must be connected to one of the four room buses of a teleCARE IP room controller by the 4-pole room bus connector. The room bus connector includes the 5.5Vdc power supply for the NIMS2. Each room bus offers individual addresses for up to four switch modules.
Installation Guide teleCARE IP TD 93021US 6.6.2 NIMS2 Room Bus Address Setting The room bus address of the medical rail socket is selected using the DIP switch on the top side of the printed circuit board. For details of the DIP switch settings see 6.4.10, Dip Switch Settings on page 67. DIP Switch for Room Bus Address Figure 96. NIMS2 DIP switch 6.6.
Installation Guide teleCARE IP TD 93021US 6.6.4 External Call Contact with Call LED Output The external call connection allows an external normally open third-party contact to activate a teleCARE call in parallel to the red button of the bedside module. The 4-pole connector provides SWITCH and GND terminals for connection to a normally open contact of an external switching device. These terminals provide 5.5Vdc at 0.6mA, for monitoring the external device contact. The 4-pole connector also provides a +5.
Installation Guide teleCARE IP TD 93021US 6.6.5 Mounting the Medical Rail Socket The following illustration shows how the medical rail socket is mounted in the underside of a medical rail. Figure 99. Medical rail socket mounting and cut-out dimensions 17 July 2017 / Ver.
Installation Guide teleCARE IP 6.7 TD 93021US Door Side Module (NIDM) The Door Side Module (NIDM) is a three-button switch module which is connected to the teleCARE IP room bus. It has a buzzer which can be used to signal calls, a 4-pole connector for the room bus, a 4-pole connector for a passive bus and connector for speech module. Figure 100. Door-Side module: front and back view 6.7.
Installation Guide teleCARE IP TD 93021US Note: The 4-pole connector terminals required for the room bus and the passive bus connections module must be ordered separately. 6.8 Pull Cord Module - Active (NIPC-W3A) The Pull Cord Module (NIPC) is intended for use in the teleCARE IP system, in areas such as bathrooms and toilets. It is an “active peripheral” therefore it must be connected to one of the four room buses of a teleCARE IP room controller. Figure 102.
Installation Guide teleCARE IP TD 93021US 4-Pole Connector for Room Bus Connector for the Speech Module Not supported with UL 2560 systems Dip Switch for Setting the Room Bus Address 0, 1, 2, or 3 Figure 103. Pull cord module electrical connections and address setting Note: The 4-pole connector terminals required for the room bus connections is not supplied with the switch module. It is available as accessories and must be ordered separately. 6.8.
Installation Guide teleCARE IP 6.9 TD 93021US Toilet Cancel Module - Active (NITC-XXA) Figure 105. Toilet cancel module (active) The Toilet Cancel Module is designed for use in the teleCARE IP system. It is a wall mounted single switch module used to cancel toilet calls made by linked toilet call devices. Each room bus offers individual addresses for up to four switch modules. The address is of the active toilet cancel module is fixed at number 4 and cannot be changed.
Installation Guide teleCARE IP TD 93021US Note: The 4-pole connector terminals required for the room bus and the passive bus must be ordered separately as accessories. 6.10 Pull Cord Module - Passive (NIPC-XXP) Figure 107. Passive pull cord module 3 buttons The Passive Pull Cord Module is intended for use in the teleCARE IP system, in areas such as bath-rooms and toilets. It must be connected to the passive bus of a door side module or active pull cord cancel module.
Installation Guide teleCARE IP TD 93021US 4-Pole Connector for the Passive Bus Figure 108. Passive pull cord module electrical connections 6.11 Toilet Cancel Module - Passive (NITC-XXP) Figure 109. Passive toilet cancel module The Passive Toilet Cancel Module is intended for use in the teleCARE IP system, in areas such as bathrooms and toilets. It must be connected to the passive bus of a door side module or a room display module.
Installation Guide teleCARE IP TD 93021US on page 60). 4-Pole Connector for the Passive Bus Figure 110. Passive toilet cancel module electrical connections Note: The 4-pole connector terminal for the passive bus is not supplied with the switch module. It is available as an accessory and must be ordered separately. 6.12 Pull Cord Module (NIPC2) Active and Passive The NIPC2 Pull Cord Modules are designed for use in the teleCARE IP system.
Installation Guide teleCARE IP TD 93021US The active version of the NIPC2 is connected to one of the room buses of the IP Room Controller. It has a 4-pin connector for the connection of the room bus, consisting of: 5.5Vdc, data, voice and ground (0V). The room bus address is set by DIP switches. The passive version must be connected to the passive bus of a door side module, a room display or a toilet cancel module. It has a 4-pin connector for the connection of the passive bus, consisting of: 5.
Installation Guide teleCARE IP TD 93021US 6.12.1 Mounting the NIPC2 Pull Cord Module In order to avoid physical damage to the module and to reduce the risk of exposure to excessive spray water in shower rooms, bathrooms and similar wet areas, the NIPC2 should be installed with the pull cord module mounted above the height of any water source.
Installation Guide teleCARE IP TD 93021US 6.12.2 Positioning the Back box for the Pull Cord Module The NIPC2 pull cord module must be mounted on a smooth flat surface in order to ensure that it is splash water proof in accordance with IP44. The ideal surface is a ceramic tiled wall with the back box for the NIPC2 situated in the center of a tile so that the pull cord module backplate does not sit over a gap between tiles, as shown in the following illustration: Figure 113.
Installation Guide teleCARE IP TD 93021US 6.12.4 Mounting the NIPC2 Backplate The backplate of the NIPC2 must be mounted over the back box using the holes in the corners of the backplate in order to ensure that the NIPC2 is IP44 splash water proof. 6.12.5 Drilling the Backplate Mounting Holes Four suitably sized holes should be drilled around the back box at 3in (77mm) between the centers (1). A wall plug which will accept a screw of diameter 0.14in (3.5mm) to 0.15in (3.
