ACMCBJ Series Access Power Controllers with Power Supplies Installation Guide Models Include: • AL400ULACMCBJ • AL600ULACMCBJ • AL1012ULACMCBJ • AL1024ULACMCBJ - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Class 2 Rated PTC Protected - Class 2 Rated PTC Protected Power-Limited Outputs Power-Limited Outputs - 12VDC @ 10 amp. - 24VDC @ 10 amp.
Overview: These units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC PTC protected outputs. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc.
Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding.
6. Input trigger options (Fig. 1, pg. 5): (a) Normally Open [NO] input trigger: Inputs 1-8 are activated by normally open or open collector sink inputs. Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND]. (b) Open Collector Sink inputs: Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (-) to the terminal marked [GND]. 7. Fire Alarm Interface options (Figs. 4 through 8, pg.
Typical Application Diagram: FACP Dry Form "C" Output FACP C (Fire Alarm Control Panel) NO NO C NC FACP OUTPUT RELAY Fig. 1a KEYPAD NORMALLY OPEN N.O. DOOR RELEASING DEVICE ACCESS CONTROL PANEL NC NO C NC + INP --- T + RET FACP INTERFACE J3 TRG IN GND IN GND IN GND IN GND 1 2 3 4 F1 F2 F3 IN GND IN GND IN GND IN GND 5 6 7 8 F4 F5 F6 F7 F8 ON 2 3 4 1 2 3 4 SW1-SW8 ON 1 ON 1 Fig. 1 MAIN 10A 250V LED2 LED3 LED4 LED5 LED6 LED7 MAG.
Fig. 2 CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating.
Terminal Identification: Power Supply Board Terminal Legend L, N + DC – AC FAIL NC, C, NO BAT FAIL NC, C, NO + BAT – Function/Description Connect 115VAC 60Hz to these terminals: L to hot, N to neutral. AL400ULACMCBJ - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8CB board (power-limited). AL600ULACMCBJ - 12VDC/24VDC @ 6 amp to ACM8CB board (power-limited). AL1012ULACMCBJ - 12VDC @ 10 amp to ACM8CB board (power-limited). AL1024ULACMCBJ - 24VDC @ 10 amp to ACM8CB board (power-limited).
Hook-Up Diagrams: Fig. 3 Optional hook-up using two (2) isolated power supply inputs: Fig. 4 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): CUT JUMPER J3 CUT JUMPERS J1 AND J2 J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (ACM8CB POWER) J1 INTERFACE J3 TRG Fig. 5 Normally Open - Non-Latching FACP trigger input: Fig. 6 Normally Open FACP Latching trigger input with reset: (This output has not been evaluated by UL) J3 INTERFACE J3 TRG N.O.
AL1024ULACMCBJ Battery Size Calculation Worksheet. A. AL1024ULACMCBJ internal current consumption (stand-by) ___________________ 0.35 A B. Load current consumption (stand-by) ___________________ A C. Stand-by time required (Hours) ___________________ H D. Battery capacity required for stand-by (A+B)*C ___________________ AH E. AL1024ULACMCBJ internal power consumption (Alarm) ___________________ 0.35 A F. Load current consumption (Alarm) ___________________ A G.
Enclosure Dimensions (H x W x D approximate): 18” x 14.5” x 4.625” (457.2mm x 368.3mm x 117.48mm) 14.5” (368.3mm) 1.5” (38.1mm) 2.5” (63.5mm) 2.5” (63.5mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.0” (25.4mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.5” (38.1mm) 2.5” (63.5mm) 8.5” (215.9mm) 6.0” (152.4mm) 18.0” (457.2mm) 18.0” (457.2mm) 18.0” (457.2mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.0” (25.4mm) 2.75” (69.85mm) 1.5” (38.1mm) 14.5” (368.3mm) 4.
Notes: ACMCBJ series - 11 -
Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.