Installation Manual

Specifications:
OrderingInformation:
LC-1R
LCInstructions03.09
Singlerelay
LC-2R
Tworelay
Optionalexternalantenna
XA
CatalogNumber Description
ADURATECHNOLOGIES
SanFrancisco,CA94105
Tel:415.227.0868•TollFree1-888-828-8281
ADURATECHNOLOGIES
SanFrancisco,CA94105
Tel:415.227.0868•TollFree1-888-828-8281
www . aduratech .co m
lightcontroller
ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,pursuant
toPart15oftheFCCRules.TheselimitsaredesignedtoprovidereasonableprotectionagainstharmfulInterfer-
encewhentheequipmentisoperatedinacommercialenvironment.Theequipmentgenerates,usesandcan
radiateradiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructionmanual,maycause
harmfulinterferencetoradiocommunications.Operationoftheequipmentinaresidentialareaislikelytocause
harmfulinterferenceinwhichcasetheuserwillberequiredtocorrecttheinterferenceathis/herownexpense.
ClassAdigitaldevices
InputVoltage:
InputFrequency:
Relays:
MaxSwitchedCurrent:
RadioFrequency:
RFTransmissionOutputPower(Average):
100‒277VAC
60Hz
Normallyopen,SPST,zerocrossingcontrol
5ABallast/5ATungsten(LC-2R=5Ax2relays)
2.4GHz
+12dBm
Mounting: Magnetsorscrewsinsideof
aUL-ratedfixtureorenclosure
ratedfortheapplication.
Dimensions:
OperatingEnvironment: 40to140degF
Memory:
Configurationprogramming
storedinnon-volatilememory
Currentmeasurement:
Voltagemeasurement: 2%accuracyfullscale
2%accuracyfullscale
Wires: 24”Long,600VACRated,18AWGsolidconductors
7”5/8Lx1“3/16Wx1”H
CAUTION
• Disconnect all incoming power before installation or service.
• All installation and maintenance work must be performed by qualified
personnel.
• The Light Controllers must be installed in accordance with state, local
and national electrical codes and requirements.
• Light Controller must be installed within a UL-rated fixture or enclosure
rated for this application.
INSTALLATION
INSTRUCTION MANUAL
The Light Controller is to be used to control lighting in commercial and
industrial buildings. It provides control of lights (on/off or dimming) by
means of commands transmitted and received via radio frequency. The
Light Controller is intended to be used in a network of devices which
communicate wirelessly including wall switches, occupancy sensors,
gateways and computer software applications.
The Light Controller is to be mounted inside the enclosure of a light fixture
or in a separate UL- rated enclosure. In the case of fluorescent lights, the
Light Controller is to be installed inside the ballast cavity of a standard
fluorescent luminaire.
The Light Controller is intended to be used to control fluorescent ballasts,
incandescent lights, LED drivers, and HID ballasts.
There are 3 models of the Light Controller:
• LC-1R has one relay and is intended to control one light fixture or group
of light fixtures.
• LC-2R has two relays and is intended to control two levels of light
within one fixture or two fixtures or two groups of light fixtures.
• LC-1RD has one relay and a low voltage dimming output (Class 1 rated)
intended to control standard 0-10 VDC dimming ballasts. Each LC-1RD
can provide dimming control to a maximum of 5 standard 0-10 VDC
dimming ballasts.
LC-1RD Singlerelaywith0-10VDCdimming
WARRANTYINFORMATION
AduraTechnologieswarrantiesitsproductstobefreeofdefectsforaperiodoffiveyears.AduraTechnologieswill,atitsoption,repairor
replaceanyproductthatisdefectiveinmaterialsormanufacturethatisreturnedtoADURAwithinthewarrantyperiod.Thiswarrantyis
voidifthisproducthasbeeninstalledimproperlyorinanimproperenvironment,overloaded,misused,oralteredinanymanner,ornot
installedinaccordancewithanylabelsorinstructions.AduraTechnologiesisnotliableforincidental,indirect,special,orconsequential
damages,includingwithoutlimitation,damageto,orlossofuseofproperty,revenueorprofit.Thiswarrantydoesnotcoverthecostof
installation,removalorreinstallation.
TM TM
Installation Materials (Not Supplied)
Wiring connectors. All existing wiring connectors must be replaced with
new UL-listed wiring connectors, either wire nuts or captive-type connectors.
All wiring connectors must be correctly sized for the application, the number
and the size of the electrical conductors.
Sheet metal screws. As an option, the Light Controller can be secured
with 2 #8 sheet metal screws.