Installation Guide teleCARE IP TD 93021US The four screws should be tightened carefully so that just enough pressure is applied on the gasket to compress it evenly all around between the backplate and the wall surface. Figure 117. Fixing the backplate to the wall Caution: Do not excessively tighten the fixing screws as this will distort the backplate and the foam gasket resulting in an ineffective waterproof seal. 6.12.
Installation Guide teleCARE IP TD 93021US 6.12.8 Room Bus Electrical Connections The NIPC2 WAA is an active teleCARE IP peripheral which must be connected to the 4-pin room bus connector on the switch module. Refer to section 6.4.2, Preparing the Wires for the 4-pole Connector Terminal on page 61). in order to correctly strip the cable and prepare the wires for the 4-pole connector. The connections of the room bus wires in the 4-pole connector are shown in the following illustration. 5.
Installation Guide teleCARE IP TD 93021US 6.12.10 Passive Pull Cord Module Electrical Connections The NIPC2 WAP is a passive teleCARE IP peripheral which must be connected to the passive bus of a door side module or a toilet cancel module. Refer to section 6.4.2, Preparing the Wires for the 4-pole Connector Terminal on page 61). in order to correctly strip the cable and prepare the wires for the 4-pole connector. The connections of the passive bus wires is shown in the following illustration. 5.
Installation Guide teleCARE IP TD 93021US 6.12.11 Mounting the NIPC2 Pull Cord Module to the Backplate The method described for mounting the switch module to the backplate is basically the same for the active and the passive pull cord switch modules. The following illustration shows the back plate mounted on the back box with the cable pulled through and connected to the 4-pole connection terminal. Figure 123.
Installation Guide teleCARE IP TD 93021US Mount the switch module on the backplate by first position the two latch fasteners of the backplate over the two teeth on the inside of the lower edge of the cover plate (1). Next rotate the pull cord module up to the backplate (2) so that the screws line up with the fixing posts on the back plate. Figure 125.
Installation Guide teleCARE IP TD 93021US 6.12.12 Assembling and Attaching the Pull Cord It is important to assemble and attach the pull cord to the pull switch module correctly to ensure the cord is securely attached and that the “safety break” mechanism works reliably. The following illustrations show how to prepare the pull cord: Figure 127. Assembling and attaching the pull cord 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US 6.13 Duty Selector (NIDS) Figure 128. Duty Selector front and back view Important: An NIDS module must be permanently located adjacent to the primary NIRD annunciator. The Duty Selector is an auxiliary peripheral which can be connected to any one of the four room buses from the room controller. It has a fixed address number 5 on the room bus which cannot be changed.
Installation Guide teleCARE IP TD 93021US 6.13.1 Duty Selector Electrical Connections The duty selector is an “active peripheral” therefore it must be connected to one of the four room buses of a teleCARE IP room controller by the 4-pole room bus connector. It has the fixed room bus address of 5 and this address cannot be changed. 4-Pole Connector for Room Bus Test LED Auxiliary Inputs 1&2 Figure 129.
Installation Guide teleCARE IP TD 93021US 6.13.2 Auxiliary Inputs The third 4-pole connector is used for auxiliary inputs. It has two input circuits which are available as interfaces to external devices. These terminals provide 5.5Vdc at 0.6mA, for monitoring the external device contacts, as shown in Figure 130. Test LED Figure 130.
Installation Guide teleCARE IP TD 93021US 6.14 Card Reader (NICR) The Card Reader Module (NICR) is a single switch module suitable for use in the teleCARE IP system. It is an RFID device, operating frequency of 13.56 MHz, for use with contactless (Mifare Classic) smart cards. Figure 131. Card reader front and back view The NICR allows staff members to register their presence in a room or to open an electrically locked door through a contactless proximity authorized smart card.
Installation Guide teleCARE IP TD 93021US • The Auxiliary Monitoring circuits are power limited to 5.5Vdc at 0.6mA. 6.14.1 Card Reader Electrical Connections The NICR has two connectors consisting of the room bus and the auxiliary connections. It is an “active peripheral” therefore it must be connected to one of the four room buses of a teleCARE IP room controller by the 4-pole room bus connector (see 6.4.1, 4-Pole Connector Terminal on page 60).
Installation Guide teleCARE IP TD 93021US Figure 133. Typical installation with card reader 6.14.2 Card Reader Auxiliary Connections The NICR has auxiliary connections which provide for the control of external functions such as activating an electrically operated door locks and monitoring door-open alarm contacts or other suitable purposes. The applications of the relay contacts and the auxiliary connections are configured in the System Manager.
Installation Guide teleCARE IP TD 93021US Figure 134. NICR auxiliary connections WARNING: • The equipment that is connected to this interface is not considered to be part of the system configuration unless the equipment complies with ANSI/UL 2560 standard for Emergency Call Systems for Assisted Living and Independent Living Facilities. • The Auxiliary Monitoring circuit is not electrically isolated.
Installation Guide teleCARE IP TD 93021US 6.15 Speech Module (NISP) The Speech Module (NISP) is a teleCARE IP peripheral which facilitates speech in combination with Ascom Interactive Messaging (IM). It consists of a white plastic body, a printed circuit board and a perforated anodized aluminum face plate. Figure 135. Speech Module (NISP) front and back view The NISP incorporates a pre-amp circuit and a speaker amplifier and includes two loudspeakers and an electric microphone.
