Access Control Systems / Wander monitoring INSTRUCTIONS FOR USE ACCESS CONTROL SYSTEM PE3LR WANDER MONITORING AD-CARE
Access Control Systems / Wander monitoring SUMMARY PE3LR / AD-CARE SYSTEM OVERVIEW P. 1 WORKING PRINCIPLE SYSTEM COMPONENTS - READERS/CONTROLLERS/SOFTWARE P. 2 SYSTEM COMPONENTS - TAGS / CARDS / AD-CARE-W WRIST P. 4 PE3LR / AD-CARE STAND ALONE SYSTEM DETAILS P. 6 Technical specifications PE3LR-C / AD-CARE Stand-alone controller P. 6 Wiring information PE3LR-C / AD-CARE Stand-alone controller P. 7 Technical specifications PE3LR-E external reader P.
Access Control Systems / Wander monitoring PE3LR / AD-CARE SYSTEM OVERVIEW ADVEEZ TECHNOLOGY ADVANTAGES 100% Hands Free Access: accurate, long range, compatible with ADVEEZ & existing OEM access control systems The ADVEEZ PE3LR is a hands-free access control system that combines precision, long range and 3D detection. It offers very convenient and efficient access control via the ADVEEZ PE3RL-T card/tag which can be carried in a bag or pocket and still be quickly identified.
Access Control Systems / Wander monitoring PE3LR / AD-CARE SYSTEM OVERVIEW INSTALLATION OVERWIEW Request to Exit button input (2 wires) PE3LR-C / AD-CARE-C main controller Door contact input (2 wires) PE3LR-E External antenna wiring (passive reader) (6 wires) Magnetic Lock Door strike Relay output 1 (2 wires) Additional contact Relay output 2 (2 wires) Alarm, Display…..
ands-free Access Control Access Systems Control/ System WanderPE3LR monitoring SYSTEM COMPONENTS PE3LR / AD-CARE SYSTEM COMPONENTS— PE3LR/AD-CARE controller & PE3LR external antenna—FCC ID: R8T-PE3LR-C INTERNAL READER—PE3LR-C / AD-CARE STAND-ALONE CONTROLLER Hands-free Access Control – 1 access point 1024 cards in stand-alone version (64000 users in network version) Program cards directly with Master Card (PE3LR-MC) or management software via PC– USB Cable The Internal Reader function PE3LR-C Door Controll
Access Control Systems / Wander monitoring SYSTEM COMPONENTS PE3LR / AD-CARE SYSTEM COMPONENTS—CREDENTIALS HANDS-FREE TAG PE3LR-T (FCC-ID: R8T-PE3LR-T*) CR2032 battery life: 2,000,000 hands-free tag activations Tag dimensions 74 mm/ 34 mm / 10 mm Hands-free badge color options: Black (ref: RAL9004), Grey (ref: RAL9006) - Red Master Tag PE3LR-T-MC enables programming tags Inserting CR2032 battery Declip tag cap and insert battery in holder “This device (FCC ID : R8T-PERL3-T) complies with part
Access Control Systems / Wander monitoring SYSTEM COMPONENTS PE3LR / AD-CARE SYSTEM COMPONENTS—CREDENTIALS AD-CARE-W WANDER MONITORING WRIST (FCC-ID: R8T-AD-CARE-W*) CR1632 battery life: 2,000,000 wander monitoring activations Housing dimensions 52 mm/ 40 mm / 9,5 mm White anti-batcterial plastic housing 1 way white wrist material: Vinyl Wrist width: 16 mm TORX SCREW DIAM. 2.
Access Control Systems / Wander monitoring PE3LR / AD-CARE Controller specifications / mounting instructions PE3LR-C / AD-CARE-C controller (FCC-ID : R8T-PE3LR-C*) Stand alone door controller PE3LR-C / AD-CARE (health care variant) Programming via PC 2 frequency RF system Both ADVEEZ hands Free + 125 kHz EM cards supported 12V/24V power supply with no configuration needed 200 mA average current draw / 1A peak Operating temperature : -20°C / +70°C Protection class: IP54 Weight: 0.
