ACMCB Series Access Power Controllers with Power Supplies Installation Guide Models Include: • AL400ULACMCB • AL600ULACMCB • AL1012ULACMCB • AL1024ULACMCB - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Class 2 Rated PTC Protected - Class 2 Rated PTC Protected Power-Limited Outputs Power-Limited Outputs - 12VDC @ 10 amp. - 24VDC @ 10 amp.
Overview: These units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC PTC protected outputs. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc.
Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding.
(b) Auxiliary Power outputs (unswitched): Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (-) of the device being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads, etc. 6. Input trigger options (Fig. 1, pg. 5): (a) Normally Open [NO] input trigger: Inputs 1-8 are activated by normally open or open collector sink inputs. Connect devices (card readers, keypads, request to exit buttons etc.
Typical Application Diagram: Fig. 1 Fig. 1a Intact = Dry Input Cut = Wet Input Normally Open (N.O.) Door Releasing Device FACP Keypad Access Control Panel TRG (Fire Alarm Control Panel) C NO TRG IN GND IN GND IN GND IN GND 1 2 3 4 F1 F2 F3 IN GND IN GND IN GND IN GND 5 6 7 8 F4 F5 F6 F7 F8 ON ON 2 3 4 1 2 3 4 SW1-SW8 FACP Interface ON 1 1 NO C NC + INP --- T + RET FACP INTERFACE NC Fig.
Fig. 2 ON OFF --- 24V ON --- 12V CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating.
Terminal Identification Tables: Power Supply Board Terminal Legend L, N + DC – AC FAIL NC, C, NO BAT FAIL NC, C, NO + BAT – Function/Description Connect 115VAC 60Hz to these terminals: L to hot, N to neutral. AL400ULACMCB - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8CB board (power-limited). AL600ULACMCB - 12VDC/24VDC @ 6 amp to ACM8CB board (power-limited). AL1012ULACMCB - 12VDC @ 10 amp to ACM8CB board (power-limited). AL1024ULACMCB - 24VDC @ 10 amp to ACM8CB board (power-limited).
Hook-Up Diagrams: Fig. 3 Optional hook-up using two (2) isolated power supply inputs: Fig. 4 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): CUT JUMPERS J1 AND J2 J1 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (ACM8 POWER) TRG TRG N.O. TRIGGER INPUT N.O. TRIGGER INPUT NC JUMPER Fig. 8 Normally Closed - Latching FACP trigger input with reset: (This output has not been evaluated by UL) TRG INTERFACE NO C NC FACP -8- N.C.
AL1024ULACMCB Battery Size Calculation Worksheet. A. AL1024ULACMCB internal current consumption (stand-by) ______________________________ 0.35 A B. Load current consumption (stand-by) ______________________________ A C. Stand-by time required (Hours) ______________________________ H D. Battery capacity required for stand-by (A+B)*C ______________________________ AH E. AL1024ULACMCB internal power consumption (Alarm) ______________________________ 0.35 A F.
Enclosure Dimensions (H x W x D approximate): 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.5” (393.7mm) 2.0” (50.8mm) 5.0” (127.0mm) 5.0” (127.0mm) 1.1” (27.94mm) 1.25” (31.
Notes: ACMCB series - 11 -
Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A.