Installation Guide teleCARE IP TD 93021US For a two-module combination with the speech module mounted to the left side of the switch module (viewed from the front) the R190193 cable 8.0in (200mm) is required. Cable R190193 Length 8.0 in. (200mm) Figure 137. Speech module to the left of the switch module For a three-module combination the R190192 cable (length 7.0in (170mm) and the R190193 cable length 8.0in (200mm) are both required 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US 6.16 Room Display (NIRD) The NIRD Room Display (NIRD) combines Ascom interactive messaging (IM) functionality, with a teleCARE door side module and an RFID card reader in a wall mounted module which is suitable for use in residents rooms and staff rooms. It has an EBA polyester film membrane which covers the display and incorporates the buttons, keys and the LEDs. Important: At least one NIRD serving the property must be permanently installed in a fixed location.
Installation Guide teleCARE IP TD 93021US 6.16.1 Room Bus Electrical Connections The NIRD is an active teleCARE IP peripheral which must be connected to teleCARE IP room bus by a 4pole connector, as shown below. Figure 139. 4-pole connector terminal for the room bus 6.16.2 Room Bus with Passive Peripheral Bus Electrical Connections When a passive peripheral bus is required the room bus and the passive peripheral bus must be combined in an 8-pole connector.
Installation Guide teleCARE IP TD 93021US 6.16.3 Room Display Backplate (Short) To mount the NIRD as a single module the short backplate must be used: Figure 141 indicates the location of a hole which needs to be drilled for mounting purposes. Figure 141. Room display backplate (short) The backplate must be fixed to the wall using the four corner holes (indicated in the drawing below by red circles). = Essential = Optional CAUTION! DO NOT MOUNT THE ROOM DISPLAY CLOSE TO OR OVER METAL OBJECTS.
Installation Guide teleCARE IP TD 93021US 6.16.4 Room Display Combined with the Speech Module The NIRD can be combined with the NISP Speech Module in teleCARE IP systems with speech. The NIRD is used to select calls, control voice communication and cancel calls. The NISP facilitates two-way voice communication via a press-to-talk function on the NIRD. (For details of the NISP speech module refer to chapter 6.15“Speech Module (NISP)” on page 101.) Figure 143.
Installation Guide teleCARE IP TD 93021US 6.16.5 Room Display Backplate (Long) The long backplate must be used to mount the NIRD combined with the NISP. Figure 144 indicates the location of a hole which needs to be drilled for mounting purposes. Figure 144.
Installation Guide teleCARE IP TD 93021US The backplate must be fixed to the wall using the four corner holes and the two holes in the middle of the backplate (indicated in the drawing below by red circles). CAUTION! DO NOT MOUNT THE ROOM DISPLAY CLOSE TO OR OVER METAL OBJECTS. = Essential = Optional There must be a minimum distance of 1 inch (30mm) in all directions between the room display and any metal objects to avoid the degradation of the card reader antenna performance. Figure 146.
Installation Guide teleCARE IP TD 93021US Next connect the NIRD room display to the NISP and plug in the room bus connector. Figure 148. Connecting the NIRD to the NISP and connecting the room bus Refer to 6.16.1, Room Bus Electrical Connections on page 104 for full details. Next, snap fit the room display to the backplate. Figure 149. Mounting the NIRD on the backplate 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US 6.17 Television Interface Module The television interface module is the interface between the television stereo audio output and the teleCARE IP system. It provides the necessary galvanic separation between the television and the teleCARE peripherals. In the teleCARE IP application the television interface module is a passive device requiring no power supply. Figure 150.
Installation Guide teleCARE IP TD 93021US 6.17.1 Television Interface Module Electrical Connections J3: Not used. J1: TV Stereo Audio Input from the Television Headphone Jack Socket J2: TV Stereo Audio Output to the teleCARE IP Figure 152.
Installation Guide teleCARE IP TD 93021US 6.18 Sunblind Control Module Figure 153. Sunblind Control Module The Sunblind Control Module is a passive device on the teleCARE IP room bus. It has two heavy duty relays with normally open contacts to control the sunblind motor. The sunblind control module is compatible with the bedside module NIBM2 and the medical rail socket NIMS2. It is used in combination with the NIPH3-A7A and NIPH3-AES handsets to control the up and down motors of sunblinds. Figure 154.
Installation Guide teleCARE IP TD 93021US WARNING: Up to 230Vac power to the sunblind motor control relay must be fused at 2 Amps. Appropriate cable for the voltage and current must be used for the sunblind motor control. WARNING: The equipment that is connected to this interface is not considered to be part of the teleCARE IP system. 17 July 2017 / Ver.
Installation Guide teleCARE IP 7 Peripherals TD 93021US External Inputs In many installations, the need for connecting external alerts from sensors to the teleCARE IP system might arise. Some modules are already capable of handling external inputs. Other modules need a special Connection Board (NICB) to handle these external inputs. The external inputs connection board (NICB) extends teleCARE IP system capability of processing external inputs from normally open (N.O.) or normally closed (N.C.
Installation Guide teleCARE IP Peripherals TD 93021US Ensure that the electrical power to the equipment is switched off before connecting the Connection Board to any of the listed switch modules. The area in which the teleCARE equipment is to be installed must be clean, dry and weatherproof. The NICB must be mounted in the back box onto which the switch modules are mounted. 7.4 NICB-kit The NICB is part of a kit. NICB-kit order number is NICB-AAA.
Installation Guide teleCARE IP 7.5 Peripherals TD 93021US Connection Board The NICB has two connectors: a 5-pole connector for connection to the cross cable and a 4-pole connector (NICT4-AA) for connections to the external inputs. The following figure shows the connections. Figure 159. Connections on the NICB 7.5.1 4-Pole Connector Terminal Figure 160. 4-pole connector terminal The NICB kit (NICB-AAA) contains a 4-pole connector terminal (NICT4-AA).
