Data Sheet
eFlow104NA8D distributes and switches power to access control systems and acces-
sories. It converts a 120VAC 60Hz input into eight (8) independently controlled
24VDC PTC protected outputs. These power outputs can be converted to dry form
“C” contacts. Outputs are activated by an open collector sink or normally open
(NO) dry trigger input from an Access Control System, Card Reader, Keypad,
Push Button, PIR, etc. Unit will route power to a variety of access control hardware
devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs
will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables
Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary
devices. The fire alarm disconnect feature is individually selectable for any or all of
the eight (8) outputs.
eFlow104NA8D
Power Supply/Charger with Multi-Output
Access Power Controllers
Rev. DSeFlow104NA8D_02182014
Overview
Specifications
Input:
• Input120VAC60Hz,4.5amp.
• Powersupplyinputoptions:
a) One (1) common power input for ACM8CB and
lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8CB and one (1) for lock accessory
power (external power supply is required). Current
is determined by the power supply connected, not
to exceed a maximum of 10 amp total.
• Eight(8)AccessControlSystemtriggerinputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
Output:
• 24VDCoutputs@10ampsupplycurrent.
• Power-limitedoutputs.
• Eight(8)independentlytriggercontrolledoutputs.
Output options:
a) Eight (8) Fail-Safe filtered power outputs.
b) Eight (8) Fail-Secure filtered power outputs.
c) Any combination of the above.
• Eight(8)unswitchedfilteredaux.poweroutputs
(outputsarerated@2amp).
• OverVoltageprotection.
• Shortcircuitandthermaloverloadprotection.
Fire Alarm Disconnect:
• FireAlarmdisconnect(latchingornon-latching)is
individually selectable for any or all of the
eight (8) outputs.
• FireAlarmdisconnectinputoptions:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• AlarmoutputrelayindicatesthatFACPinputis
triggered(form“C”contactrated@1amp28VDC
not evaluated by UL).
Supervision:
• ACfailsupervision(form“C”contacts).
• Batteryfail&presencesupervision
(form “C” contacts).
• Lowpowershutdown.ShutsdownDCoutput
terminalsifbatteryvoltagedropsbelow70-75%
(depending on the power supply).
Prevents deep battery discharge.
Visual Indicators:
ACM8CB Access Power Controller:
• RedLEDsindicateoutputsaretriggered
(relays energized).
• GreenLEDindicatesFACPdisconnectistriggered.
eFlow Power Supply Board:
• ACinputandDCoutputLEDindicators.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• PowerSupplyBoardmaximumchargecurrent
1.54amp.
• Automaticswitchovertostand-bybatterywhenAC
fails. Transfer to stand-by battery power is
instantaneous with no interruption.
• Zerovoltagedropwhenunitswitchesovertobattery
backup (AC failure condition).
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• ACM8CBboardmainfuseisratedat10amp.
• 122.85BTU/Hr.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm)
- Combinationknockoutsare0.625”and0.75”.
- Accommodates up to two (2) 12AH batteries.
• Productweight(approx.):8.9lbs.(4.04kg).
• Shippingweight(approx.):10.2lbs.(4.63kg).
eFlow104NA8D