Installation Instructions

Overview:
LPS5C24X linear power supply/charger converts a 115VAC 60Hz input to a 24VDC @ 3.5 amp continuous supply current.
The output stays regulated until the batteries discharges to 25% capacity.
Specifications:
Input:
• 115VAC50/60Hz,1.6amp.
Output:
• 24VDC@3.5amp.
• Filteredandelectronicallyregulated.
• Thermalandoverloadprotection
with autoreset.
Battery Backup:
• Builtinchargerforsealedleadacidbatteries.
•Automaticswitchovertostand-by
batterywhenACFails.
•PTCbatteryprotection.
• Maximumchargecurrent0.3amp.
• Includesbatteryleads.
Visual Indicators:
• ACinputandDCoutputLEDindicators.
Supervision:
• LowbatteryandACfailsupervision
(dry relay outputs 1 amp @ 28VDC).
Enclosure Dimensions (H x W x D):
13.5”x13”x3.25”(342.9mmx330.2mmx82.55mm)
Power Supply Voltage Output Specifications:
Output VDC Maximum Load DC
24VDC 3.5 amp
Installation Instructions:
TheLPS5C24XshouldbeinstalledinaccordancewithTheNationalElectricalCodeandallapplicable
Local Regulations.
1. MounttheLPS5C24Xinthedesiredlocation.
2. ConnectACpowertotheblackandwhiteflyingleadsofthetransformer (Fig. 1). Connect green lead to the earth
ground.Use18AWGorlargerforallpowerconnections(Battery,DCoutput).
3. Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.
4. Connect devices to be powered to the terminals marked [+ DC -- ] (Fig. 1).
5. Connectbatterytotheterminalsmarked[+BAT-- ] on the unit (battery leads included) (Fig. 1).
Note:Whenbatteriesarenotused,alossofACwillresultinlossofoutputvoltage.
Terminal Identification:
Terminal Legend Function/Description
AC/AC LowvoltageACinput(24VAC150VA).Altronixpart#T24150.
+BAT-- Stand-bybatteryconnections.
+ DC -- 24VDC @ 3.5 amp continuous output.
LPS5C24X
Linear Power Supply/Charger
Green
Lead
Battery connection
(non power-limited)
Wire
Strap
(from
Enclosure
to Door)
Battery & AC
Supervision
Circuit
(power-limited)
AC AC
+ DC ---
+ BAT ---
BAT
FAIL
NO C NC NO C NC
24VDC
AC
FAIL
White
Lead
Black
Lead
Input 115VAC
50/60Hz
1.6 amp
XFMR Bracket
X
F
M
R
Green
Lead
(Ground)
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
Fig. 1

Summary of content (2 pages)