Installation Guide teleCARE IP Peripherals TD 93021US Figure 162. NICB connected to external contacts. IMPORTANT: The maximum cable length between the NICB and the external contacts shall not exceed 10m/33ft. 17 July 2017 / Ver.
Installation Guide teleCARE IP 7.6 Peripherals TD 93021US Bed Module (NIBM2) and Pull Cord Module - Active (NIPC-XXA) The modules NIBM2 and active NIPC can be connected to the NICB for the use of one external input. IMPORTANT: Only IN0 of the NICB shall be used. IN1 of the NICB shall not be connected. If IN1 of the NICB is connected, the switch module cannot properly detect the presence of the NICB. Figure 163.
Installation Guide teleCARE IP 7.7 Peripherals TD 93021US Door Side Module (NIDM) and Toilet Cancel Module - Active (NITC-XXA) The modules NIDM and active NITC can be connected to the NICB for the use of two external inputs. These modules shall be connected to the NICB via two 4-pole screw terminals. Figure 164. Door side module: front and back view Note: The two 4-pole screw terminals which are required to connect the room bus and the passive bus to the NICB module must be ordered separately.
Installation Guide teleCARE IP Peripherals TD 93021US • Strip the insulation from the end of each wire over 5mm (3/16in). • Connect the cross cable wires to the two 4-pole screw connectors. 17 July 2017 / Ver.
Installation Guide teleCARE IP Peripherals TD 93021US • Place the 4-pole screw connectors on the switch module. Note: The NITC-XXA is connected in a similar way as the NIDM. 17 July 2017 / Ver.
Installation Guide teleCARE IP 7.8 Peripherals TD 93021US Room Display (NIRD) The Room Display (NIRD) can be connected to the NICB for the use of two sensor inputs. An 8-pole screw terminal is used for the connection of the Room bus and the NICB. Figure 165. Room Display Note: The 8-pole connector terminal which is required to connect the room bus and the external bus to the NICB module must be ordered separately. The article number is R180732. 7.8.
Installation Guide teleCARE IP Peripherals TD 93021US • Strip the insulation from the end of each wire over 5mm (3/16in). • Connect the wires to the 8-pole screw connector as shown below. 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US • Place the 8-pole connector on the switch module. 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT 8 Wireless Functionality 8.1 General teleCARE IP with wireless functionality is intended for use in nursing homes and in assisted living facilities. teleCARE IP is able to support wireless functionality through the NIRC3 teleCARE IP room controller combined with the NIRX transceiver, which is piggy-back mounted on the circuit board of the NIRC3. For detailed information refer to “Principle of the teleCARE IP with Wireless Functionality” on page 127.
Installation Guide teleCARE IP TD 93021US DRAFT The NIFX fixed wireless transceiver is a three-button wall mounted switch module. It comes as a socket version used for the connection of a handset or equipped with a pull-cord. Both variants of the NIFX include a 125 kHz LF receiver and an NIRX 916 to 921 MHz Class 1 transceiver which is piggy-back mounted on the circuit board of the NIFX.
Installation Guide teleCARE IP TD 93021US DRAFT 8.2 Principle of the teleCARE IP with Wireless Functionality The system is configured using the teleCARE IP System Manager - NISM2. The wireless server is a Unite application on the NISM2 serving as the central controller for all wireless devices in the teleCARE IP system with wireless functionality.
Installation Guide teleCARE IP TD 93021US DRAFT 8.2.1 Location Based - Using LF Beacons The addition of the NILF low frequency beacons gives location based wireless functionality available including access control. The NILF will send out its ID, including location information, at regular intervals using a low frequency 125 kHz signal that will be picked up by the wireless transceiver modules that pass by the NILF. Figure 169.
Installation Guide teleCARE IP TD 93021US DRAFT 8.3 teleCARE Wireless with Speech The room controller (NIRC3) is required for speech in teleCARE IP Wireless and each NIRC3 must include a voice piggyback module (NIVP). In order to achieve the required RF coverage some of the NIRC3s must include a transceiver module (NIRX). Refer to “RF Planning Considerations” on page 132 for details. The wireless mobile transceiver (NITX) is required.
Installation Guide teleCARE IP TD 93021US DRAFT Dynamic Mode In “Dynamic Location” mode, the NITX can move around the coverage area and speech will be automatically directed to the current location of the NITX when a call is received. The real-time location of the NITX is determined by LF beacons (NILF) mounted at the entrance to each room. The NILF transmits an LF location signal which is received by the NITX. The NITX memorizes its’ current location until it receives a new LF location signal.
Installation Guide teleCARE IP TD 93021US DRAFT Speech Handling Overview The table below shows the speech handling based on their static or dynamic location mode setting in combination with passive or active location beacons. Transceiver location mode Static Dynamic 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT 8.4 teleCARE IP Wireless Planning 8.4.1 RF Planning Considerations The room controller NIRC3 (with transceiver module NIRX installed) functions as a base station and must be situated where it can reliably receive the RF signals of the wireless devices in the designated coverage area. The optimum indoor coverage area is approximately 100 feet from the NIRC3 base station (depending on the environment).
Installation Guide teleCARE IP TD 93021US DRAFT Figure 173. NIRC3 base station horizontal coverage Note: The size and shape of the NIRC3 base station coverage areas in the above illustrations are theoretical. In practice the coverage can be distorted by environmental influences such as metal objects, strong magnetic fields and other sources of RF radiation. Testing the NIRC3 base station Coverage Area To perform an RF coverage test the following equipment is required: • An NIRC3 room controller.
