Protect PV - Solar Inverters Installation Manual AEG Power Solutions GmbH Revision: 01 Date: 2011-05-25 Installation Manual 8000038781_00_BAL_en
Contents Contents 1. Safety and Conformity 2 Safety Information 2 Hazards of PV Systems 3 PV Load Switch 3 Conformity 4 Approvals and Certifications 4 2. Introduction 5 Introduction 5 Installation Sequence 6 Overview of Inverter 7 3.
1. Safety and Conformity 1 1. Safety and Conformity 1.1. Safety Information All persons installing and servicing inverters must be: • Trained and experienced in general safety rules for work on electrical equipment • Familiar with local requirements, rules and regulations for the installation Safety information important for human safety. Violation of warnings may result in injury to persons or death. Information important for the protection of property.
1. Safety and Conformity Before installation: Check for damage to inverter and packaging. If in doubt, contact the supplier before installing the inverter. Installation: For optimum safety, follow the steps described in this manual. Keep in mind that the inverter has two voltage carrying sides; the PV input and the AC grid. Disconnecting the inverter: Before starting work on the inverter, switch off AC grid at the mains switch and PV using the PV load switch.
1. Safety and Conformity 1 1.4. Conformity 1.4.1. Approvals and Certifications For more information, go to the download area at www.aegps.com/solarinverters, Approvals and Certifications. CE marking - This certifies the conformity of the equipment with the regulations which apply in accordance with the directives 2004/108/EC and 2006/95/EC.
2. Introduction 2. Introduction 2 2.1. Introduction This manual explains the installation and setup of the Protect PV solar inverter, for the installation technician. Illustration 2.1: Protect PV 10 kW, Protect PV 12.5 kW, Protect PV 15 kW CE marking - This certifies the conformity of the equipment with the regulations which apply in accordance with the directives 2004/108/EC and 2006/95/EC.
2. Introduction Protect PV variant 2 User interface Ancillary services Local Web Server Power Level Adjustment, Primary Frequency Control ✓ ✓ ✓ ✓ ✓ Protect PV Protect PV easy DC power rating Ride Through Fault Ride Through 10 kW Reactive Power 12.5 kW 15 kW ✓ ✓ ✓ ✓ ✓ ✓ Table 2.
2. Introduction 2.1.2. Overview of Inverter 2 Illustration 2.3: Overview of AEG PS Protect PV inverter Live Part 1. AC Connection Area 2. DC Connection Area 3. Terminal block for parallel connection 4. Auxiliary output: Potential free relay PELV (Safe to touch) 5. Auxiliary interface: RS485 6. Auxiliary interface: Temperature, Irradiation, Energy meter (SO) 7. Auxiliary interface: Ethernet Other 8. DC-switch The inverter can also be configured via the Web Server .
3. Installation 3. Installation 3.1. Installation Dimensions and Patterns 3 Note: When choosing the installation place, ensure that all labels are visible at all times. For details refer to the section Specifications. Avoid constant stream of water. Avoid direct sunlight. Ensure adequate air flow. Ensure adequate air flow. Mount on non-flammable surface. Mount upright on vertical surface. Prevent dust and ammonia gases.
3. Installation 3 Illustration 3.1: Safe Distances Observe these distances when installing one or more inverters. One row mounting is recommended. Contact the supplier for information on mounting in more rows. Illustration 3.2: Wall Plate Note: Use of the wall plate delivered with the inverter is mandatory. Use screws that can safely carry the weight of the inverter. The inverter must be aligned and it is important that the inverter is accessible at the front to allow room for servicing.
3. Installation 3.2. Mounting the Inverter For the safe handling of the inverter, two people must carry the unit, or a suitable transport trolley must be used. Safety boots must be worn. 3 Tilt the inverter as shown in the illustration and place the top of the inverter against the mounting bracket. Use the two guides (1) at the top plate to control the inverter horizontally. Illustration 3.
3. Installation Place the lower part of the inverter against the mounting bracket. 3 Illustration 3.5: Place Inverter in Mounting Bracket Lower (4) the inverter and make sure that the hook of the inverter base plate is placed in the lower part of the mounting bracket (5). Check that it is not possible to lift the bottom of the inverter away from the mounting bracket. (6) Fasten the screws on either side of the wall plate to secure the inverter. Illustration 3.6: Fasten screws 3.3.
