User's Manual

SI Instructions 07.09
w w w . a d u r a t e c h . c o m
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful Interference when the equipment
is operated in a commercial environment. The equipment generates, uses and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause harmful interference to radio communica-
tions. Operation of the equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his/her own expense.
Class A Digital Devices
CAUTION
• Disconnect all power before installation or service.
• All installation and maintenance work must be performed by qualified personnel.
• The Sensor Interface must be installed in accordance with state, local and national
electrical codes and requirements.
INSTALLATION
INSTRUCTION MANUAL
WARRANTY INFORMATION
Adura Technologies
warranties its products to be free of defects for a period of five years. Adura Technologies will, at its option,
repair or replace any product that is defective in materials or manufacture that is returned to ADURA within the warranty period.
This warranty is void if this product has been installed improperly or in an improper environment, overloaded, misused, or altered
in any manner, or not installed in accordance with any labels or instructions. Adura Technologies is not liable for incidental, indirect,
special, or consequential damages, including without limitation, damage to, or loss of use of property, revenue or profit. This
warranty does not cover the cost of installation, removal or reinstallation.
To comply with RF exposure compliance requirements, for mobile configurations, a separation distance of at least 20 cm must be
maintained between the antenna of this device and all persons. This device must not be co-located or operating in conjunction with
any other antenna or transmitter.
Installation Materials (Not Supplied)
Wiring connectors. All existing wiring connectors must be replaced with new UL listed
wiring connectors, either wire nuts or captive-type connectors. All wiring connectors must
be correctly sized for the application, the number and the size of the electrical conductors.
sensor interface
The Sensor Interface is to be used in lighting systems to control lighting in commercial and
industrial buildings. It transmits signals received from an occupancy sensor and from a
photocell onto ADURA’s™ wireless network.
The Sensor Interface is intended to be used in a network of devices which communicate
wirelessly, such as Light Controllers, wall control devices and software management tools.
The Sensor Interface is intended to mount onto an electrical junction box. Often, the
Sensor Interface and the junction box will be mounted in the space above a finished
ceiling. The Sensor Interface is intended for indoor use only. It is rated for mounting in
a plenum.
The Sensor Interface is a low voltage device that must be powered by a Class 2 power
supply.
The Sensor Interface has 2 input channels:
• Channel 1 = Blue Wire
• Channel 2 = Yellow Wire
Either channel can be used to monitor standard low voltage occupancy sensors, low
voltage photocells and dry contracts.
Specications:
Input Voltage:
Power Consumption:
Radio Frequency:
RF Transmission Output Power (Average):
15 – 30 VDC
11 mA
2.4 GHz
+12 dBm
40 to 120 deg F, dry location
Dimensions:
Operating Environment:
Sensor Input Channels (2):
Configuration Programming:
Configuration programming
stored in non-volatile memory
Mounting:
UL Listing: UL 2043 plenum rated
0 - 30 VDC
Wires: 9" 600 VAC plenum rated, 18 AWG solid conductors
3 1/4” L x 1 7/16“ W x 1” H
Ordering Information:
Catalog Number Description
Sensor Interface - 2 Input ChannelsSI - 2C