Installation Guide teleCARE IP TD 93021US DRAFT Figure 174. NIRC3 with USB stick for RF coverage testing Coverage Test Procedure To start coverage testing press on the call button of the NITX (or NIFX) that is operating in the RF test mode. If the NITX (or NIFX) is in range of an NIRC3 base station it will receive an acknowledgment. The LED on of NITX (or NIFX) will confirm the acknowledgment by 3 flashes within approximately 1.25 seconds. 1.
Installation Guide teleCARE IP TD 93021US DRAFT 8.4.2 LF Planning Considerations The NILF has an LF transmitter with a maximum transmissions range of approximately 9 feet radius, but this will vary depending on the environment. Therefore an area to be covered must be within a maximum of 9 feet of the NILF. The NILF is best mounted on a wall or at a door post at approximately 4 feet above the floor.
Installation Guide teleCARE IP TD 93021US DRAFT Note: Refer to “NILF DIP Switch Settings” on page 180 in order to adjust the configuration of the NILF to suite the requirements. The NILF has a circular coverage distribution pattern in the horizontal plane. The coverage area has a radius 9 feet radius from the NILF (free of obstructions), as shown in the following illustration. Reduced signal strength is possible through walls of light weight construction. Figure 177.
Installation Guide teleCARE IP TD 93021US DRAFT NILF range test To perform an LF range test the following equipment is required: • An NILF location beacon. • An NITX or NIFX with LF functionality that is set to “LF test” mode. Note: For detailed information on how to put the NITX or NIFX in LF test mode, refer to “Appendix - Wireless Planning Considerations” of the teleCARE IP Configuration Manual “TD 93019US”.
Installation Guide teleCARE IP TD 93021US DRAFT 8.5 Wireless Infrastructure The use of a full wireless infrastructure is an extension on the existing wireless functionality and is intended for use in nursing homes and in assisted living facilities. In an environment consisting mainly of wireless devices, a full wireless infrastructure can be achieved using a wireless gateway (NIRC3 + NUREP) in combination with wireless repeaters (NUREP).
Installation Guide teleCARE IP TD 93021US DRAFT Figure 180. IEEE 802.15.4 versus 802.11 (Wi-Fi) The wireless call peripherals consist of the wireless bedside module (NUWBM3), wireless universal transceiver module (NUUTX), wireless passive infrared module (NUWIR), fixed transceiver (NIFX), mobile transceiver (NITX), Staff transceiver (NITX) and an optional low frequency beacon (NILF) as described in the general section, see “General” on page 125.
Installation Guide teleCARE IP TD 93021US DRAFT 8.6 Principle of the Wireless Infrastructure In an environment consisting mainly of wireless devices, a full wireless infrastructure can be achieved using a wireless gateway (NIRC3 + NUREP) in combination with wireless repeaters (NUREP), To create a wireless gateway, a wireless repeater (NUREP) is connected via a USB cable to a room controller (NIRC3). The wireless gateway is located at a central location.
Installation Guide teleCARE IP TD 93021US DRAFT Also a wireless repeater must be able to see the next and the previous wireless repeater in the subnet at all times, all the way up to the wireless gateway. The status of the wireless repeaters in a wireless infrastructure are constantly monitored and an error message will be sent if a section fails to respond. 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7 teleCARE IP Wireless Components 8.7.1 NUREP Wireless Repeater The wireless repeater (NUREP) is the wireless infrastructure building-block of the wireless system. Wireless repeaters receive the signals from the wireless modules from residents and all the wireless modules in the resident room. Wireless repeaters also retransmit these signals to the central equipment (wireless gateway), via other wireless repeaters.
Installation Guide teleCARE IP TD 93021US DRAFT NUREP Electrical Connections The figure below shows the electrical connections of the wireless repeater (NUREP). Figure 183.
Installation Guide teleCARE IP TD 93021US DRAFT NUREP External Power Supply Connection Connect the supplied 5VDC Class II power adapter to the wireless repeater. Figure 184. Connect the external power supply. NUREP Battery Placement (Optional) It is possible to place two batteries as backup power in case the mains power fails. Place the two AA type 1.5V alkaline batteries according the image below, observe polarity. Figure 185. Insert the batteries 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.2 Outdoor Box Wireless Repeaters can be mounted outdoors using a suitable weatherproof enclosure that meets local electrical code. An outdoor box protects the repeater from the outdoor elements, for example at a campus style facility or when outdoor coverage is required to capture calls from residents when outside. An example of an outdoor box is shown below. Figure 186. Example of an outdoor box with repeater. 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.3 Wireless Gateway The wireless gateway (NIRC3 + NUREP) is the interface between the wireless infrastructure and the teleCARE IP central equipment (system manager). The wireless gateway is the central receiver receiving the RF signals of the repeaters and the RF signals of the wireless devices that are in the direct vicinity of the wireless gateway. Figure 187.
Installation Guide teleCARE IP TD 93021US DRAFT Wireless Repeater Electrical Connections for Wireless Gateway Usage The wireless repeater is connected to the room controller via a USB cable. This cable takes care of the data and the power of the repeater. The room controller is powered by the 24VDC system power. Figure 188.
Installation Guide teleCARE IP TD 93021US DRAFT NUREP - NIRC3 Interconnection Wireless gateway NUREP - NIRC3 Interconnection using a USB to micro USB cable (Article number 660464). Figure 189. USB connection between NIRC3 and NUREP (1) Plug the micro USB connector into the socket on the wireless repeater NUREP. (2) plug the USB connector into the top slot of the USB 2.0 socket on the NIRC3 Figure 190.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.4 NUWBM3 Wireless Active Bedside Module The wireless bedside module (NUWBM3) is a wall mounted switch module. It has three customizable buttons with LEDs, a white plastic body and includes a spacer for surface mounting. It comes with an Ascom SafeConnect socket used for the connection of the bedside handset. see “NUHS1B Handset Connection” on page 153 Figure 191. NUWBM3 NUWBM3 Electrical Connections Figure 192.