3. Installation Removal is performed in the reverse order of mounting. With a firm grip at the lower end of the inverter, lift the inverter approximately 20 mm vertically. Pull the inverter slightly away from the wall. Push upwards at an angle until the wall plate releases the inverter. Lift the inverter away from the wall plate. 3 3.4. Opening and Closing the Inverter Remember to observe all ESD safety regulations.
3. Installation Push the front cover upwards. When a slight resistance is felt, give the front cover a tap on the bottom to snap it into holding position. It is recommended to use the holding position instead of dismounting the front cover completely. 3 Illustration 3.8: Open the Inverter To close the inverter, hold on to the lower end of the front cover with one hand and give it a tap on the top until it falls into place. Guide the front cover into place and fasten the two front screws.
3. Installation 3 Illustration 3.10: Fasten Front Screws and Ensure Proper PE Connection. The two front screws are the PE connection to the front cover. Make sure that both screws are mounted and fastened with the specified torque. 3.5. AC Grid Connection Note: When choosing the installation place, ensure that all labels are visible at all times. For details refer to the section Specifications.
3. Installation 3 Illustration 3.11: AC Cable Wire Strip Legend 1 Blue cable - Neutral 2 Yellow/green cable - Earth The illustration shows the stripping of insulation of all 5 wires of the AC cable. The length of the PE wire must be longer than the mains and neutral wires. Illustration 3.12: AC Connection Area 1. Verify the inverter matches the grid-voltage 2. Release main circuit breaker and make precautions to prevent reconnection. 3. Open the front cover. 4.
3. Installation 3 6. The Protective Earth wire (PE) is mandatory and must be connected directly to the chassis PE terminal. Insert the wire and fasten the screw to secure the wire. 7. All wires must be properly fastened with the correct torque. See the section Technical Data, Torque Specifications for Installation. 8. Close the front cover, and remember to verify that both front screws are applied with the correct torque to obtain PE connection. 9. Close main circuit breaker.
3. Installation When unmated the MC4 connectors are not IP54. The intrusion of moisture may occur in the following situations: 1. The inverter runs in Master/Slave operation and only one or two PV inputs are in use. In this case, the other inputs are not connected to PV and they are therefore open to intrusion. 2. Not all PV inputs are connected. 3. PV connectors are not fitted; for example in case of disconnection of parts of a PV plant over a longer period of time.
4. Start-up and Check of Settings 4. Start-up and Check of Settings 4.1. Start-up and Check of Settings Note: Due to the advanced functionalities of the inverter, it may take up to 10 seconds before the display becomes available after power up. 4 Note: For the version the first start-up and check of settings can also be performed via the integrated Web Server. For further details, refer to the Web Server User Manual. The inverter is shipped with a predefined set of settings for different countries.
4. Start-up and Check of Settings Set time as prompted by the display. Press 'OK' to select number. Press ‘ ▲ ’ to scroll up through the numbers. Select by pressing 'OK'. The clock is 24-hour format. 4 Illustration 4.2: Set Time Note: It is very important to set the time and date accurately as the inverter uses this for logging. If a wrong time/date is accidentally set, correct it immediately in the set date and time menu [Setup → Inverter details → Set date and time].
4. Start-up and Check of Settings Enter the amount of installed PV power for each of the PV inputs. When two or more PV inputs are connected in parallel, each PV input in the parallel group must be set to the total amount of PV power installed to that group divided by the number of parallel inputs. See the table below for examples of installed PV power. 4 Illustration 4.4: Installed PV Power The display will now show “Select country”. The country is set to “undefined” at initial start-up.
4. Start-up and Check of Settings Note: If the two country selections do not match they will be cancelled and it will be necessary to redo the selections. If a wrong country is accidentally accepted at the first selection, simply accept the “Country: Undefined” in the confirm country screen. This will cancel the country selection and a new selection is possible. If a wrong country is selected twice, call service. The inverter will start automatically if sufficient solar radiation is available.
4. Start-up and Check of Settings of larger networks. Replication can be performed once, prior to defining the country setting in follower inverters. To enable Master mode go to the Inverter details menu [Setup → Inverter details → Master mode] and set Master mode to Enabled. Ensure that no other master inverters are present in the network prior to carrying out this action. When Master mode is enabled, it is possible to initiate a network scan [Setup → Inverter details → Master mode → Network].
