ACMJ Series Access Power Controllers with Power Supplies Installation Guide Models Include: • AL400ULACMJ • AL600ULACMJ - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs • AL1012ULACMJ • AL1024ULACMJ - 12VDC @ 10 amp. - 24VDC @ 10 amp. - Fused Outputs - Fused Outputs Rev.
Overview: These units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC fuse protected outputs. These power outputs can be converted to dry form “C” contacts. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc.
Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding.
(b) Form “C” outputs: When form “C” outputs are desired the corresponding output fuse (1-8) must be removed. Connect negative (–) of the power supply directly to the locking device. Connect the positive (+) of the power supply to the terminal marked [C]. For Fail-Safe operation connect the positive (+) of the device being powered to the terminal marked NC]. For Fail-Secure operation connect the positive (+) of the device being powered to the terminal marked [NO].
Typical Application Diagram: Fig. 1 Fig. 1a Intact = Dry Input Cut = Wet Input Normally Open (N.O.) Door Releasing Device FACP Keypad Access Control Panel TRG (Fire Alarm Control Panel) C NO F1 F2 F3 IN GND IN GND IN GND IN GND 5 6 7 8 F4 F5 F6 F7 F8 ON ON 2 3 4 1 2 3 4 SW1-SW8 FACP Interface ON 1 1 NO C NC + INP --- T + RET FACP INTERFACE TRG IN GND IN GND IN GND IN GND 1 2 3 4 Fig.
Fig. 2 CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating. Divider Fire Alarm Interface Optional Rechargeable Stand-by Battery NC C NO COM NC C NO COM OUTPUT 5 OUTPUT 6 NC C NO COM NC C NO COM OUTPUT 3 OUTPUT 4 LED3 LED2 LED1 3.5A 250V F1 + DC – NC C NO COM NC C NO COM OUTPUT 1 OUTPUT 2 LED4 3.5A 250V 3.5A 250V 3.
Terminal Identification Tables: Power Supply Board Terminal Legend L, N + DC – AC FAIL NC, C, NO BAT FAIL NC, C, NO + BAT – Function/Description Connect 115VAC 60Hz to these terminals: L to hot, N to neutral. AL400ULACMJ - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8 board (power-limited). AL600ULACMJ - 12VDC/24VDC @ 6 amp to ACM8 board (non power-limited). AL1012ULACMJ - 12VDC @ 10 amp to ACM8 board (non power-limited). AL1024ULACMJ - 24VDC @ 10 amp to ACM8 board (non power-limited).
Hook-Up Diagrams: Fig. 3 Optional hook-up using two (2) isolated power supply inputs: Fig. 4 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): CUT JUMPERS J1 AND J2 J1 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (ACM8 POWER) TRG TRG N.O. TRIGGER INPUT N.O. TRIGGER INPUT NC JUMPER Fig. 8 Normally Closed - Latching FACP trigger input with reset: (This output has not been evaluated by UL) TRG INTERFACE NO C NC FACP - 8 - N.C.
AL1024ULACMJ Battery Size Calculation Worksheet. A. AL1024ULACMJ internal current consumption (stand-by) ______________________________ 0.35 A B. Load current consumption (stand-by) ______________________________ A C. Stand-by time required (Hours) ______________________________ H D. Battery capacity required for stand-by (A+B)*C ______________________________ AH E. AL1024ULACMJ internal power consumption (Alarm) ______________________________ 0.35 A F.
Enclosure Dimensions (H x W x D approximate): 18” x 14.5” x 4.625” (457.2mm x 368.3mm x 117.48mm) 14.5” (368.3mm) 1.5” (38.1mm) 2.5” (63.5mm) 2.5” (63.5mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.0” (25.4mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.5” (38.1mm) 2.5” (63.5mm) 8.5” (215.9mm) 6.0” (152.4mm) 18.0” (457.2mm) 18.0” (457.2mm) 18.0” (457.2mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.0” (25.4mm) 2.75” (69.85mm) 1.5” (38.1mm) 14.5” (368.3mm) 4.
Notes: ACMJ series - 11 -