Installation Guide teleCARE IP TD 93021US DRAFT NUWBM3 Battery Connections Connect the battery leads of the battery holder to the 3-pole screw terminal connector.. 2 - Battery lead ground connection 3 - Battery lead +V connection Figure 193. NUWBM3 battery connection Insert two AA alkaline batteries, observe polarity Figure 194. Batteries inserted into battery holder 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT Assemble the NUWBM3. Figure 195. NUWBM3 assembly Mount the NUWBM3 onto the spacer: (1) Insert the battery holder into the spacer (2) Screw the metal adapter onto the spacer (3) Slide the frame onto the adapter (4) Connect the 3-pole screw terminal connector to the NUWBM3 circuit board (5) Insert the NUWBM3 into the frame till it snap fits 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT Back view of an assemble NUWBM3. Figure 196. NUWBM3 assembled NUWBM3 External Power Supply Connection (Optional) Connect the Class II power adapter (CE, UL approved) to the 3-pole screw terminal connector. 1 - Power supply lead +5 VDC connection 2 - Power supply lead ground connection Figure 197. External 5 VDC connection 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT Remove the NUWBM3 from the Spacer Figure 198. Remove the NUWBM3 from the spacer To remove the NUWBM3 from a spacer, for example to change the batteries: (1) Insert a flat blade screwdriver into the bottom of the frame (2) Gently push the screwdriver upwards until the NUWBM3 is released from the metal adapter. NUHS1B Handset Connection The Ascom SafeConnect socket is used for connecting the NUHS1B 1-button handset with handset disconnect alarm functionality.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.5 NIRX teleCARE IP Transceiver The NIRX transceiver is a printed circuit module which is piggy back mounted on the NIRC3 room controller and the NIFX fixed transceiver. The NIRX will adds wireless call functionality to the NIRC3 room controller and the fixed transceiver. Optionally the NIRX can also be mounted on the NILF location beacon for actively monitoring the state of the NILF, such as tamper and low battery alarm conditions. Figure 200.
Installation Guide teleCARE IP TD 93021US DRAFT Optional NILF Figure 202. Piggyback mounting the transceiver module on the NILF 8.7.7 NIVP Voice Piggyback Module The NIRC3 can be extended with an optional voice piggyback module (NIVP) to include speech and with an optional transceiver module (NIRX) for wireless functionality.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.8 NIFX Fixed Transceiver The NIFX series fixed transceiver is a wireless teleCARE IP switch module which is available as socket module or pull cord module. It has 3 function buttons, a white plastic body and includes a spacer for surface mounting. The pull cord version includes the cord with two red balls but no socket. NIFX-1BB NIFX-1AB Figure 204.
Installation Guide teleCARE IP TD 93021US DRAFT Replacing the Batteries The NIFX fixed transceiver requires 2 x 1.5V AA disposable alkaline batteries. The battery voltage is continually monitored and if low voltage is detected a “low battery” alarm is transmitted. Figure 206. Replacing the batteries The low battery status is included in every heartbeat transmission of the unit. Under normal circumstances the battery life is 1 to 1½ years.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.9 NITX Mobile Transceiver The NITX-AAB and NITX-BAB mobile transceivers are wireless call units for residents. The NITX-BBB is a staff transceiver for staff and caregivers. They are robust and water resistant (IP 67). The units NITX-AAB and NITX-BAB contain a 916 to 921 MHz RF transceiver, a call button and a reassurance LED.
Installation Guide teleCARE IP TD 93021US DRAFT Using the NITX-BBB Transceiver The NITX-BBB may be used by the staff and caregivers to cancel calls initiating from a NITX (BAB) and NIFX (1AB or 1BB) or to call for assistance. • A single short button press cancels a call when the staff transceiver is within one foot of the NITX or NIFX which initiated the call. If additional assistance is needed: • A single Long button press places an Assistance call.
Installation Guide teleCARE IP TD 93021US DRAFT Figure 210. Remove the circuit board Remove the battery from the circuit board by sliding it in the direction of the arrow. Place the new battery with the positive“+” terminal facing upwards and slide it into place. Figure 211. Removing the old and placing the new battery 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT Transceiver Accessories Interchangeable rings, buttons and strap loops make it possible to customize the transceiver body. The four rings and six buttons including a ring mounting tool are available as customization kit and the five strap loops including a rivet are available as an accessory kit. Figure 212. Transceiver accessories 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.10 NUUTX Universal Transceiver The universal transceiver (NUUTX) is a wireless interface point for all sorts of sensors and detectors. The NUUTX has two independent inputs and a magnetic window/door alarm detector. The NUUTX is battery operated with a battery lifetime of > 5 years. Figure 213. NUUTX Universal Transceiver NUUTX Components Figure 214. NUUTX Universal Transceiver exploded view 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT NUUTX components: (1) Bracket for mounting the NUWIR on walls or window/door posts (2) Battery lid (3) Screws (4) Case (lower halve) with circuit board mounted (5) Location of magnetic field sensor (6) Two 2-pole spring loaded wire clamp connectors for the connection of external contacts (7) Case (upper halve) NUUTX Window - Door Alarm Monitoring The NUUTX can be used to detect the state of a window or door using a (hall effect switch) which is mounted on th
Installation Guide teleCARE IP TD 93021US DRAFT Alternatively in situations where existing window or door contacts are available or when integrated into a window or door post, the outputs can be connected to one of the NUUTX inputs. See “NUUTX Inputs” on page 165. 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT NUUTX Inputs The NUUTX has two inputs that can be used to interface external alerts coming from a wide variety of detectors. For example: • Fire detectors • Window/door open detector • Low pressure switches to generate an alert from a resident • Bed exit sensor • Chair sensor • Alerts from the building management system Figure 216.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.11 NUWIR Wireless PIR Module The motion sensor or PIR (passive infrared) sensor (NUWIR) is used to detect resident movement. For example the NUWIR can be used in the toilet, to indicate that a resident is in the toilet. Software will determine when to alert the caregivers. The NUWIR is battery operated with a battery lifetime of > 3 years. Figure 217.
