Safety Instructions

1 of 3
rPP20 Relay Pack
POWER/RELAY PACK
FAMILY INSTRUCTIONS
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/08/2020
912-00056-002 FCC ID: 2ADCB-RMODIT IC: 6715C-RMODIT IFETEL: RCPACRM18-1879 Acuity Brands Lighting Inc. RMODIT
Electrical Specifications Input Ratings 120-277VAC
Maximum Load 20A general purpose, tungsten and standard
ballast; 16A electronic ballast
Dimming Load Sinks 100mA; 0-10VDC dimmable ballasts
or LED drivers; “D” 0-10V leads Class 1, “DS”
0-10V leads Class 2
Minimum Load None
Class Rating 0-10V Dimming can be wired Class 1 or 2
Mechanical Mounting 1/2” Knockout (7/8” hole)
Connection Type Line and Low Voltage Leads
Environmental Warrantied Operating Temperature -10°C to 60°C up to 5 amps; -10°C to 50°C up
to 20 amps
Standards/ Ratings RoHS, UL 916, UL 924 (optional), FCC / IC / IFETEL
SPECIFICATIONS (rPP20)
READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
IMPORTANT SAFEGUARDS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD
ALWAYS BE FOLLOWED INCLUDING THE FOLLOWING:
DO NOT USE OUTDOORS.
DO NOT MOUNT NEAR GAS OR ELECTRIC HEATERS.
EQUIPMENT SHOULD BE MOUNTED IN LOCATIONS AND AT HEIGHTS WHERE
IT WILL NOT READILY BE SUBJECTED TO TAMPERING BY UNAUTHORIZED
PERSONNEL.
THE USE OF ACCESSORY EQUIPMENT NOT RECOMMENDED BY THE
MANUFACTURER MAY CAUSE AN UNSAFE CONDITION.
TITLE 20/24
Do not exceed maximum wattage, ratings, or published
operation conditions of product.
Do not overload.
Follow all manufacturer’s warnings, recommendations
and restrictions to ensure proper operation of product.
To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions included with and on the fixture box and all fixture labels.
Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
Installation and service should be performed by a qualified licensed electrician.
Maintenance should be performed by qualified person(s) familiar with the products’ construction & operation & any hazards involved. Regular maintenance programs recommended.
To be installed to a circuit with overvoltage control to Overvoltage category Cat.III or less, minimum suppression rating 6.0 kV for a 600 V ac rms system voltage
DO NOT INSTALL DAMAGED PRODUCT! This product has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any part damaged or broken during or after assembly should be replaced.
CAUTION: RISK OF PRODUCT DAMAGE
Electrostatic Discharge (ESD): ESD can damage product(s). Personal grounding equipment should be worn
during all installation or servicing of the unit.
Do not touch individual electrical components, as this can cause ESD and aect product performance.
Do not stretch or use cable sets that are too short or are of insucient length.
Do not tamper with contacts.
Do not modify the product.
Do not change or alter internal wiring or installation circuitry.
Do not use product for anything other than its intended use.
WARNING - RISK OF BURN or FIRE
CAUTION - RISK OF INJURY
Wear gloves and safety glasses at all times when
installing, servicing or performing maintenance.
WARNING - RISK OF ELECTRIC SHOCK
Disconnect or turn o power before installation or servicing.
Verify that supply voltage is correct by comparing it with the
product information.
Make all electrical and grounded connections in accordance with
the National Electrical Code (NEC) and any applicable local code
requirements.
All wiring connections should be capped with UL approved
recognized wire connectors.
All unused connector openings must be capped.
C US LISTED
WARRANTY
5-year limited warranty.
Full warranty terms located at: www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
NOTE: Specications subject to change without notice.
Actual performance may dier as a result of end-user environment and application.
FCC ID: 2ADCB-RMODIT
IC: 6715C-RMODIT
IFETEL: RCPACRM18-1879
Acuity Brands Lighting Inc. RMODIT
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
Este equipo contiene el módulo con IFT #: RCPRIBM18-1491 La operación de este equipo está sujeta a las
siguientes dos condiciones: (1) es posible que este equipo o dispositivo no cause interferencia perjudicial y (2)
este equipo o dispositivo debe aceptar cualquier interferencia, incluyendo la que pueda causar su operación
no deseada.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
1. Reorient or relocate the receiving antenna.
2. Increase the separation between the equipment and receiver.
3. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
4. Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development Canada’s licence-exempt RSS(s). Operation is subject to the following two conditions:
1. This device may not cause interference.
2. This device must accept any interference, including interference that may cause undesired operation of the device.
Lémetteur/récepteur exempt de licence contenu dans le présent appareil est conforme aux CNR d’Innovation, Sciences et Développement économique Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée
aux deux conditions suivantes :
1. Lappareil ne doit pas produire de brouillage;
2. Lappareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.