Installation Instructions

PROSiXSMOKEV
Wireless Smoke/Heat Detector
Installation Instructions
This is a multi-criteria wireless smoke
detector which employs advanced levels
of detection and discrimination to
reduce common cooking nuisance
alarms and faster to different types of
fire conditions. It is intended for use
with Controls that support PROSiX™
series devices.
To remove the mounting bracket, turn
the top of the detector 15 degrees
counterclockwise and separate the
mounting bracket and top cover.
PROSiXSMOKEV
Open
Enrollment
Enroll the device using AlarmNet 360. When prompted, activate the
device by pulling the battery tab or, if already powered, press the
Test button to enroll. It will enroll into 2 zones: smoke detection into
one zone and heat detection into a second zone.
If the detector is not successfully enrolled during the enrollment
period, the LED turns off and the device powers down. Activate the
tamper or press the Test Button to restart the enrollment process.
NOTES: Enrollment time varies depending on the signal strength
between the device and the Control. Once enrolled in a system, the
detector cannot be used with another Control until it is removed from
the current Control. See the Control’s instructions for details.
Enroll
Program
Consult the Control’s instructions to program the device in the system. This detector reports the following signals to the Control:
Smoke and Heat detection
- Smoke Alarm when smoke is detected
- Heat Alarm when temperature of 135° F (57° C) or greater
- Rate-of-Rise Alarm when temperature is >104° F (40° C) @ 15° F/minute (8.33° C/minute).
Maintenance: Contaminated chamber that requires cleaning.
End-of-Life
Base Tamper: It will send a tamper signal to the control when the smoke head is removed from its base.
Supervision: 200 second check-in compatible.
Signal and battery Strength: Signal and battery strength information are sent with every communication to the panel.
NOTE: If programmed in the Control to operate in One-Go-All-Go mode, all smoke detectors programmed as One-Go-All-Go in the
system will sound on alarm.
Tamper
When the detector is removed from its base, it will send a tamper signal to the Control. OPTIONAL: The detector can be made
tamper-proof to prevent unauthorized removal from its base. Break off the small pillar on the base as shown. This will cause the
detector to latch to the base. From this point on, to remove the detector from its base, you must use a small screwdriver to release
the catch (push the catch towards the base) and twist the detector counter-clockwise. A screw can be added to prevent removal
from the base.