Installation Guide teleCARE IP TD 93021US DRAFT NUWIR components: (1) Bracket for mounting the NUWIR on walls or window/door posts (2) Battery lid (3) Screws (4) Case (lower halve) with circuit board mounted (5) 3-pin header used to set the sensitivity of the PIR module (6) Fresnel lens, adjust orientation depending on horizontal or vertical mount (7) Case (upper halve) NUWIR Orientation The default orientation for mounting the NUWIR is vertical.
Installation Guide teleCARE IP TD 93021US DRAFT The graphic below shows the required orientation of the fresnel lens when mounting the NUWIR horizontally. Figure 220. Fresnel lens orientation for horizontal mount NUWIR Sensitivity The sensitivity of the NUWIR can be set to low or high by adjusting the setting of the 3-pole pin header that is located on the circuit board. To change the sensitivity of the NUWIR, position a shunt on the 3-pole header according to the image below. Figure 221.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.12 IR Range Test Perform an IR range test before starting with the final assembly of the NUWIR. Located directly above the passive infrared sensor (PIR) is a motion detected status LED which lights up when motion is detected. For range testing purposes the LED will only function for 60 seconds after inserting the batteries. In order not to disturb the residents, this LED will not function during normal operation.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.14 (3) Slide the battery lid back into place until it snap fits.NUUTX NUWIR Mounting Instructions The NUUTX and the NUWIR are designed to be mounted on walls or onto window/door posts. They can be mounted both vertically and horizontally. Place the NUUTX NUWIR onto a post or the wall and mark the holes for drilling with a sharp pencil. The NUWIR should be placed at approximately 4 feet (1.
Installation Guide teleCARE IP TD 93021US DRAFT Mount the bracket on the wall with the two larger sized snap fittings at the top. Figure 224. Orientation of the bracket (1) Larger sized snap fittings on top (2) Smaller sized snap fittings at the bottom (3) Screw the bracket onto the wall Place the NUUTX or NUWIR into the bracket by aligning the two holes on top of the module with the two fittings on top of the bracket. Figure 225. Align the NUUTX or NUWIR to the top of the bracket.
Installation Guide teleCARE IP TD 93021US DRAFT Finally rotate the module until it snap fits on the lower halve of the bracket. Figure 226. Snap fit the NUUTX or NUWIR onto the bracket. (1) Rotate the module until it snap fits on the lower halve of the bracket 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.15 NILF Low Frequency Beacon The low frequency beacon NILF is contained in a white plastic enclosure with a slim design that is suitable for surface mounting on walls or at a door post. The NILF is powered by three 1.5V “C” alkaline batteries. In situations where battery power is not suitable the unit can be powered by certified ECS power supplies (see Section 4.
Installation Guide teleCARE IP TD 93021US DRAFT Figure 228. NILF installation example WARNING: The NILF produces a low frequency magnetic field. Installing the NILF in proximity of metal objects or electrical cables can negatively influence the magnetic field which reduces the LF field coverage. Open the NILF by removing the screw that is located at the bottom of the housing. To remove the front cover slightly lift it up and gently pull it off of the rear cover. Figure 229.
Installation Guide teleCARE IP TD 93021US DRAFT Figure 230. Mark the holes for drilling Screws with a diameter of 1/8 in. (3.8mm) should be used to mount the NILF to the door post or the wall. Two suitably sized holes should be drilled at the marked spots. In a wooden door post holes should be drilled that are slightly smaller than the size of the screws that are used. When mounting the NILF on a wall, holes should be drilled that accept a wall plug suitable for using screws with a diameter of 1/8 in.
Installation Guide teleCARE IP TD 93021US DRAFT Mount the NILF on the door post or wall. Figure 232. Placing the NILF on the door post The two screws should be tightened carefully using the appropriate screwdriver. Make sure that the NILF does not bend when tightening the screws. Figure 233. Tightening the two screws. 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US DRAFT Mounting an NILF with NIRX IMPORTANT: Do not attempt to mount the NILF onto the wall when the NIRX is placed onto the NILF circuit board. Figure 234. Do not mount the NILF to the wall while the NIRX is placed Because the NIRX covers the top hole of the NILF case, the NIRX antenna area will get damaged when trying to mount the NILF to the wall while the NIRX is in place.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.6 NILF Electrical Connections The electrical connections on the component side of the low frequency beacon printed circuit board are shown in the following drawing of the NILF circuit board. NIRX piggyback connectors J3: Internal antenna connection J2: External Connections Figure 236.
Installation Guide teleCARE IP TD 93021US DRAFT Antenna Connection The 2-pole antenna connection (J3) is connected to the internal LF antenna. Figure 238. NILF internal antenna connected External Connections The 8-pole external connector (J2) has connections for a second beacon (used for range extending in a master/slave configuration), a galvanically separated tamper alarm relay output, the internal battery and connection of an alternative external 24Vdc power supply. Figure 239.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.7 NILF DIP Switch Settings The NILF uses three sets of 8-pole DIP switches to set the ID, output power and transmission rate, master/ slave mode and the active location functionality. NILF ID DIP switches SW1 (1-8) and SW2 (1-4) are used to set the 12 bit ID code of the NILF. SW 2 - bit 8 to 11 SW 1 - bit 0 to 7 Figure 240.