5. Technical Data 5. Technical Data 5.1. Technical Data Nomenclature 1) Pac,r Vac,r Iacmax cosphiac,r fr Vdc,r Vmppmin Vmppmax Vdcmax Vdcstart Vdcmin Idcmax Protect PV 10 kW Parameter AC Max./Nom. power AC Reactive power range AC voltage range (P-N) Nominal current AC Max. current AC AC current distortion (THD %) Power factor at 100 % load Controlled power factor range “Connecting” power loss Night-time power loss (off grid) Grid frequency DC Nominal power DC Max.
5. Technical Data 1) 2) 3) 4) According to FprEN 50524. For fixed systems with semi-optimal conditions. At identical input voltages. At unequal input voltages, Vmppmin can be as low as 250 V depending on total input power. SPL (Sound Pressure Level) at 1.5m.
5. Technical Data Parameter Temperature Environmental class according to IEC Specification -25°C - +60°C (>45°C derating) IEC60721-3-3 3K6/3B3/3S3/3M2 Air quality ISA S71.04-1985 Level G2 (at 75%RH) Coastal, heavy industrial and farmer areas Must be measured and classified acc. to ISA S71.04-1985 Vibration 1G Ingress protection class 54 Max. operating altitude 3000m above sea level. PELV protection is effective up to 2000m above sea level only. Installation Avoid constant stream of water.
5. Technical Data 5 Illustration 5.1: Protect PV 10 kW Cable Losses [%] versus Cable Length [m] Illustration 5.2: Protect PV 12.5 kW Cable Losses [%] versus Cable Length [m] Illustration 5.
5. Technical Data - Layout type (inside wall, under ground, free air etc.) - UV resistance 5 Illustration 5.4: Overview of Inverter with Torque Indications 1 2 3 4 5 6 7 Parameter Front screws Locking screw Terminal blocks (small) Terminal blocks (large) PE M16 M25 Screwdriver TX 30 TX 30 Straight slot 0.5x3.0 mm Straight slot 1.0x5.5 mm Straight slot 1.0x5.5 mm SW 19 mm SW 30 mm Tightening Torque 6-8 Nm 5 Nm 0.5 Nm Min. 1.2 Nm 2.2 Nm 2-3 Nm 2-3 Nm Table 5.
5. Technical Data 5.1.2. Wiring Diagram 5 Illustration 5.
5. Technical Data 5.1.3. Auxiliary Interface Specifications Parameter Serial Communication Common cable specification RJ45 (2 pcs.) connectors Parameter details Cable jacket diameter (⌀) Cable type Cable Characteristic Impedance Max. cable length Wire gauge Cable shield termination Maximum wire gauge Cable shield termination Terminal block Max.
5. Technical Data 1) Max. number of inverters are 100. If GSM modem is used for portal upload, the amount of inverters in a network is limited to 50. 2) For outdoor use, we recommend outdoor burial type cable (if buried in the ground) for both Ethernet and RS485. 3) Third input is used for compensation of the irradiation sensor. 4) The number of inverters to be connected in the RS485 network depend on which peripheral device is connected.
5. Technical Data 5.1.4. RS485 Communication Board Connections 5 Illustration 5.7: RS485 Detail of Communication Board. BIAS L and Bias H are to be connected to RX/TX B and RX/TX A respectively for termination of RS485 bus. Pinout RS-485 Pinout Ethernet only, via the RJ45 connector 1. GND 1. RX+ 2. GND 2. RX 3. RX/TX A (-) 3. TX+ 4. BIAS L 4. 5. BIAS H 5. 6. RX/TX B (+) 6. TX7. Not connected 7. 8. Not connected 8.
France & Africa Italy Czech Republic AEG Power Solutions ZI 10 rue Jean Perrin 37173 Chambray-lès-Tours Tel: + 332 47 80 88 96 Fax: + 332 47 80 88 38 service.fr@aegps.com Email: AEG Power Solutions Via Trento 30 20059 Vimercate – Milan Tél : +39 0 39 686 3837 Fax : +39 0 39 686 3847 service.it@aegps.com Email: AEG Power Solutions spol. s r.o. Na vlastní pude 6/1368 102 00 PRAHA 15 Hostivar Tel: + 420 602 316 314 Fax: + 420 274 773 265 Email: service.cz@aegps.