Data Sheet

Input:
Input 115VAC, 60Hz, 2.6 amp.
Input fuse rated @ 3.5 amp/250V.
Fire Alarm Panel or Access Control System trigger
inputs. N.O. or N.C. supervised trigger input and
polarity reversal trigger input.
Output:
12VDC outputs.
10 amp supply current.
Five (5) PTC protected Class 2 Rated power-limited
outputs, rated @ 2 amp.
Output relay energizes when unit is triggered
(form “C” contact rated 1 amp @ 28VDC).
Filtered and electronically regulated output.
Short circuit and thermal overload protection.
Battery Backup:
Built-in charger for sealed lead acid or
gel type batteries.
Automatic switch over to stand-by battery
when AC fails.
Maximum charge current 0.7 amp.
Supervision:
AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 6 hours.
Low battery supervision (form “C” contacts).
Battery presence supervision (form “C” contacts).
Power fail supervision relay (form “C” contacts).
Visual Indicators:
AC input and DC output LED indicators
(power supply board).
Red LEDs indicate condition of power outputs
(multi-output board).
Power and input trigger LEDs (multi-output board).
Electrical:
Operating temperature: 0º C to 49º C ambient.
61.42 BTU/Hr.
System AC input VA requirement: 299VA.
Mechanical:
Enclosure Dimensions (H x W x D approx.):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
- Accommodates up to two (2) 12VDC/12AH batteries.
Product weight (approx.): 8.95 lbs. (4.06 kg).
Shipping weight (approx.): 10.25 lbs. (4.65 kg).
Specifications
AL1012ULM
Multi-Output Power Supply/Charger
Rev. DSAL1012ULM_05212015
AL1012ULM multi-output access control power supply/charger is specifically
designed for use with access control systems and accessories. This unit converts
a 115VAC, 60Hz input into five (5) individually PTC protected Class 2 Rated
power-limited 12VDC outputs. Each output will route power to a variety of ac-
cess control hardware devices including Mag Locks, Electric Strikes, Magnetic
Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure
modes. Controlled trigger input is achieved through normally open (N.O.) or
normally closed (N.C.) supervised input or the polarity reversal from an FACP
(Fire Alarm Control Panel). A form “C” dry output relay enables HVAC Shut-
down, Elevator Recall or it may be used to trigger auxiliary devices.
Overview
Agency Approvals
UL 294 UL Listed for Access Control
System Units.
CUL Listed - CSA Standard C22.2
No.205-M1983, Signal Equipment.
AL1012ULM

Summary of content (2 pages)