Installation Guide teleCARE IP TD 93021US DRAFT Output Power and Transmission Rate DIP Switch Settings With the 4 bit output power DIP switch SW3 (1-4) selection the range of the LF field can be adjusted. In relation with the output power, the repetition rate of the low frequency transmissions can be set to normal, high, low and very low using 2 bit DIP switch setting on SW2 (5 and 6). Repetition SW 2 Rate Repetition Rate SW 3 Output Power Figure 241.
Installation Guide teleCARE IP TD 93021US DRAFT Master / Slave Mode DIP Switch Settings With DIP switch SW2 (8) the master / slave mode of the NILF can be set. SW 2 Master / Slave Figure 242.
Installation Guide teleCARE IP TD 93021US DRAFT Beacon Mode With DIP switch SW3 (5) the mode of the LF location beacon can be set to passive or active. SW 3 Beacon Mode Figure 244.
Installation Guide teleCARE IP TD 93021US DRAFT Tamper Alarm The tamper alarm output has a galvanically separated normally closed contact. The tamper alarm output can be connected to a third-party system for generating an alarm when the NILF is tampered with. This contact has a maximum rating of 300 mA at 30 Vdc. IMPORTANT: The tamper alarm output is only functional when an external 24Vdc power supply is used to power the NILF. The solid state relay is disabled when only batteries are used.
Installation Guide teleCARE IP TD 93021US DRAFT 8.7.8 NILF Power Supply The NILF can be powered by batteries or by an external 24Vdc power supply. For 24Vdc external power supply, use only a certified ECS power supply (see Section 4.). Placing the Batteries The NILF requires three 1.5V “C” (R14) alkaline batteries. The battery voltage is continually monitored. A red LED will indicate low battery status (1 flash per minute) and tamper alarm (continuous rapid flashing).
Installation Guide teleCARE IP TD 93021US DRAFT External Power Supply Connection Alternatively an external ECS certified 24Vdc power supply can be connected to power the NILF. 24Vdc ECS certified Power Supply Figure 247. External 24Vdc power supply connection 17 July 2017 / Ver.
Installation Guide teleCARE IP 9 TD 93021US Installation Examples Note: 1). All references to the NISE socket extension module and NIMS medical rail socket do not apply for UL 2560 systems. Note: 2). References to the NISE socket extension module can be interpreted as applying to the speech module (NISP) instead. 9.
Installation Guide teleCARE IP TD 93021US Figure 174. Wiring for 2-bed room with active toilet and shower peripherals 17 July 2017 / Ver.
Installation Guide teleCARE IP 9.2 TD 93021US 2-Bed Room with Passive Toilet Cancel and Passive Pull Cord Peripherals The following installation of a teleCARE IP system consists of one room controller with integrated corridor lamp (NIRC3) to which the peripherals are connected. The room controller offers four room buses which connect the peripherals to the room controller The example shown in the Illustration below is a 3-bed room with a toilet and shower.
Installation Guide teleCARE IP TD 93021US Figure 176. Wiring for 3-bed room with passive toilet cancel and passive pull cord 17 July 2017 / Ver.
Installation Guide teleCARE IP 9.3 TD 93021US 2-Bed Room with a Medical Rail Socket at each Bed The example shown in the Illustration below is a 2-bed room with peripherals for the toilet and shower. Each bed is equipped with a medical rail socket (which is usually installed in the medical rail above the bed) and a handset. Figure 177. 2-Bed Room with medical rail sockets 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US Figure 178. Wiring for a 2-bed room with medical rail sockets 17 July 2017 / Ver.
Installation Guide teleCARE IP 9.4 TD 93021US Room Controller with Corridor Lamps (Master/Slave) The example below shows the combination of a room controller and 2 corridor lamps. In the example there are three resident rooms, each containing 3 beds and a toilet with shower. One of the rooms is connected to the room controller and each of the other rooms is connected to a corridor lamp. Each corridor lamp is connected to one of the room buses of the room controller. Figure 179.
Installation Guide teleCARE IP TD 93021US Figure 180. Wiring for three rooms with a room controller with two corridor lamps 17 July 2017 / Ver.
Installation Guide teleCARE IP 9.5 TD 93021US 4-Bed Room with Speech The installation of a teleCARE IP system with speech is basically the same as without speech except that the teleCARE IP Speech Module is added at each active peripheral where speech communication is required.
Installation Guide teleCARE IP TD 93021US Figure 182. Wiring for 4-bed room with Speech at each bed 17 July 2017 / Ver.
Installation Guide teleCARE IP 9.6 TD 93021US Duty Selector at a staff Station The Duty Selector is an peripheral which can be connected to any one of the four room buses from the room controller. It has a fixed address number 5 on the room bus which cannot be changed. It also has two inputs and two galvanically isolated outputs via relays. The two input circuits and the two output circuits are available as interfaces to external devices.
Installation Guide teleCARE IP TD 93021US Figure 184. Wiring for staff station with duty selector and door side module 17 July 2017 / Ver.
Installation Guide teleCARE IP 9.7 TD 93021US Positioning of the teleCARE IP Peripherals The following illustrations show typical room installations with recommended locations for the teleCARE equipment. 9.7.1 Room Controller, Door side Module and Customizable Module: 9.7.2 Toilet Cancel Module and Pull Cord Module: 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US 9.7.3 Bedside Module: 17 July 2017 / Ver.
Installation Guide teleCARE IP TD 93021US Document History Version Date Description A 21 August 2014 • First US release B 12 February 2015 • Product images Update • Disabling the LEDs if only the relay contact is required, see “Disabling the LEDs” on page 39 • Connection of an ESPA (or a TAP) paging system added, see “System Manager (NISM2)” on page 51 • Content referring to NIRC, NICL and NILD has been removed.