Access Control Systems / Wander monitoring WIRING INFORMATION—TERMINAL BLOCK DETAILS PE3LR/AD-CARE Controller Block 1 – BLUE– 4 Pins – POWER SUPPLY –RTE button Pin 1: 12V/24V Pin 2: GROUND 1 B2 B1 Pin 3: Request To Exit button + Pin 4: Request To Exit button - Block 2 – GREY- 6 Pins – 2 Relay / Door contact Pin 1: Relay– NO2 B4 B3 Reset Button Pin 2: Relay - C2 U17 1 1 Pin 3: Relay– NC2 Pin 1: Relay– NO1 Pin 2: Relay- C1 Connector for USB-PC communication Pin 3: Relay – NC1 Jumper configurat
Access Control Systems / Wander monitoring Wiring information - PE3LR/AD-CARE interface to access CTL & nurse call BLOCK 3 : NURSE CALL (ESPA4.4.4 output or POCSAG TEXT or ASCII) Pin 1: RS485-B RS485-RS232 TX Pin 2: RS485-A Converter RX 446 MHz Pin 3: GROUND Contacteur de porte Pin 4: DATA 1 - Wiegand Access control—door controllers Pin 5: DATA 0 - Wiegand Access control—door controllers Protocole configuration depending on device downstream of AD-CARE controller : Select tick box ESPA4.4.
Access Control Systems / Wander monitoring WIRING INFORMATION—PE3LR / AD-CARE—LOCKING DEVICES / RELAYS / POWER SUPPLY Block 2 – GREY - 6 contacts – 2 Relay / Contacts—Door strike configuration (NO) + door strike Pin 1: Relay – NO2 12V/+Alim Pin 2: Relay - C2 0V/-PWR Pin 3: Relay – NC2 Pin 1: Relay – NO1 Intrusion—Alarm wiring depends on device Pin 2: Relay - C1 Manufaturer / type Pin 3: Relay – NC1 Block 2 – GREY - 6 contacts – 2 Relay / Contacts—Magnetic Lock configuration (NC—permanently supplied)
Access Control Systems / Wander monitoring WIRING INFORMATION PE3LR / AD-CARE PE3LR-E EXTERNAL READER (FCC-ID : R8T-PE3LR-C*) Reading of hands free card PE3LR-T with high reading distance accuracy PE3LR-E enables extending detection zone by connecting it to PE3LR-C PE3LR-C-MC Mounting on standard wall box– 2 screws (minimum distance from a metal surface: 5 cm) (caution: avoid mounting close to 125kHz proximity card readers) 12V / 24V Connection via removable terminal block 2 colors (red/green) LED actua
Access Control Systems / Wander monitoring Single-reader configuration - PE3LR-C / AD-CARE The access control can work with the single door PE3LR-C is positioned on entry on the inside wall or on the outside wall depending on wall metal content controller/internal reader. The following drawing shows the detection zone inside the ring. In this configuration, the access control works in both Zone to be secured direction (internal and external).
Access Control Systems / Wander monitoring PE3LR-E located on the entrance PE3LR-C controller Located in the zone to be secured ZONE 1 ZONE 2 Sensing movement direction via PE3LR-C door controller Drawing below shows 2 separated zones, each being fitted with 1 external reader close to entrance and 1 controller/internal reader inside. Door controller’s jumper J1 is activated so that reader function gets activated. Door controller’s jumper J4 is deactivated so that access control is not active on exit.
Hands-free access control system PE3LR ADVEEZ SUPERVISED SYSTEM : connecting PE3LR & AD-CARE controllers TECHNICAL SPECIFICATIONS PE3LR-NT NETWORK CONTROL Manage Access authorization for all card types Control 128 doors in Radio / RJ-45 / RS-485 mode In the radio mode, each Controller PE3LR-C-NT is a network access point Central access control management: users, credentials, readers, etc.