Power Supply/Chargers Installation Guide Models Include: eFlow102N/eFlow102NX - 10 amp @ 12VDC eFlow102N8/ eFlow102NX8 eFlow102N8D/ eFlow102NX8D eFlow102N16/ eFlow102NX16 eFlow102N16D/ eFlow102NX16D - 10 amp @ 12VDC - Eight (8) Fused Outputs - 10 amp @ 12VDC - Eight (8) PTC Outputs - 10 amp @ 12VDC - Sixteen (16) Fused Outputs - 10 amp @ 12VDC - Sixteen (16) PTC Outputs Altronix Corp. 140 58th St. Brooklyn, NY Rev. 102NRP052213 More than just power.
Overview: The eFlow102N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC nominal output (see Power Supply Configuration Reference Chart and Specifications).
Input: Specifications: Supervision (cont’d): • 120VAC, 60Hz. Output: • For output voltage and supply current, refer to eFlow102N series Power Supply Configuration Reference Chart, pg. 2. • Auxiliary Power-Limited output rated @ 1 amp (unswitched). • Over Voltage Protection. Battery Backup: • Built-in charger for sealed lead acid or gel type batteries. • Maximum charge current 1.54 amp. • Automatic switch over to stand-by battery when AC fails.
8. To enable Low Output Power Shutdown set dip switch [Shutdown] to ON position (Fig. 1c, pg. 5). To disable Low Output Power Shutdown set dip switch Shutdown] to OFF position (Fig. 1c, pg. 5). 9. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown (Fig. 1d, pg. 5). 10. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Fig. 1e, pg. 5). 11.
Terminal Identification: Power Distribution Module Terminal Legend PD8UL/PD8ULCB 1P to 8P 1N to 8N Terminal Legend Function/Description PD16W/PD16WCB 1P to 16P Positive DC power outputs. 1N to 16N Negative DC power outputs. AC1 5A 250V L G 1a N AC FAIL BAT FAIL --- DC + 1h --- BAT + Fig. 1 - eFlow102N Board configuration 1g AC DELAY SHUTDOWN O N NC C NO NC C NO AC DC 1b 1 min. 2 hr.
Power Distribution Module(s): Fig. 3a - PD8UL Power Distribution Board Non Power-Limited Outputs Fig. 3b - PD8ULCB - Power Distribution Board Power-Limited Outputs Replace fuses with the same type and rating 3.5A, 250V.
Fig. 5 - eFlow102N configuration Edge of Enclosure Enclosure to Access Control Panel or U.L. Listed Reporting Device 5A 250V Sentrol model # 3012 Tamper Switch or equivalent (Not Included) Wire Strap (from Enclosure to Door) Green Lead (ground) L 120VAC power mains Non Powerlimited G N Door PD8UL/PD8ULCB PD16W/ PD16WCB AC1 AC FAIL NC C NO BAT FAIL NC C NO Battery & AC Supervision Circuit (Power-limited) DC Output to devices* (refer to Fig. 3a, 3b, 4a or 4b for board configuration pg.
NEC Power-Limited Wiring Requirements for eFlow102N Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Fig. 7 - eFlow102NX configuration Edge of Enclosure Enclosure Battery & AC Supervision Circuit (power-limited) power-limited Sentrol model # 3012 Tamper Switch or equivalent (Not Included) 120VAC power mains (non power-limited) Class 1 to Access Control Panel or U.L. Listed Reporting Device L AC1 AC FAIL G C NO AC DC AC DELAY SHUTDOWN BAT FAIL NC 2 hr. 1 min.
NEC Power-Limited Wiring Requirements for eFlow102NX Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Enclosure Dimensions (BC300) (approximate H x W x D): eFlow102N, eFlow102N8, eFlow102N8D, eFlow102N16, eFlow102N16D 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.20” (31mm) 3.25” (83mm) 1.20” (31mm) 0.75” (19mm) 12.5” (318mm) 11.0” (279mm) 1.20” (31mm) 0.75” (19mm) 0.9375” (24mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 0.9375” (24mm) 3.25” (83mm) 3.25” (83mm) 3.
Enclosure Dimensions (BC400) (approximate H x W x D): eFlow102NX, eFlow102NX8, eFlow102NX8D, eFlow102NX16, eFlow102NX16D 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.5” (393.7mm) 2.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with eFlow102N output.
Notes: - 14 - eFlow102N Series
Notes: Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 website: www.altronix.com, e-mail: info@altronix.com, Made in U.S.A.
Power Supply/Chargers Operating Guide Models Include: Model Output Input 120VAC, 60Hz 12VDC 3.5 amp 10 amp 24VDC Auxiliary Power-Limited Output (unswitched) Ripple Voltage ---------- 1 amp 760mV eFlow102N, eFlow102N8, eFlow102N8D, eFlow102N16, eFlow102N16D eFlow102NX, eFlow102NX8, eFlow102NX8D, eFlow102NX16, eFlow102NX16D Overview: The eFlow102N series power supply/chargers convert a 120VAC, 60Hz input, to a 12VDC output. Burg. Applications 4 hr. Stand-by/ 15 min. Alarm 0.